06-782R-008n ELECTRICAL SYMBOL LEGEND NOTE: ® CONNECT EXIT AND EMERGENCY LIGHTS TO NEAREST LIGHTING CIRCUIT AHEAD OF SWITCHES AND CONTROL DEVICES. ELECTRICAL NOTES 1. ALL CONDUCTORS SHALL BE COPPER, RATED 75 C WET /DRY EXCEPT WHERE OTHERWISE REQUIRED BY U.L. OR CODES, LION. MINIMUM WIRE SIZE SHALL BE #12 AWG. EXCLUDING CONTROL WIRING. 2. ALL CONDUIT RISERS SHALL BE RIGID GALVANIZED STEEL (RGS). WHERE CONDUIT BENDS UPWARD FROM UNDERGROUND TO ABOVE GROUND, USE AN APPROVED PVC TO RGS COUPLER, AS REQUIRED. RGS CONDUITS SHALL EXTEND A MINIMUM OF 18' BELOW GRADE. 3. UNLESS NOTED AS EXISTING, ALL EQUIPMENT, WIRING, DEVICES, ETC. SHALL BE NEW. 4. ENTIRE INSTALLATION SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE, LATEST EDITION (NEC ) AND THE LATEST EDITIONS OF THE FLORIDA BUILDING CODE AND ALL LOCAL CODES, RULES AND ORDINANCES HAVING JURISDICTION. 5. ALL CONDUIT RUNS ARE SHOWN DIAGRAMMATICALLY. EXACT ROUTING SHALL BE DETERMINED IN THE FIELD, UNLESS OTHERWISE NOTED. 6. ALL DISCONNECT SWITCHES SHALL BE SIZED BY NEC TO ACCOMMODATE EQUIPMENT SERVED, INCLUDING REQUIRED FUSES, LION. SWITCHES SHALL BE HORSE POWER RATED AND SIZED FOR 1/2 MAX. HORSEPOWER, HEAVY DUTY TYPE. 7. ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT WHERE EXPOSED TO THE WEATHER. ALL FLEX CONDUITS CONNECTED TO SUCH EQUIPMENT SHALL BE LIQUID TIGHT. 8• WIRE WAYS SHALL BE SIZED AS REQUIRED, PER NEC, UNLESS OTHERWISE NOTED (LION). 9. COORDINATE ALL ELECTRICAL SITE WORK WITH GENERAL CONTRACTOR. 10. FOR UNDERGROUND ELECTRICAL CONDUITS, PROVIDE FULL BOXES, SUCH THAT NO SINGLE CONDUIT RUN HAS BENDS IN EXCESS OF 360. PULL BOXES SHALL BE SUITABLE AND APPROVED FOR THE INTENDED USE. WARNING TAPE WHICH SAYS 'WARNING BURIED ELECTRIC SHALL BE PLACED IN TRENCHES AB N ABOVE ALL UNDERGROUND ELECTRIC CONDUITS. WHERE CONDUITS PASS UNDERNEATH PAVED AREAS, THEY SHALL BE RGS. WHERE UNDERGROUND CONDUITS ARE NOT EXPOSED TO MECHANICAL DAMAGE OR ARE NOT UNDER PAVED AREAS, THEY SHALL 13E SCHEDULE 40 PVC. ALL CONDUIT RISERS SHALL BE RGS. 11. FOR TELEPHONE SYSTEM: A PROVIDE GROUNDING FOR ALL TELEPHONE OUTLETS AND EQUIPMENT PER REQUIREMENTS OF TELEPHONE COMPANY. B. VERIFY LOCATION OF TELEPHONE SERVICE WITH TELEPHONE COMPANY, PRIOR TO SUBMITTING BID. 12. ALL CIRCUIT BREAKERS SHALL BE INVERSE TIME TYPE (THERMAL MAGNETIC). TWO AND THREE POLE CIRCUIT BREAKERS SHALL BE COMMON TRIP. NO TIE HANDLES PERMITTED. 13. ALL ELECTRICAL EQUIPMENT, DEVICES, WIRE, ETC., SHALL BE USTED, FOR THE INTENDED USE, WITH UNDERWRITER'S LABORATORY, INC. (U.L.) WHERE STANDARDS HAVE BEEN ESTABUSHED BY U.L 14. ALL CONDUCTORS )SHALL BE IN CONDUITS. ALL C(OND)UITS SHALL BE EXCEPT THAT: (A)�TP LY VINYL CHLIORIDEV(PVC)) CONDUITS RMAY BE USED IN CONCRETE SLABS AND UNDERGROUND PROVIDED ELBOWS AND RISERS ARE RGS; (B) ELECTRICAL NON— METALLIC TUBING (ENT) MAY BE USED IN OR ON WALLS OR CEILINGS WHERE NOT SUBJECT TO MECHANICAL DAMAGE DAMP CONDITIONS OR CORROSIVE CO DITIONS C) LIQUID TIGHT FLEXIBLE CONDUIT WHERE REQUIRED, D� FLEXIBL METALLIC CONDUIT WHERE REQUIRED IN DRY LOCATION. ALL CONDUITS IN HAZARDOUS AREAS PER NEC SHALL MEET THE REQUIREMENTS OF NEC CHAPTER 5. 15. PROVIDE LAMPS WITH FIXTURES, VERIFY LAMP TYPE WITH MANUFACTURER. 16. COORDINATE ELECTRIC SERVICE WITH POWER COMPANY. 17. ELECTRICAL CONTRACTOR SHALL NOT SCALE DRAWINGS. CONTRACTOR SHALL REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT LOCATIONS OF ALL EQUIPMENT UNLESS NOTED OTHERWISE. 18. ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL CONDITIONS, LOCATIONS, DIMENSIONS AND COUNTS AS SHOWN AND /OR NOTED ON THE DRAWINGS. THIS SHALL INCLUDE ANY AND ALL FABRICATIONS PRIOR TO INSTALLATION. 19. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR FOR THE ADVANCED ORDERING OF LONG LEAD ITEMS, AS NOT TO INTERFERE WITH THE PRODUCTION OF OTHER TRADES RESULTING IN ANY DOWN OR LAG TIME. 20. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO PROVIDE ALL LABOR, MATERIALS AND SUPERVISION NECESSARY TO ACCOMPLISH THE WORK AS SHOWN AND /OR NOTED ON THE DRAWINGS. 21. IT SHALL BE UNDERSTOOD THAT ALL WORK PERFORMED SHALL BE DONE BY A LICENSED ELECTRICAL CONTRACTOR AND IN A FIRST —CLASS WORKMANLIKE MANNER. SAID CONTRACTOR SHALL MEET ALL REQUIREMENTS SET FORTH BY ANY LOCAL ORDINANCE AND GOVERNING AUTHORITIES. 22. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO REPAIR TO ORIGINAL CONDITIONS ANY AND ALL DAMAGES TO BUILDING SURFACES, EQUIPMENT AND FURNISHINGS CAUSED DURING PERFORMANCE OF WORK. 23. THE ELECTRICAL CONTRACTOR SHALL KEEP ALL AREAS IN WHICH WORK IS BEING PERFORMED, FREE FROM DEBRIS AT ALL TIMES AND SAID AREAS SHALL. BE LEFT BROOM CLEAN AT THE END OF EACH WORKING DAY. 24. IT SHALL NOT BE THE INTENT OF THESE PLANS AND /OR SPECIFICATION TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE ELECTRICAL CONTRACTOR SHALL BE EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER. 25. WHERE CORE DRILLING OF FLOOR/WALLS IS REQUIRED, CONTRACTOR SHALL SEAL OPENINGS WATERTIGHT AFTER UTILITIES HAVE BEEN INSTALLED. LOCATION OF CORED HOLES SHALL COORDINATE WITH LOCATION OF EQUIPMENT IN A MANNER TO BE CLEAN AND FUNCTIONAL THE CONTRACTOR SHALL INSTALL ONLY ONE CONDUIT PER HOLE AND SEAL THE OPENING AROUND THE CONDUIT AS SPECIFlED. 26. ELECTRICAL CONTRACTOR SHALL VERIFY CIRCUIT PROTECTIVE DEVICE RATING FOR EQUIPMENT PRIOR TO CONSTRUCTION. 27. METER CANS, HUBS, do LUGS FOR SAME ARE TO BE FURNISHED do INSTALLED BY ELECTRICAL CONTRACTOR. ELECTRICAL CONTRACTOR TO VERIFY SPECIFIC TYPE OF METER CAN TO BE USED WITH F.P.L. PRIOR TO BID. NOTE: ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NECESSARY WIRING TO FLOW do TAMPER SWITCHES. CORRD. W/ FIRE PROTECTION PLANS FOR EXACT QUANTITY AND LOCATION PRIOR TO BID, AND WITH APPROVED FIRE PROTECTION SHOP OWGS. PRIOR TO ROUGH — IN OR INSTALLATION OF ANY DEVICES. ----- - - - - -- EXISTING 1 FIRE ALARM ! PANEL ! L- ---------- J GROUND FLOOR FIRE ALARM RISER DIAGRAM N.T.S. Al LIGHTING FIXTURE SCHEDULE FLUORESCENT LIGHT FIXTURE 0/ MOTOR O Dom+ LIGHT ❑T TRANSFORMER I� FLUORESCENT STRIP ^/V\A/\ LL FLEXIBLE CONDUIT EXIT LIGHT -L GROUNDING ELECTRODE & CONDUCTOR SYSTEM q�0 u EMERGENCY BATTERY PACK © TELEVISION OUTLET (18' A.F.F.) Q DUPLEX RECPT - 20 AMP (FLOOR BOX) RECESSED DIRECT /INDIRECT INTERCOM SYSTEM 14C DUPLEX RECPT - 20 AMP (18' A.F.F.) w >O Z) ® CENTRAL VACUUM STATION INFINITY DUPLEX RECPT - 20 AMP (42' A.F.F.) 0 TELEPHONE OUTLET (FLOOR BOX) ® SPECIAL PURPOSE RECEPTACLE(18- A.F.F.) COMPACT FLUORESCENT TELEPHONE OUTLET (18' A.F.F.) � z0 SINGLE POLE SWITCH - 20 AMP (48' A.F.F.) 35K V) Q © COMPUTER OUTLET (18' A.F.F.) �LL. THREE WAY SWITCH - 20 AMP (48' A.F.F.) 1 75MR16 120 RECESSED © SMOKE DETECTOR (PHOTOELECTRIC TYPE) DIMMER SWITCH 2000 WATTS 48' A.F.F.) 1 10OA19 120 RECESSED Q DUCT SMOKE DETECTOR MOTOR RATED SWITCH 3 F035K8 120 RHEOSTAT FAN CONTROL (48' A.F.F.) QQ SPEAKER - CEILING MOUNTED EY FUSIBLE DISCONNECT SWITCH Q JUNCTION BOX ODAYBRITE 2AVG250TT -1 /2EB 31�12 POLE DISCONNECT FRAME O ELECTRICAL PANELBOARO RECESSED MANUFACTURER FUSE RECOMMENDATION Q THERMOSTAT 52', 5 BLADE CEILING FAN WITH FAN J -BOX ODAYBRITE 2DPG231U6- FA12 -1 /2EB VERIFY COLOR WITH TENANT ❑F FIRE ALARM PULL STATION (48' A.F.F.) ❑H FIRE ALARM HORN (80' TO BOTTOM) ® FIRE ALARM FLASHING STROBE LIGHT (80' TO BOTTOM) FIRE ALARM HORN WITH FLASHING STROBE LIGHT H (80' TO BOTTOM) rya INTENSITY OF STROBE T I BE LIGHT N CANDELA CYCLONE SERIES 1 LED 120 15 TAMPER SWITCH EM BEGHELLI ❑FS FLAW SWITCH NOTE: ® CONNECT EXIT AND EMERGENCY LIGHTS TO NEAREST LIGHTING CIRCUIT AHEAD OF SWITCHES AND CONTROL DEVICES. ELECTRICAL NOTES 1. ALL CONDUCTORS SHALL BE COPPER, RATED 75 C WET /DRY EXCEPT WHERE OTHERWISE REQUIRED BY U.L. OR CODES, LION. MINIMUM WIRE SIZE SHALL BE #12 AWG. EXCLUDING CONTROL WIRING. 2. ALL CONDUIT RISERS SHALL BE RIGID GALVANIZED STEEL (RGS). WHERE CONDUIT BENDS UPWARD FROM UNDERGROUND TO ABOVE GROUND, USE AN APPROVED PVC TO RGS COUPLER, AS REQUIRED. RGS CONDUITS SHALL EXTEND A MINIMUM OF 18' BELOW GRADE. 3. UNLESS NOTED AS EXISTING, ALL EQUIPMENT, WIRING, DEVICES, ETC. SHALL BE NEW. 4. ENTIRE INSTALLATION SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL CODE, LATEST EDITION (NEC ) AND THE LATEST EDITIONS OF THE FLORIDA BUILDING CODE AND ALL LOCAL CODES, RULES AND ORDINANCES HAVING JURISDICTION. 5. ALL CONDUIT RUNS ARE SHOWN DIAGRAMMATICALLY. EXACT ROUTING SHALL BE DETERMINED IN THE FIELD, UNLESS OTHERWISE NOTED. 6. ALL DISCONNECT SWITCHES SHALL BE SIZED BY NEC TO ACCOMMODATE EQUIPMENT SERVED, INCLUDING REQUIRED FUSES, LION. SWITCHES SHALL BE HORSE POWER RATED AND SIZED FOR 1/2 MAX. HORSEPOWER, HEAVY DUTY TYPE. 7. ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT WHERE EXPOSED TO THE WEATHER. ALL FLEX CONDUITS CONNECTED TO SUCH EQUIPMENT SHALL BE LIQUID TIGHT. 8• WIRE WAYS SHALL BE SIZED AS REQUIRED, PER NEC, UNLESS OTHERWISE NOTED (LION). 9. COORDINATE ALL ELECTRICAL SITE WORK WITH GENERAL CONTRACTOR. 10. FOR UNDERGROUND ELECTRICAL CONDUITS, PROVIDE FULL BOXES, SUCH THAT NO SINGLE CONDUIT RUN HAS BENDS IN EXCESS OF 360. PULL BOXES SHALL BE SUITABLE AND APPROVED FOR THE INTENDED USE. WARNING TAPE WHICH SAYS 'WARNING BURIED ELECTRIC SHALL BE PLACED IN TRENCHES AB N ABOVE ALL UNDERGROUND ELECTRIC CONDUITS. WHERE CONDUITS PASS UNDERNEATH PAVED AREAS, THEY SHALL BE RGS. WHERE UNDERGROUND CONDUITS ARE NOT EXPOSED TO MECHANICAL DAMAGE OR ARE NOT UNDER PAVED AREAS, THEY SHALL 13E SCHEDULE 40 PVC. ALL CONDUIT RISERS SHALL BE RGS. 11. FOR TELEPHONE SYSTEM: A PROVIDE GROUNDING FOR ALL TELEPHONE OUTLETS AND EQUIPMENT PER REQUIREMENTS OF TELEPHONE COMPANY. B. VERIFY LOCATION OF TELEPHONE SERVICE WITH TELEPHONE COMPANY, PRIOR TO SUBMITTING BID. 12. ALL CIRCUIT BREAKERS SHALL BE INVERSE TIME TYPE (THERMAL MAGNETIC). TWO AND THREE POLE CIRCUIT BREAKERS SHALL BE COMMON TRIP. NO TIE HANDLES PERMITTED. 13. ALL ELECTRICAL EQUIPMENT, DEVICES, WIRE, ETC., SHALL BE USTED, FOR THE INTENDED USE, WITH UNDERWRITER'S LABORATORY, INC. (U.L.) WHERE STANDARDS HAVE BEEN ESTABUSHED BY U.L 14. ALL CONDUCTORS )SHALL BE IN CONDUITS. ALL C(OND)UITS SHALL BE EXCEPT THAT: (A)�TP LY VINYL CHLIORIDEV(PVC)) CONDUITS RMAY BE USED IN CONCRETE SLABS AND UNDERGROUND PROVIDED ELBOWS AND RISERS ARE RGS; (B) ELECTRICAL NON— METALLIC TUBING (ENT) MAY BE USED IN OR ON WALLS OR CEILINGS WHERE NOT SUBJECT TO MECHANICAL DAMAGE DAMP CONDITIONS OR CORROSIVE CO DITIONS C) LIQUID TIGHT FLEXIBLE CONDUIT WHERE REQUIRED, D� FLEXIBL METALLIC CONDUIT WHERE REQUIRED IN DRY LOCATION. ALL CONDUITS IN HAZARDOUS AREAS PER NEC SHALL MEET THE REQUIREMENTS OF NEC CHAPTER 5. 15. PROVIDE LAMPS WITH FIXTURES, VERIFY LAMP TYPE WITH MANUFACTURER. 16. COORDINATE ELECTRIC SERVICE WITH POWER COMPANY. 17. ELECTRICAL CONTRACTOR SHALL NOT SCALE DRAWINGS. CONTRACTOR SHALL REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT LOCATIONS OF ALL EQUIPMENT UNLESS NOTED OTHERWISE. 18. ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY ALL CONDITIONS, LOCATIONS, DIMENSIONS AND COUNTS AS SHOWN AND /OR NOTED ON THE DRAWINGS. THIS SHALL INCLUDE ANY AND ALL FABRICATIONS PRIOR TO INSTALLATION. 19. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR FOR THE ADVANCED ORDERING OF LONG LEAD ITEMS, AS NOT TO INTERFERE WITH THE PRODUCTION OF OTHER TRADES RESULTING IN ANY DOWN OR LAG TIME. 20. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO PROVIDE ALL LABOR, MATERIALS AND SUPERVISION NECESSARY TO ACCOMPLISH THE WORK AS SHOWN AND /OR NOTED ON THE DRAWINGS. 21. IT SHALL BE UNDERSTOOD THAT ALL WORK PERFORMED SHALL BE DONE BY A LICENSED ELECTRICAL CONTRACTOR AND IN A FIRST —CLASS WORKMANLIKE MANNER. SAID CONTRACTOR SHALL MEET ALL REQUIREMENTS SET FORTH BY ANY LOCAL ORDINANCE AND GOVERNING AUTHORITIES. 22. THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO REPAIR TO ORIGINAL CONDITIONS ANY AND ALL DAMAGES TO BUILDING SURFACES, EQUIPMENT AND FURNISHINGS CAUSED DURING PERFORMANCE OF WORK. 23. THE ELECTRICAL CONTRACTOR SHALL KEEP ALL AREAS IN WHICH WORK IS BEING PERFORMED, FREE FROM DEBRIS AT ALL TIMES AND SAID AREAS SHALL. BE LEFT BROOM CLEAN AT THE END OF EACH WORKING DAY. 24. IT SHALL NOT BE THE INTENT OF THESE PLANS AND /OR SPECIFICATION TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION. THE ELECTRICAL CONTRACTOR SHALL BE EXPECTED TO FURNISH AND INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM AND PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER. 25. WHERE CORE DRILLING OF FLOOR/WALLS IS REQUIRED, CONTRACTOR SHALL SEAL OPENINGS WATERTIGHT AFTER UTILITIES HAVE BEEN INSTALLED. LOCATION OF CORED HOLES SHALL COORDINATE WITH LOCATION OF EQUIPMENT IN A MANNER TO BE CLEAN AND FUNCTIONAL THE CONTRACTOR SHALL INSTALL ONLY ONE CONDUIT PER HOLE AND SEAL THE OPENING AROUND THE CONDUIT AS SPECIFlED. 26. ELECTRICAL CONTRACTOR SHALL VERIFY CIRCUIT PROTECTIVE DEVICE RATING FOR EQUIPMENT PRIOR TO CONSTRUCTION. 27. METER CANS, HUBS, do LUGS FOR SAME ARE TO BE FURNISHED do INSTALLED BY ELECTRICAL CONTRACTOR. ELECTRICAL CONTRACTOR TO VERIFY SPECIFIC TYPE OF METER CAN TO BE USED WITH F.P.L. PRIOR TO BID. NOTE: ELECTRICAL CONTRACTOR SHALL PROVIDE ALL NECESSARY WIRING TO FLOW do TAMPER SWITCHES. CORRD. W/ FIRE PROTECTION PLANS FOR EXACT QUANTITY AND LOCATION PRIOR TO BID, AND WITH APPROVED FIRE PROTECTION SHOP OWGS. PRIOR TO ROUGH — IN OR INSTALLATION OF ANY DEVICES. ----- - - - - -- EXISTING 1 FIRE ALARM ! PANEL ! L- ---------- J GROUND FLOOR FIRE ALARM RISER DIAGRAM N.T.S. Al LIGHTING FIXTURE SCHEDULE TYPE MANUF. CATALOG NUMBER LAMPS VOLTS MOUNTING REMARKS O-p C LL Qty Type ODAYBRITE O 2AVG332- PMW- 1/3EB' 3 F035K8 120 RECESSED RECESSED DIRECT /INDIRECT W 14C v= F_ w >O Z) LL LIL O INFINITY PH60- 226Q- MWT -BH 2 PL26DTT 120 RECESSED COMPACT FLUORESCENT � z0 35K V) Q DOWNLIGHT OINFINITY �LL. LVDR45P- 75MR16- MWT -BH 1 75MR16 120 RECESSED LOW VOLTAGE DOWNLIGHT OINFINITY A60- 10OA19IF- MWT -BH 1 10OA19 120 RECESSED INCANDESCENT DOWNLIGHT ODAYBRITE 2DPG332- FA12 -1 /3EB 3 F035K8 120 RECESSED 2'X4' LENSED TROFFER ODAYBRITE 2AVG250TT -1 /2EB 2 F 0T 120 RECESSED 2'X2' DIRECT /INDIRECT ODAYBRITE 2DPG231U6- FA12 -1 /2EB 2 F03lT U 120 RECESSED 2'X2' LENSED TROFFER X BEGHELLI CYCLONE SERIES 1 LED 120 SURFACE EDGE LIT EXIT SIGN EM BEGHELLI LUNA 2 INCL 120 WALL 2 HEAD EMERGENCY -- - -------- - - - -- r-- I i I(MTD. ON WALL)- - :..._...__ ;..._..' ;. (TYP) G -11 ' ! ! + T1 0 11 i G-4 ! j i I . . ..... I : .L i_._T�4r_4— - -- -•� .._u._......_ ....... ...... ! - - -- ,L -- — ii ; ' i I � i P) _ !! ' (T Y — — ... ....... ; _ .... I I • -- '' - - - - - -- OA ,(TYP) Q ; TYP ; T ,s j - - - -- - ' THIS AREA :I , , v �BUILDING D PERMIT : A UNDER BASE/ - • / i THIS ARE / BUILDINGI PERMIT ( O _....... _ ............. ;._._ ...... iJ I j `. C TYP) VER. LOC. 3 � ; , : EM J 1' : . � 4! - -- -- 22 : t EM 2 3 TYP) G-13 J i', i ! -- - - _ I ( O I. 3 / "� (T.YP) i TY)\ (TIP) - 4 I C j i ! : i O I I EM (TYP) `, i i T3 -6 BI.. I ....... .. _. \ i ` i „ , i : ! : O TY• i I P �: ;`,� ( ) ., •3 ....._.. ...... _...._ it i .......... .... j.. • t' : i i I , i . EM EM G-15 I 42 EM ,, ..__ � •� E I J J EM T C Si I - EM / I ; EM , : • i , J \ `,� 'i \ � .. .. j . . _ �.. .. _ �.� � it ;Jj , ! (TIP) (TYP) ! '; t YP (TYP) • ' 3, I/ ! (TYP) : i O! : > 2 Q(3 TlC �S Vi X.::L Ex'rST1r1G �� t { OF E. I ;spy `t `' p v�nTHTH =p�c c!.s '•^ - = cX CCUPAtbC1ES, A$ SET PORiI 11N Tt- �., TL= p E. :_ . ... ! ► ---,--•= PA 101 LIFE C i E D _ ............ LIGHTING PLAN SCALE : 1/4"=V-011 ;REVISIONS No. O;NER QEOT x_ -REv. (3- 13 -06) Q OUNER REGIV. REV. Q f1 t� RE�YD. REV Q CE O-p C LL ON LL O 201 oo n.e. 21 avenue no. Hari beach, fI 33179 o ` C:) U o In CL CI te) CL I w O -i— Q) O ul w, t M � C— m u `U m JJ ci or 1 3039 c DRAWN A.H. CHECKED R.P. DATE 11 -30 -05 SCALE AS NOTED JOB NO. 0423 SHEET E -2 OF 4 SHEETS DO NOT SCALE Q • COO CE O-p C LL ON LL O . CCL cQ W 14C v= F_ w >O Z) LL LIL V) O J0 Q � z0 CC V) Q p� �LL. W DRAWN A.H. CHECKED R.P. DATE 11 -30 -05 SCALE AS NOTED JOB NO. 0423 SHEET E -2 OF 4 SHEETS DO NOT SCALE