06-782R-0051 OR 2 HOUR RATED GYPSUM WALLBOARD ASSEMBLY V��S i P /P9� STUD /FURRING CONDUIT (EMT) OR ROMEX (WIRE) S.1'steo ELEC. OUTLET BOX STUD /FURRING STUD /FUR ING CONDUIT (E.M.T.) /CONDUIT (E.M.T.) 1 10 I I — —1 L 3M FIRE BARRIER 3M FIRE BARRIER/"' ARRIER 1 -OR 2 HOUR FIRE MOLDABLE PUTTY MOLDABLE PUTTY RATED ASSEMBLY (ALL AROUND) (ALL AROUND) FRONT VIEW SIDE VIEW WALL OPENING PROTECTIVE MATERIALS (CLIV) This category covers proprietary compositions which are used to maintain the hourly ratings of fire resistive walls and partitions containing flush mounted devices such as outlet boxes, electrical cabinets and mechanical cabinets. The Individual Classifications Indicate the specific applications and the method of installation for which the materials have been evaluated. The basic standard used to Investigate products in this category is ANSI /UL 263. 'Fire Tests of Building Construction and Materials'. MINNESOTA MINING & MFG CO. 3M CENTER, ST PAUL MN 55144 Type MPP -45+ moldable putty pads for use with max 4 11/16 by 4 11/16 In. flush device UL Listed Metallic Outlet Boxes in fire rated gypsum wallboard watt assemblies framed with min 3 -1/2 In. wide wood or steel studs and constructed as specified In the Individual U300 or U400 Series Wall and Partition Designs in the Fire Resistance Directory. Type MPP -45+ moldable putty pads for use with max 4 by 3 -3/4 by 3 In. deep UL Listed Nonmetallic Outlet Boxes manufactured by Carton, made of PVC and bearing a 2 hr rating under the Outlet Boxes and Fittings Classified for Fire Resistance category in the Fire Resistance Directory. For use in fire rated gypsum wallboard wall assemblies framed with min 3 -5/8 in. wide wood studs and constructed as specified in the individual U300 Series Wall Partition Desings in the Fire Resistance Directory. Moldable putty pads are to be Installed to completely cover the exterior surfaces of the box within the stud cavity with a ball of the putty material used to plug the end of each electrical metallic tube or conduit at Its connection to the box. A min 1/8 in. thickness of putty material Is required on the exterior surfaces of flush device boxes in 1 and 2 hr fire rated Wall and Partition Desing. When the moldable putty pad outlet box protective material Is used as directed, the horizontal separation between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the outlet boxes are not installed back to back. 2 Hour Fire Rated Through c&—og, Penetration Firestop for Single MyMe Metal Pipe through 3735 Green Rd. Concrete Floors or Walls Beachwood, OH, 44122 yste�'` using TREMstop IA. CAJ 1302 F- Rating = 2 Hr. Drawing not to scale T- Rating = 0 Hr. 4 1 o a a. a d G 4' d .. C 3 OPre -Rated Concrete Floors or Block Walls = Min. 4 -1/2' thickness. O Metallic Pipe, A) Steel Pipe - 8' diam. (or smaller) Sch. 10 (or heavier) steel pipe. B) Iron Pipe - 8' diam. (or smatter) cast or ductile Iron pipe. C) Conduit - 4' diam. (or smaller) EMT or steel conduit. D) Copper Tubing - 4' diam. (or smatter) Type L (or heavier) copper tubing. E) Copper Pipe - 4' diam. (or smaller) Regular (or heavier) copper pipe. OPacking Material- See table below for mineral wool insulation (min. 4.0 pcf) requirements. OTREMstop IA- See table below for minimum thickness of sealant. Apply sealant flush with top of floor surface or with both sides of the wall assembly. Annular Space Min. Packing Material Min. Thickness F- Rating Range, In. Thickness, in. of Sealant, In. Hr. 1/2 to 1 -3/8 0 1 2 1/2 to 1 -3/8 4 1/2 2 Cj UL `r5'stel` WL 1113 F- Rating = 1 and 2 Hr. T- Rating = 0 Hr. VNZMQ 3735 Green Rd. Beachwood, OH, 44122 Drawing not to scale O Pre -Rated Gypsum Wallboard /Stud Wall Assembly O Metallic Pipet A) Steel Pipe - 4' diam. (or smaller) Sch. 40 (or heavier) steel pipe. B) Iron Pipe - 4' diam. (or smaller) cast or ductile Iron pipe. C) Conduit - 4' diam. (or smaller) EMT or rigid steel conduit. D) Copper Tubing - 4' diam. (or smaller) Type L (or heavier) copper tubing. E) Copper Pipe - 4' diam. (or smaller) Regular (or heavier) copper pipe. The annular space shall be min. 1/4' to max. 5/8' within the firestop system. 3O TREMstop IA- Min. 112' thickness of sealant applied within opening. Additional sealant to be applied so that a min. of 1/4' crown Is formed around penetrating Item. V&911 �s 1 f / `J�stev^ CAJ 2184 F- Rating = 2 Hr. T- Rating = 1 112 Hr. 4 a 4 Ad Mame 3735 Green Rd. Beachwood, OH, 44122 Drawing not to scale ° 4, d 4 .4 O Pre -Rated Concrete Floors or Block Walls = Min. 4 -1/2' thickness. O Plastic Pipe, A) Nom. 2' diam. (or smaller) Sch. 40 PVC pipe. B) Nom. 2' diam. (or smatter) SDR17 CPVC pipe. NOTE, For use In closed (process or supply) piping systems. OForming Material- Foam backer rod firmly packed into the opening as permanent form. OTREMstop IA- Sealant applied within opening, flush with top surface of floor or both surfaces of wall assembly as shown in table below. When required, apply additional sealant such that a min. 1/8' crown Is formed around the penetrating Item. Max. Pipe Annular Space, Min. Sealant Sealant Crown Diameter, In. in. Thickness, in. Required 1 -112 3/8 to 3/4 1/2 Yes 2 1/4 to 3/8 1 No �L `rJ'steO WL 2176 F- Rating = 1 Hr. T- Rating = 0 Hr, VNME90 3735 Green Rd. Beachwood, OH, 44122 Drawing not to scale O Pre -Rated Gypsum Wallboard /Stud Wall Assembly O Plastic Pipe - Non. 2' diam. (or smaller) Sch. 40 solid core PVC or SDR 17 CPVC pipe for use In closed or open piping systems. The annular space shall be min. 0' to max. 7/8' within the firestop system. O TREMstop IA - Min. 1/2' thickness of sealant applied within opening. Additional sealant to be Installed such that a min. 1/4' crown is formed around the penetrating Item. •REVILSIONS No. 201 o n.e. 21 avenue ,, no. miami beach, iI 33179 m N U o O u7 CL O I a N _ O M Q■ } rn U ° M vi 'C- m C 1- ti.. 0 m ar 13039 c u I-1`�� /�� 1 d �17i v G� DRAWN E.D.A. CHECKED R.P. DATE 11 -30 -05 SCALE AS NOTED JOB NO. 0423 SHEET A -4 OF 4 SHEETS J I DO NOT SCALE { 1_ ■ Qr1 Q ■ cn 0 OG O OCo �� LL O . Q CO cc � W Q v� Vm >o ■ V) O �0 a� � Z INC V) 0 LL. UJ r -ii, 2 W TIJ-) DRAWN E.D.A. CHECKED R.P. DATE 11 -30 -05 SCALE AS NOTED JOB NO. 0423 SHEET A -4 OF 4 SHEETS J I DO NOT SCALE { 1_