06-781-019ELECTRICAL NOTES
ALL CONDUCTORS SHALL BE COPPER, RATED 75 C WET /DRY EXCEPT
WHERE OTHERWISE REQUIRED BY U.L. OR CODES, UON. MINIMUM WIRE
SIZE SHALL BE #12 AWG. EXCLUDING CONTROL WIRING.
ALL CONDUIT RISERS SHALL BE RIGID GALVANIZED STEEL (RGS). WHERE
CONDUIT BENDS UPWARD FROM UNDERGROUND TO ABOVE GROUND, USE
AN APPROVED PVC TO RGS COUPLER, AS REQUIRED. RGS CONDUITS
SHALL EXTEND A MINIMUM OF 18' BELOW GRADE.
UNLESS NOTED AS EXISTING, ALL EQUIPMENT, WIRING, DEVICES,
ETC, SHALL BE NEW.
ENTIRE INSTALLATION SHALL BE IN ACCORDANCE WITH THE NATIONAL
ELECTRICAL CODE, LATEST EDITION (NEC) AND THE LATEST
EDITIONS OF THE FLORIDA BUILDING CODE AND ALL LOCAL CODES,
RULES AND ORDINANCES HAVING JURISDICTION.
ALL CONDUIT RUNS ARE SHOWN DIAGRAMMATICALLY. EXACT ROUTING
SHALL BE DETERMINED IN THE FIELD, UNLESS OTHERWISE NOTED.
ALL DISCONNECT SWITCHES SHALL BE SIZED BY NEC TO ACCOMMODATE
EQUIPMENT SERVED, INCLUDING REQUIRED FUSES, UON. SWITCHES
SHALL BE HORSE POWER RATED AND SIZED FOR 1/2 MAX.
HORSEPOWER, HEAVY DUTY TYPE.
ALL ELECTRICAL EQUIPMENT SHALL BE RAINTIGHT WHERE EXPOSED TO
THE WEATHER, ALL FLEX CONDUITS CONNECTED TO SUCH EQUIPMENT
SHALL BE LIQUID TIGHT.
WIRE WAYS SHALL BE SIZED AS REQUIRED, PER NEC, UNLESS
OTHERWISE NOTED (UON).
COORDINATE ALL ELECTRICAL SITE WORK WITH GENERAL CONTRACTOR.
FOR UNDERGROUND ELECTRICAL CONDUITS, PROVIDE FULL BOXES,
SUCH THAT NO SINGLE CONDUIT RUN HAS BENDS IN EXCESS OF 360.
PULL BOXES SHALL BE SUITABLE AND APPROVED FOR THE INTENDED
USE. WARNING TAPE WHICH SAYS 'WARNING BURIED ELECTRIC' SHALL
BE PLACED IN TRENCHES ABOVE ALL UNDERGROUND ELECTRIC
CONDUITS. WHERE CONDUITS PASS UNDERNEATH PAVED AREAS, THEY
SHALL BE RGS. WHERE UNDERGROUND CONDUITS ARE NOT EXPOSED TO
MECHANICAL DAMAGE OR ARE NOT UNDER PAVED AREAS, THEY SHALL
BE SCHEDULE 40 PVC. ALL CONDUIT RISERS SHALL BE RGS.
FOR TELEPHONE SYSTEM,
A. PROVIDE GROUNDING FOR ALL TELEPHONE OUTLETS AND
EQUIPMENT PER REQUIREMENTS OF TELEPHONE COMPANY,
B. VERIFY LOCATION OF TELEPHONE SERVICE WITH TELEPHONE
COMPANY, PRIOR TO SUBMITTING BID.
ALL CIRCUIT BREAKERS SHALL BE INVERSE TIME TYPE (THERMAL
MAGNETIC). TWO AND THREE POLE CIRCUIT BREAKERS SHALL BE
COMMON TRIP, NO TIE HANDLES PERMITTED,
ALL ELECTRICAL EQUIPMENT, DEVICES, WIRE, ETC,, SHALL BE LISTED,
FOR THE INTENDED USE, WITH UNDERWRITER'S LABORATORY, INC. (U.L,)
WHERE STANDARDS HAVE BEEN ESTABLISHED BY U,L.
ALL CONDUCTORS SHALL BE IN CONDUITS. ALL CONDUITS SHALL BE
INTERMEDIATE (IMC) OR RIGID GALVANIZED STEEL (RGS) EXCEPT
THATi (A) POLY VINYL CHLORIDE (PVC) CONDUITS MAY BE USED IN
CONCRETE SLABS AND UNDERGROUND PROVIDED ELBOWS AND RISERS
ARE RGSj (B) ELECTRICAL NON- METALLIC TUBING (ENT) MAY BE USED IN
OR ON WALLS OR CEILINGS WHERE NOT SUBJECT TO MECHANICAL
DAMAGE DAMP CONDITIONS OR CORROSIVE CONDITIONS) (C) LIQUID
TIGHT kEXIBLE CONDUIT WHERE REQUIRED, (D) FLEXIBLE METALLIC
CONDUIT WHERE REQUIRED IN DRY LOCATIONS. ALL CONDUITS IN
HAZARDOUS AREAS PER NEC SHALL MEET THE REQUIREMENTS OF NEC
CHAPTER 5.
PROVIDE LAMPS WITH FIXTURES, VERIFY LAMP TYPE WITH
MANUFACTURER.
COORDINATE ELECTRIC SERVICE WITH POWER COMPANY,
ELECTRICAL CONTRACTOR SHALL NOT SCALE DRAWINGS, CONTRACTOR
SHALL REFER TO ARCHITECTURAL PLANS AND ELEVATIONS FOR EXACT
LOCATIONS OF ALL EQUIPMENT UNLESS NOTED OTHERWISE.
ELECTRICAL CONTRACTOR SHALL VISIT THE JOB SITE AND VERIFY
ALL CONDITIONS, LOCATIONS, DIMENSIONS AND COUNTS AS SHOWN
AND /OR NOTED ON THE DRAWINGS, THIS SHALL INCLUDE ANY AND
ALL FABRICATIONS PRIOR TO INSTALLATION,
IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR
FOR THE ADVANCED ORDERING OF LONG LEAD ITEMS, AS NOT TO
INTERFERE WITH THE PRODUCTION OF OTHER TRADES RESULTING IN
ANY DOWN OR LAG TIME.
IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR
TO PROVIDE ALL LABOR, MATERIALS AND SUPERVISION NECESSARY TO
ACCOMPLISH THE WORK AS SHOWN AND /OR NOTED ON THE DRAWINGS.
IT SHALL BE UNDERSTOOD THAT ALL WORK PERFORMED SHALL BE DONE
BY A LICENSED ELECTRICAL CONTRACTOR AND IN A FIRST -CLASS
WORKMANLIKE MANNER. SAID CONTRACTOR SHALL MEET ALL
REQUIREMENTS SET FORTH BY ANY LOCAL ORDINANCE AND GOVERNING
AUTHORITIES.
THE ELECTRICAL CONTRACTOR SHALL BE RESPONSIBLE TO REPAIR TO
ORIGINAL CONDITIONS ANY AND ALL DAMAGES TO BUILDING
SURFACES, EQUIPMENT AND FURNISHINGS CAUSED DURING PERFORMANCE
OF WORK.
THE ELECTRICAL CONTRACTOR SHALL KEEP ALL AREAS IN WHICH WORK
IS BEING PERFORMED, FREE FROM DEBRIS AT ALL TIMES AND SAID
AREAS SHALL BE LEFT BROOM CLEAN AT THE END OF EACH WORKING
DAY.
IT SHALL NOT BE THE INTENT OF THESE PLANS AND /OR
SPECIFICATION TO SHOW EVERY MINOR DETAIL OF CONSTRUCTION.
THE ELECTRICAL CONTRACTOR SHALL BE EXPECTED TO FURNISH AND
INSTALL ALL ITEMS FOR A COMPLETE ELECTRICAL SYSTEM AND
PROVIDE ALL REQUIREMENTS NECESSARY FOR EQUIPMENT TO BE
PLACED IN PROPER WORKING ORDER.
WHERE CORE DRILLING OF FLOOR /WALLS IS REQUIRED, CONTRACTOR
SHALL SEAL OPENINGS WATERTIGHT AFTER UTILITIES HAVE BEEN
INSTALLED. LOCATION OF CORED HOLES SHALL COORDINATE WITH
LOCATION OF EQUIPMENT IN A MANNER TO BE CLEAN AND
FUNCTIONAL. THE CONTRACTOR SHALL INSTALL ONLY ONE CONDUIT
PER HOLE AND SEAL THE OPENING AROUND THE CONDUIT AS
SPECIFIED.
ELECTRICAL CONTRACTOR SHALL VERIFY CIRCUIT PROTECTIVE DEVICE
RATING FOR EQUIPMENT PRIOR TO CONSTRUCTION.
METER CANS, HUBS, L LUGS FOR SAME ARE TO BE FURNISHED
INSTALLED BY ELECTRICAL CONTRACTOR. ELECTRICAL CONTRACTOR
TO VERIFY SPECIFIC TYPE OF METER CAN TO BE USED WITH F.P.L.
PRIOR TO BID.
41
LIGHTING PLAN
SCALE : 1 /4 " =I' -0"
COON,
wIsIt
r
D RAW N
A.H.
CHECKED
R.P.
DATE
11-30-05
SCALE
AS NOTED
JOB NO.
0423
SHEET
E -2
OF 3 SHEETS
J
..p
C_
LL-
5w
Op
L
LL
.Q
W
Q
�-
Vm
>o
LV!
0
C)
0
O
w.
W
CC
Z
Do
ca
a
ch
-i
a
0
�-
LL.
W
p
.q-
j
_i
W
T-
D RAW N
A.H.
CHECKED
R.P.
DATE
11-30-05
SCALE
AS NOTED
JOB NO.
0423
SHEET
E -2
OF 3 SHEETS