06-781-012CONDENSING UNIT (TYPICAL) l l ANCHOR CONDENSING UNIT WITH 2 -/10 SCREWS SELF THREADED SEE PLANS FOR QUANTITY EACH SIDE OF STRAP TO °' I" BEAMS USING MIN. 1' WIDE, >° 22 GA. GALVANIZED STRAPS 3' HIGH X 2 1/2' WIDE ALUMINUM PAIL 3_ (TYPICAL EACH CORNER) 1 1/2'X1 1/2' ALUMINUM SQUARE �yl. 2'.2'x1 /4' THICK ISOMODE NEOPRENE PAD (TYPICAL EACH 24' CORNER) CONC. SLAB LIQUID SLEEVE 25/50 RATED INSUJLATION SUCTION LINE LOW VEL ❑CITY SUPPLY OR RETURN AIR DUCT PITCH PAN, MAKE LENGTH AND WIDTH OF �- 4'.4'.1 /4'ALUMIN. BASE SEE DETAIL BELOW. (TYPICAL AT EACH VERTICAL (;MT) AL 2 o_ .V �O3 O3 INSULATION WHERE DUCTS ARE SO SPECIFIED LO FILL SLEEVE WITH FIRE-PROOF/ 1 C14 .. -+- EQUIPMENT ROOM) U AREA DEFINED BY QASE PLATE LL AROUND LUS 2 USED. 6 g OCLEARANCE PER 12" OF DUCT ON ALL FOUR SIDES DUCT RESISTANT CC O7 COLLAR (SEE NOTES) 9 O1" TYP. ALL FOUR SIDES O SILICON SEALANT FOAM E M co HEAVIER ANGLES SNUG TO w* DETAIL IN COMPLIANCE WITH FLORIDA BUILDING CODE AND IASEp pry PREFABBICA AALLUuMINUuM�A TMI) AS MANUFACTURED BY A/C ALIE SrSTE S CTC. PR -B55 AROUND CLOSER 10 1 1/2'X1 1/2' ALUMINUM SQUARE ANGLE AS REQ'D 11 O BUSI,EES PARKWAY, ROYAL PALM BEACH, ����.. 33411 W BY LOCAL BLDG. 12 FLOOR SLAB I,v W 6 NOTES: 1. COLLAR GAUGES: 1 A. FOR COLLARS NOT 4' EXCEEDING 36'W OR 4' 7/16' HOLE FOR 3/9'Y 4* { 'HILT' 20 GAUGE 24 "H - 16 GAUGE B. FOR COLLARS EXCEEDING 36 "W OR BASE PLATE- 24 "H - 14 GAUGE GALVANIZED STEEL I KWIK BOLT PATH 4' MINIMUM EMBEOMENTINTO CONCRETE I SHEET -METAL (SIZE AS REO�D) —� 10 NUTS 12" C -C MAX. MIN. 2 BOLTS REFRIGERANT LINES FROM ACCU'S ��I'; �� .,_ ^•'� �`� � SPIN-IN COLLAR WITH VOLUME DAMPER IN EACH SIDE TOP & BOTTOM 3. INSTALLATION SHALL CONFORM TO NFPA -90A 4. PROVIDE ACCESS DOORS 10 , \ ` • \� SERVICE FUSIBLE LINKS AS REQUIRED 1. FLASHING AS RECOM. j.., �� :�� =-::;� OPERATOR TO BE OUTSIDE THE INSULATI ❑N. 1 /2- ALUMINUM I 1 ME ❑ BY MANUF. �.� \� ;; `:'� -;�' PROVIDE INSULATION GUARD WHERE TUBING _... e NECESSARY (DAMPER WHERE NOTED). [, �:_:':;� (PROVIDE DUCT DAMPERS WHERE ACCESSIBLE) 'KWIC' 4'.4'x1 /4' ALUMINUM BASE ROOF JOIST INSULATED FLEX DUCT 2 -3/6' ILL. BOLTS A H W/2 1/2' MINIMUM EMBEDMENT NUT (TYPICAL EACH BASE PLATE) BASE PLATE DUAL METAL PLATE/WASHER •• •. •• t\' ` �A \ ;::`- ='1 / SEAL JOINT WITH DUCT SEALER 2 -3/6' THROUGH BOLTS WITH NUTS WHERE LEGS NOT LOCATED ABOVE JOIST BOLTS THRU CURB, ROOF DECK AND Jasr OR wE1n cuRe To � ROOF DECK. USE CONCRETE ROOF SLAB INSULATE OR LINE SURFACES SEE ENLARGED DETAIL THIS DWG. TO PREVENT CONDENSATION. �- CEILING DIFFUSER OR RETURN REGISTER. CONDENSING UNIT PREFABRICATED SUPPORT DETAIL N.T.S. PATE STAINLESS ADJUSTABLE CLAMP, PATE STEPPED PVC BOOT STRIPIN ROOF PIPE SEAL N.T.S. SPRING & NEOPRENE TYPE VIBRATION ISOLATORS TYP. 3/8" HANGING RODS (THREADED) COORDINATE W/ STRUCTURAL ENGINEER AND /OR ARCH. ON HOW TO FASTEN TO STRUCTURE MOUNTING CLIPS OR UNITS CONNECTION TO SUPPORT RODS AS RECOMMENDED BY MFG. ELECTRIC HEAT ASSEMBLY FLEXIBLE DUCT CONNECTOR SUPPLY AIR DUCT SMOKE DETECTOR IN SUPPLY AIR DUCT AS REQUIRED TRANSITION AS REQUIRED PROVIDE 24" SERVICE CLEARANCE FOR ALL ACCESS PANELS PATE SPUN ALUMINUM BASE. BUILT UP ROOF TRANSITION AS REQ'D. RETURN AIR DUCTWORK OUTSIDE AIR DUCT W/ OPPOSED BLADE DAMPER (TYPICAL) FILTER & RACK ASSEMBLY 1" GALV. DRAIN PAN '—STRAPPED TO A.H.U. INSULATED CONDENSATE DRAIN AND TRAP (SEE PLUMB. FOR CONTINUATION) �— REFRIGERANT LINES TO CONDENSING UNITS INSULATE SUCTION LINE) AUX. DRAIN (SEE PLUMB. FON CONTINUATION) AIR HANDLING UNIT A.H.U. HANGING DETAIL N.T.S. REFRIGERANT PIPE RAINCOVER DETAIL N.T.S. ONE PIECE HINGED STEEL SHELL FLASHING AS RECOMMENDED BY MANUFACTURER PITCH PAN TYPE SUPPORT CURB 1 ISOLATING PAD FOR NON INSULATED LINES & ARMAFLEX (25/50 RATED) FOR INSULATED LINES ALUMINUM STRUTS 1 -5/8' X 1 -5/8' X .105' THICK (2.6MM) BY B -LINE OR APPROVED EQUAL COPPER LINE PAINT ALL EXTERI ❑R REFRIGERANT INSULATION WITH 2 COATS OF WHITE ARMA -FLEX PROTECTIVE PAINT. TYPICAL REFRIGERANT LINES CLAMPED TO CURB INSULATE ALL REFRIGERANT SUCTION LINES WITH 3/4' THICK ARMAFLEX INSULATI ❑N OR APPROVED EQUAL 'I ,— (-TYP. ROOF STRUCTURE ;0 f REFRIGERANT LINE SUPPORT DETAIL tl o G RETAINING HANGER CLIP ROD FLAT BAR RID C -CLAMP TO STRUCTURAL FLANGE W/ RETAINING CLIP OR LOCK NUT CONCRETE INSERTS FOR DUCTS UP TO 18' FOR DUCTS UP TO 36' MAXIMUM DIMENSION MAXIMUM DIMENSION DRIVE PIN THREADED STUD POWDER ACTUATED FASTENERS DUCT SUPPORT SYSTEM FOR ALL EXPOSED DUCT MANUFACTURED CONCRETE INSERT x HANGER HANGER STRA _ ROD POWER ACTUATED STUDS INTO STEEL (STRUCTURE OR DECK) x HANGER HANGER STRAP­ ROD WELDED STUDS INTO STEEL (STRUCTURE OR DECK) STRAP FDI DUCTS U FRICTION CLAMPS 8' MAX. STRAP NSION WA SHER EXPANSION SHIELDS EXPANSION NAIL 7WASHER NUT CONCRETE ANCHORS NOTE CONSTRUCTION AND INSTALLATION SHALL BE AS PER SMACNA STANDARD FOR TYPE OF DUCTWORK INSTALLED IN FACILITY. UPPER ATTACHMENT METHODS OF HANGING DUCTS AND EQUIPMENT DETAIL N.T.S. FLEXIBLE DUCT CONNECTION DETAIL N.T.S. 1/2" HANGER ROD - (4 REO'D.) FASTENED TO CONCRETE STRUCTURE ABOVE WITH EXPANSION BOLTS. HILTI KWIK BOLT D�XP. ANCHOR. ROD COUPLING TYPE 2 1/4' EMBEDMENT. TORT CROSS I (IF REQUIRED) HANGER ROD / SPRING J ISOLATOR E FAN BOTTOM HUNG HANGER ROD A.H.U. OR INLINE FAN BEYOND INLINE FAN OR A/C UNIT MOUNTING DETAIL N.T.S. ALL DAMPERS SHALL COMPLY WITH NFPA 90A UL 555 DUCT 11 T 1 ACCESS DOOR HORIZONTAL MOUNTING DETAIL VERTICAL MOUNTING DETAIL NOTE: TYPE "B' IS DETAILED FOR ALL SUPPLY AIR DUCTS TYPE "A" MAY BE USED FOR ALL RETURN ARE DUCTS AS REQUIRED. ALL MOTORIZED FIRE SMOKE DAMPERS SHALL BE FSD -60 TYPE. TYPICAL STYLE "B" FIRE DAMPER DETAIL T. . N REVISIONS zoTOO n.e. 21 avenue no. miami beach, fl 33179 O N O 2 o_ .V �O3 O3 INSULATION WHERE DUCTS ARE SO SPECIFIED LO O4 FLOOR LINE (IF NOT IN 1 C14 .. -+- EQUIPMENT ROOM) U ONOT USED. 6 g OCLEARANCE PER 12" OF DUCT ON ALL FOUR SIDES DUCT :+= Cl) W CC O7 COLLAR (SEE NOTES) 9 O1" TYP. ALL FOUR SIDES O O9 1- 1/2'0-1/2 "00 GA. OR E M co HEAVIER ANGLES SNUG TO w* FLOOR & COLLAR ALL AROUND CLOSER 10 'S" SLIP ANGLE AS REQ'D 11 WALL BY LOCAL BLDG. 12 FLOOR SLAB DEPT. W 6 NOTES: 1. COLLAR GAUGES: 1 A. FOR COLLARS NOT EXCEEDING 36'W OR 24 "H - 16 GAUGE B. FOR COLLARS EXCEEDING 36 "W OR 24 "H - 14 GAUGE 2. ATTACH ANGLES TO COLLARS OR (110 TEC SCREWS) WITH 1/4" 20 BOLTS & 10 NUTS 12" C -C MAX. MIN. 2 BOLTS IN EACH SIDE TOP & BOTTOM 3. INSTALLATION SHALL CONFORM TO NFPA -90A 4. PROVIDE ACCESS DOORS 10 SERVICE FUSIBLE LINKS AS REQUIRED NOTE: TYPE "B' IS DETAILED FOR ALL SUPPLY AIR DUCTS TYPE "A" MAY BE USED FOR ALL RETURN ARE DUCTS AS REQUIRED. ALL MOTORIZED FIRE SMOKE DAMPERS SHALL BE FSD -60 TYPE. TYPICAL STYLE "B" FIRE DAMPER DETAIL T. . N REVISIONS zoTOO n.e. 21 avenue no. miami beach, fl 33179 O N ` 4) U 2 o_ .V Q ■ LO CL O N 1 C14 .. -+- o M rn C) °• = Q f.■ N o :+= Cl) W CC oiC- LD M >_ O o L. L E M co 6) U w* a 0 0 Gi V) Of 13039 a0r W t Jill•, t • yQ L DRAWN M.R. CHECKED R.P. DATE 11 -30 -05 SCALE AS NOTED JOB NO. 0423 M-5 OF 6 SHEETS ■ Q ■ (n O •� LL. CC 00 CO) CV = Q IUL IX Cl) W CC V >_ O L L ■ E M co 00 w* Z 0 V) I a0r W D �I }A J W 6 DRAWN M.R. CHECKED R.P. DATE 11 -30 -05 SCALE AS NOTED JOB NO. 0423 M-5 OF 6 SHEETS