06-743-0065th Floor
Fire Sprinkler Ceiling Plan
012 4 8 16
III I 1 I
SCALE: 1/8' =1' -0'
5th Floor
Fire Sprinkler Piping Plan
0 1 2 4 12
I I I I I
SCALE: 3/16' =1' -0"
Ke y Plan
NO SCALE
MAXIMUM DISTANCE BETWEEN HANGERS ....
SCHEDULE
D21,
CONCRETE SLAB
2.
POWDER DRIVEN STUD
1'
(SIZE VARIES, SEE PLAN)
3.
ROD COUPLING
1 -1/4'
(SIZE VARIES, SEE PLAN)
4.
ALL THREAD ROD
5.
NOMINAL PIPE
SIZE (in.)
3/4"
1'
1 -1/4"
1 -1/2'
2'
2 -1/2"
3'
3 -1/2"
¢•
5"
F' < < .
8" (�
STEEL PIPE EXCEPT
THREADED UGHTWAU_
N/A
12 -0
12 -0
15 -0
15 -0
15 -0
15 -0
15 -0
15 -0
15 -0
15 =0 "
15 -0 " I
THREADED LIGHTWALL
N/A
12 -0
12 -0
12 -0
12 -0
12 -0
12 -0
N/A
N/A
N/A
NIA
N /A<<�
STEEL PIPE
COPPER TUBE
8 -0
8 -0
10 -0
10 -0
12 -0
12 -0
12 -0
15 -0
15 -0
15 -0
154 .
15 -0 "
..
CPVC
5 -6
6 -0
6 -6
7 -0
8 -0
9 -0
12 -0
N/A
N/A
N/A
N %" `
N/A
POLYBUTYLENE (IPS)
N/A
3 -9
4 -7
5 -0
5 -11
N/A
N/A
N/A
N/A
N/A
N/A
N/A
POLYBUTYLENE (CTS)
2 -11
3 -4
3 -11
4 -5
5 -5
N/A
N/A
N/A
N/A
N/A
N/A
N/A
I
.aa rA
d POWDER DRIVEN STUD &
ALL THREAD ROD SIZES
FOR 1' THRU 4' PIPE
3/8' IS TO BE USED
POWER DRIVEN STUD
Hanger Details
NO SCALE
SCHEDULE
D21,
CONCRETE SLAB
2.
POWDER DRIVEN STUD
1'
(SIZE VARIES, SEE PLAN)
3.
ROD COUPLING
1 -1/4'
(SIZE VARIES, SEE PLAN)
4.
ALL THREAD ROD
5.
HANGER RING
15'-0" MAX.
(SIZE VARIES, SEE PLAN)
6,
PIPE
Hanger Details
NO SCALE
SYMBOL
Hanger Location Wal
PIPE SIZE
A
B*
C
1'
3'-0' MAX.
12' -0" MAX.
3' MIN.
1 -1/4'
4' -0' MAX.
12' -0" MAX.
3" MIN.
1- 1 /2'TH 8'
5'-0" MAX.
15'-0" MAX.
3" MIN.
155
TYFRB OR BRASS UPRIGHT
TY3131
A
B•
C
SPRINKLER HEAD 41
I--
LL STEEL PIPE
LHANGER
• MAXIMUM HANGER SPACING FOR THREADED LIGHTIMALL
STEEL PIPE IS 12' -0' FOR ALL PIPE SIZES
SYMBOL
QTY
SIZE
K
TEMP
MODEL
SIN
0
113
1/2'
5.6
155
RFlI OR WHT FLUSH PEND
TY3531
O
-
1/2"
5.6
155
TYFRB OR BRASS UPRIGHT
TY3131
•
DROP IN ANCHORS &
ALL THREAD ROD SIZES
FOR V THRU 4' PIPE
3/8' IS TO BE USED
FOR 6' & 8' PIPE
1/2' IS TO BE USED
DROP IN ANCHOR
4 Q 4
tli
x ARMOVERS GREATER THAN
24' IN LENGTH SHALL BE
SUPPORTED BY A HANGER,
T
8
___0
6�
SCHEDULE
1, EXIST BRANCHLINE OR MAIN
—Q 2. NEW TEE
(SIZE VARIES, SEE PLAN)
3. ARMOVER.w
_O (SIZE VARIES, SEE PLAN)
4. 1' 90• ELL OR TEE
5. DROP (SIZE VARIES, SEE PLAN
—Qj MAY FEED TEE SUPPLYING MORE
THAN ONE SPRINKLER)
6. NEW SEMI- RECESSED
PENDENT FIRE SPRINKLER
7. CEILING.
8. NIPPLE
9, REDUCING COPULING
(SIZE VARIES, SEE PLAN)
SCHEDULE
1. NEW BRANCHLINE OR MAIN
2 NEW MECH TEE OR WELDED OUTLET
(SIZE VARIES, SEE PLAN)
3. SPRINKLER HEAD
Sprinkler Detail
NO SCALE
PENDENT SPRINKLER HEAD(S)
ON SNAP-O -LET OR MECHANICAL TEE
FLOW SWITCH
CHECK VALVE
CONTROL VALVE
with Tamper (Wired by others 0
to
i
LANDING
IF
2' DRAIN LINE
ti ; ....�:,1:
FLOOR VALVE
6' -0' AFF (U.N.O.)
2' Drain Riser Tie each
foor into drain and pipe
to suitable location at
exterior of the building
1/4' GAUGE
RISER CLAMP
(TYPICAL)
LANDING
APPROVED
MI1MR -DADS COUNTY FIRE DEPARTMENT
FIRE SLPPRPSSM! WATER MAIN EXT. Typical Floor
DATE: BY: A seewnL•Jv
NTS (FOR REFERENCE ONLY)
SEE LAYOUT DRAWINGS FOR SIZE AND LOCATION
To System
FLOOR CONTROL
VA. ASSEMBLY
2 6' -0' AFF QN11)
4' RISER
ILL
J�co M C
X 1_�?
t
w4'
i
�f
SCHEDULE
D1.
CONCRETE SLAB
2.
DROP IN ANCHOR
(SIZE VARIES, SEE PLAN)
3,
ALL THREAD ROD
(SIZE VARIES, SEE PLAN)
4.
HANGER RING
5.
PIPE
SCHEDULE
1, EXIST BRANCHLINE OR MAIN
—Q 2. NEW TEE
(SIZE VARIES, SEE PLAN)
3. ARMOVER.w
_O (SIZE VARIES, SEE PLAN)
4. 1' 90• ELL OR TEE
5. DROP (SIZE VARIES, SEE PLAN
—Qj MAY FEED TEE SUPPLYING MORE
THAN ONE SPRINKLER)
6. NEW SEMI- RECESSED
PENDENT FIRE SPRINKLER
7. CEILING.
8. NIPPLE
9, REDUCING COPULING
(SIZE VARIES, SEE PLAN)
SCHEDULE
1. NEW BRANCHLINE OR MAIN
2 NEW MECH TEE OR WELDED OUTLET
(SIZE VARIES, SEE PLAN)
3. SPRINKLER HEAD
Sprinkler Detail
NO SCALE
PENDENT SPRINKLER HEAD(S)
ON SNAP-O -LET OR MECHANICAL TEE
FLOW SWITCH
CHECK VALVE
CONTROL VALVE
with Tamper (Wired by others 0
to
i
LANDING
IF
2' DRAIN LINE
ti ; ....�:,1:
FLOOR VALVE
6' -0' AFF (U.N.O.)
2' Drain Riser Tie each
foor into drain and pipe
to suitable location at
exterior of the building
1/4' GAUGE
RISER CLAMP
(TYPICAL)
LANDING
APPROVED
MI1MR -DADS COUNTY FIRE DEPARTMENT
FIRE SLPPRPSSM! WATER MAIN EXT. Typical Floor
DATE: BY: A seewnL•Jv
NTS (FOR REFERENCE ONLY)
SEE LAYOUT DRAWINGS FOR SIZE AND LOCATION
To System
FLOOR CONTROL
VA. ASSEMBLY
2 6' -0' AFF QN11)
4' RISER
ILL
J�co M C
X 1_�?
t
w4'
i
�f