06-51-029L
s
ICI /
4TH PL WIREWAY
al'ICC I
TENANT 48 6E RISER THIS
6H�Er
EXISTING 5TH FL WIREWAY
FUTURE TENANT
E MOUNTED
� STRUCTURE)
I
I
I
2ND FLOOR METER ROOM 1/2"
FIRE ALARM GENERAL NOTES:
I. MINIMUM RACEWAY SIZE SHALL BE 3/4'. WIRING TO COMPLY WITH N.E.C. ARTICLE 160 -16.
2. ACTUAL FIELD WIRNG REQUIREMENTS FOR NEW DEVICES 614ALL BE AS INDICATED BY EQUIPMENT
SUPPLIER ON APPROVED SHOP DRAWINGS
3. MAXIMUM CONDUIT FILL - 40% OF CCNDUIT AREA
4. ALL EQUIPMENT SHALL BE U1-. LISTED BY UNDERWRITERS L 50PATORIEO FOR Tl4E INTENDED
USE AND SHALL MEET WITH THE APPROVAL OF THE LOCAL FIRE AUTHORITIES: THE COMPLETE
INSTALLATION SHALL BE MADE N ACCORDANCE WITH NFPA 012 SERIES: ALL LOCAL CODES
AND REQUIREI'ENTS, NFFA M01 AND N.E.C. ARTICLE 160,
5. FIRE ALARM CONTRACTOR TO PROVIDE ALL PROGRAMMING, ALL FN& CONNECTION", ALL
TESTING AND CERTIFICATION.
6. PROVIDE NEW CONDUIT AND WIRING AS REQUIRED TO PROVIDE A COMPLETE AND WORKABLE
SYSTEM AS DESCRIBED N SPECIFICATION SECTION 16121.
1. CONTRACTOR SHALL VERIFY WIT14 M*VACTURER FOR ACTUAL MARFACTLKR WIRNG
RECOM`NEDATIM.
8. THE DEVICE DE644ATION NDICATED IS FOR INFOFMTION ONLY. THE CONTRACTOR 6HALL
PROVIDE HIS OWN DEVICE DESIGNATION FOR APPROVAL.
9 MATCH EXISTING FIRE ALARM DEVICES, WIRE CIRCUITS AND PROVIDE POWER SUPPLY AS
REQUIRED.
10. CONTRACTOR TO PROVIDE BATTERY CALCULATION TO AVOID BATTERY OVERLOAD N THE
SYSTEM.
1L CONNECT NEW APPLIANCES INTO EXISTING NOTIFICATION CIRCUIT,
12. CONNECT NEW DETECTION DEVICE INTO THE EXISTING DETECTOR LOOP.
13. HORN/SiROBE %HALL MEET'ADA, REQUIREMENTS OF 8' -6' AFF. OR 6' BELOW CEILING
WHICHEVER IS LOWER.
w,.i -5
PARTIAL RISER NOTES
IQ EXISTING 3000 AMP 1201208V, 3PH, 4W PANEL 'WA'
2Q 5XI8TW1 12' X 12' X 60' WIREWAY TO REMAIN
3Q EXISTNG (2) 6ETS OF 4 -600 MCM 4 N GNP IN 4' CaO EACH
® KWNR METER IN NEMA I ENCLON.IRE
Q NEW 24' X 24' X 48' WIRMI AY
® NEW 2 PANEL 4A SEE %cHEPULE
1Q NEW 2 SECtICN PANEL 48. SEE SCHEDULE
® 3 POLE 400 AMP DISC MTCH NENA 1 WITH 250 AMP RnS 42 KAIC,
9Q 2 SETS OF 4N 11#4 GND M 2' CONDUIT EACH
® EXISTNG 3PWOAMP CIRCUIT BLEAKER
II 2 -2' EC WITH FUL.LWIRE FOR FUTURE TENANT SPACE
Q 2' EC WITH PULLWIRE FOR SPACE
((3 $TU13 2' EC INTO EXISTING CEILING SPACE AND CAP
® 4014 1% GND N 2' COND,
Q 3 POLE 200AMP DISC. SWITCH NEMA 1 WITH I15 AMP FUSES 42 mia
AHU -4 -3 AHU 4 -2 AHU -4 -1
t� tnt Div./
TO FIRE ALAFd'1
PANEL 16T FLOOR
"RS
RTU -1
PARTIAL ELECTRICAL RISER DIAGRAM N.T.S.
FIRE ALARM RISER DIAGRAM
ACP IN l,t FLOOR 3rd FLOOR
(TYP)
2nd FLOOR
FIR TAL ARM CONTROL PA ML
(PACP)
N.T.S.
FIMT FLOOR
DATA / VOICE
OUTLET (TYP)
VOICE OUTLET'
(TYP)
VOC WIT14 PULLWIRS TO PBX ROOM. THIS FLOOR.
TELEPHONE \ DATA RISER DIAGRAM
IN' EATIATION
besu1 .u,,,ttcdfar;,exitit�p�rc;� lto 47i�lri-
Daee crjuniy F'i.xe .1.et.Lrt z_ ?ri.
t',�pT�,'dFr1f r6xlii�xsk'Irx2'f
I%
yR
CLG. SPACE
N.T.S.
4' -0' X8' -0' X 3/4'
PLYWOOD PANTED
BLOCK TELEPH"
TERMINAL BOARD
3RD FLOOR
diez
architecture,
inc.
7430 sw 48th street
miami, florida 33155
phone: (305) 663 -1970
fax: (305) 663 -2312
e —mail: peter0diezorchitecture.com
pedro diez, ra
president ar 0008996
ENGINEERING CONSULTANT
6747
Office Building
4th Floor
6141 SUNSET DRIVE
SOUTH MIAMI, FLORIDA
PROJECT No. 04- 158.04
REVISIONS
ELECTRICAL ROOM
PLANS AND
RISER DIAGRAM
w
SCALE: AS SHOWN
DATE: DECEMBER 12, 2005
Y