06-51-017GENERA:
CONTRACTOR SHALL VERIFY ALL SPACE CONDITIONS AT JOB SITE PRIOR TO FABRICATION OF DUCTWORK AND PURCHASE OF EQUIPMENT.
REFERENCES:
A. ABC ASSOCIATED AIR BALANCE COUNCIL.
B. ADC AIR DIFFUSION COUNCIL.
C. AMCA AIR MOVEMENT AND CONTROL ASSOCIATION.
D. ANSI AMERICAN NATIONAL STANDARDS INSTITUTE.
E. API AMERICAN PIPE INSTITUTE.
F. ARI AMERICAN REFRIGERATION INSTITUTE.
G. ASHRAE AMERICAN SOCIETY OF HEATING REFRIGERATION AND AIR CONDITIONING ENGINEERS.
H. ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS.
I. ASTM AMERICAN STANDARDS FOR TESTING MATERIALS.
J. AWS AMERICAN WELDING SOCIETY.
K. FM FACTORY MUTUAL.
L. NBS NATIONAL BUREAU OF STANDARDS.
M. NEC NATIONAL ELECTRIC CODE.
N. NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION.
0. NFPA NATIONAL FIRE PROTECTION ASSOCIATION.
P. OSHA OCCUPATIONAL SAFETY AND HEALTH ACT UNITED STATES DEPARTMENT OF LABOR STANDARDS.
Q. FBC FLORIDA BUILDING CODE.
R. SMACNA SHEET METAL AND /AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION.
S. SMC STANDARD MECHANICAL CODE.
T. UL UNDERWRITERS LABORATORIES INC.
U. FMC — FLORIDA MECHANICAL CODE.
DRAWINGS: ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEM AND WORK INCLUDED IN CONTRACT. FOLLOW DRAWINGS IN
INSTALLING NEW AIR CONDITIONING SYSTEM; CHECK DRAWINGS OF ALL TRADES TO VERIFY SPACES IN WHICH WORK WILL BE INSTALLED, IF SPACE
CONDITIONS ARE INADEQUATE, OR DO NOT AGREE WITH THE CONDITIONS SHOWN ON THE DRAWINGS NOTIFY THE PROJECT ARCHITECT /ENGINEER PRIOR
TO PROCEEDING WITH THE WORK. DO NO WORK UNTIL ALL CONDITIONS ARE CORRECTED. BEGINNING OF INSTALLATION IS AN ACCEPTANCE OF THE
EXISTING CONDITIONS.
PERFORMANCE: CONTRACTOR SHALL VERIFY EXACT DIMENSIONS AT JOB SITE PRIOR TO FABRICATION OF ACCESSORIES AND PURCHASE OF EQUIPMENT.
CONTRACTOR SHALL VERIFY OPERATING CONDITION AND VOLTAGES PRIOR TO ORDERING EQUIPMENT, AND COMMENCING WORK. NOTIFY THE OWNER OF
ANY DEFICIENCY THAT COULD POSSIBLY DELAY OR AFFECT THE COMPLETION OF THE WORK.
SUBSTITUTIONS: EQUIPMENT SPECIFIED SHALL BE ADHERED TO. HOWEVER, OWNER HAS THE FINAL DECISION ON THE TYPE AND QUALITY OF
EQUIPMENT TO BE SUPPLIED. CONTRACTOR SHALL OBTAIN WRITTEN PERMISSION FROM THE OWNER PRIOR TO PURCHASING SUBSTITUTE EQUIPMENT.
CONTRACTOR SHALL BEAR THE COST OF ALL ENGINEERING WORK RELATED TO SUBSTITUTED EQUIPMENT.
WORK INCLUDED:
THE EXTENT OF THE AIR CONDITIONING WORK INCLUDES, BUT IS NOT LIMITED TO THE FOLLOWING:
1. THE INSTALLATION OF ALL SPECIFIED AIR CONDITIONING EQUIPMENT SUCH AS, BUT NOT LIMITED TO: AIR CONDITIONING UNITS, PIPING, VALVES,
INSULATION, THERMOSTATS, SMOKE DETECTORS, DUCTWORK, DAMPERS, DIFFUSERS, ETC. TO WHERE SHOWN ON DRAWINGS, AS WELL AS THE
INSTALLATION OF ALL EQUIPMENT NOT NORMALLY SHOWN ON DRAWINGS BUT NECESSARY FOR THE SYSTEM TO OPERATE AS INTENDED.
2. THE INSTALLATION OF NEW EXHAUST FANS, WITH RELATED DUCTWORK, GRILLES, ETC. AS SHOWN ON DRAWINGS AND /OR HEREIN SPECIFIED,
3. THE FABRICATION AND INSTALLATION OF ALL PIPE ACCESSORIES SUCH AS PIPE SUPPORTS, PIPE SLEEVES, DRAIN LEGS, DRAIN PANS, ETC.
WHETHER SHOWN ON DRAWINGS OR NOT, AS WELL AS THE FABRICATION AND INSTALLATION OF ALL DUCTWORK ACCESSORIES SUCH AS
VOLUME EXTRACTORS, TURNING VANES, DAMPERS, ACCESS PANELS ETC. AS SHOWN ON DRAWINGS OR AS NECESSARY FOR A COMPLETE AIR
DISTRIBUTION SYSTEM TO OPERATE AS INTENDED.
4. THE EXECUTION OF AN AIR BALANCE FOR THE NEW SYSTEM.
5. ALL CUTTING AND PATCHING ASSOCIATED WITH THIS INSTALLATION.
6. ALL PERMITS AND FEES FOR PERMITS.
HVAC SPECIFICATIONS
AIR DISTRIBUTION DEVICES:
PROVIDE ALL AIR DISTRIBUTION DEVICES CONSTRUCTED FROM ANODIZED ALUMINUM MANUFACTURED BY A SINGLE MANUFACTURER, "AMCA" AND "ADC"
RATED OF SIZES SHOWN ON DRAWINGS WITH BORDERS AND MOUNTING FRAMES SUITABLE FOR THE LOCATION WHERE AIR DISTRIBUTION PRODUCTS
ARE TO BE INSTALLED. PROVIDE AND INSTALL AIR DISTRIBUTION PRODUCTS AS SCHEDULED.
DUCTWORK:
FIBERGLASS DUCTWORK. MATERIAL: ONE INCH THICK GLASS FIBER DUCTBOARD FABRICATED FROM NOIN— CORROSIVE, NON— HYGROSCOPIC, PERMANENTLY
ODORLESS, MICROBACTERIAL— GROWTH INHIBITING, RESILIENT, LONG STAPLE, FABRIC GRADE GLASS RIBERS, FACTORY PREFORMED INTO SEMI —RIGID OR
RIGID BOARD WITH A FLEXURAL RIGIDITY RATING OF 800EI PER ASTM TEST NUMBER D- 1037 -64 WHERE NEITHER WIDTH NOR DEPTH OF DUCT
EXCEEDS 48 INCH. AND WITH A FLEXURAL RIGIDITY RATING OF 1400EI PER ASTM TEST NUMBER 04037 -64 WHERE WIDTH OR DEPTH EQUALS OR
EXCEEDS 48 INCH, FIBERGLASS BOARD SHALL BE NON— EROSIVE WHEN CONVEYING AIR AT VELOCITIES TO 2000 FPM, AND SHALL BE COVERED WITH A
FIRE RETARDANT, MOISTURE SEALING, FACTORY— APPLIED JACKET MADE OF REFLECTIVE, ALUMINUM [FOIL KRAFT PAPER OF 2 MIL MINIMUM THICKNESS.
MANUFACTURER AND PRODUCT: CERTAINTEED TOUGHTGARD WITH A R =6.5 AND A MAXIMUM THERMAL. CONDUCTIVITY OF 0.23 AT 75 DEGREE F MEAN
TEMPERATURE.
CONSTRUCTION: COMPLETED DUCT SYSTEM SHALL BE STABLE AND AIRTIGHT AT 2 INCH W.G. STATIC PRESSURE. INSTALL IN COMPLIANCE WITH THE
MANUFACTURER'S RECOMMENDATIONS. PROVIDE CONTINUOUS VAPOR RETARDANT CONTINUITY AND SEAL IN ACCORDANCE WITH SMACNA STANDARDS.
MITER ALL LONGITUDINAL CORNERS (EXCEPT SEAMS) WITH JACKET UNDISTURBED. ROUND CROSS — SECTION DUCTS SHALL BE FACTORY MOLDED ONLY.
SQUARE AND RECTANGULAR DUCTS SHALL BE SHOP OR FIELD FABRICATED FROM FLAT DUCTBOARD.
DUCT REINFORCEMENT: METALLIC DUCT REINFORCEMENT SUPPORT AND DUCT EQUIPMENT SLEEVES SHALL BE GALVANIZED STEEL.
FLEXIBLE DUCTWORK: DUCTWORK MANUFACTURED FROM STEEL WIRE HELIX ENCAPSULATED IN DOUBLE LAMINATION OF POLYESTER AND COVERED WITH
HIGH DENSITY FIBERGLASS INSULATION REINFORCED WITH SCRIM AND VAPOR BARRIER. SIMILAR TO ONNIAIR MODEL 1000.
FLEXIBLE DUCT SUPPORT AND HANGERS:
SUPPORT FLEXIBLE DUCTS AS PER MANUFACTURER'S RECOMMENDED INTERVALS BUT AT LEAST EVERY 5 FT.
MAINTAIN A MAXIMUM PERMISSIBLE SAG OF Yz" PER FT OR LESS. TOTAL SAG SHALL NOT EXCEED 2.5 IN. OVER THE 5 FT. INTERVAL.
SELECT FLEXIBLE DUCT HANGERS FROM TABLE 4 -2 "MINIMUM HANGER SIZES — ROUND DUCT" EXCEPT THAT MIN. SPACING SHALL BE KEPT AT 5' -0
BETWEEN SUPPORTS. HANGER AND SADDLE MATERIAL IN CONTACT WITH FLEXIBLE DUCT SHALL BE A'T LEAST lY" WIDE SO IT DOES NOT REDUCE THE
INTERNAL DIAMERTER OF THE DUCT WHEN THE SUPPORTED SECTION RESTS ON THE HANGER OR SADDLE. SADDLES SHALL COVER AT LEAST ONE —HALF
(Y) THE CIRCURFERENCE OF THE OUTSIDE DIAMETER OF THE DUCT AND FIT NEATLY AROUND THE LOIWER HALF OF THE OUTER CIRCUMFERENCE.
SUSPEND HANGERS FROM BUILDING STRUCTURE AS INDICATED IN THE LATEST SMACNA "HVAC DUCT CONSTRUCTION STANDARDS — METAL AND
FLEXIBLE" FIG 4 -2 AND 4 -3 "UPPER ATTACHEMENT DEVICES, TYPICAL"
SHEET METAL DUCTWORK:
VENTILATION DUCTWORK:
RIGID: ALL VENTILATION DUCTWORK SHALL BE MANUFACTURED FROM STANDARD GAUGE GALVANIZED SHEET STEEL IN COMPLIANCE WITH (SMACNA)
STANDARDS FOR THE FABRICATION, CONSTRUCTION, AND INSTALLATION OF LOW AND MEDIUM PRESSURE STEEL DUCTWORK. ALL DUCT SEAMS AND
JOINTS SHALL BE SEALED WITH A NON HARDENING, NON MIGRATING 4" WIDE MASTIC (SIMILAR TO PERMACELL #691AF) OR EQUIVALENT. SEALING
SHALL BE DONE AS RECOMMENDED BY SEALER MANUFACTURER TO OBTAIN A CLASS "A" SEAL.
FLEXIBLE: VENTILATIONS DUCTS MADE OF CORRUGATED ALUMINUM WITH WATER TIGHT LOCK SEAMS, (DESIGNED FOR LOW PRESSURE VENTING
APPLICATION WITH A MAXIMUM WORKING PRESSURE (POSITIVE OR NEGATIVE) OF 4" WG. AND A TEMPERATURE RANGE FROM —100 OF TO 400 OF,
SIMILAR TO OMNIAIR MODEL 2000.
AIR CONDITIONING DUCTWORK:
1. ROUND: SHEET METAL ROUND DUCTWORK: PROVIDE UNITED McGILL'S "UNIRIB" ROUND DUCTWORK AND FITTINGS IN SIZES SHOWN ON DRAWINGS,
MACHINED FROM GALVANIZED STRIP —COIL STEEL WITH A STANDING RIB PROJECTING RADIALLY' FROM THE OUTSIDE OF THE FORMED ROUND DUCT
AND PARALLELING TO THE CONTINUOUS HELICAL LOCKSEAM DUCT PATTERN. JOINT ALL DUCTS AND FITTINGS BY SLIP — JOINING PIECES
TOGETHER AS RECOMMENDED BY DUCTWORK MANUFACTURER. APPLY INTERNAL DUCT SEALER AS REQUIRED TO PROVIDE CLASS "A" SEAL.
FURNISH ALL DUCT SECTIONS WITHOUT BLEMISHES OR IMPERFECTIONS, CLEAN INSTALLED DUCTS FROM ALL EXCESS SEALANT AND ALL OTHER
FOREIGN MATERIAL WHICH WILL IMPAIR EXTERIOR FINISH APPEARANCE. PAINT ALL DUCT EXPO1SED SURFACES AS REQUIRED BY OWNER.
2. RECTANGULAR: MANUFACTURED FROM STANDARD GAUGE GALVANIZED SHEET STEEL IN COMPLIANCE WITH (SMACNA) STANDARDS FOR THE
FABRICATION, CONSTRUCTION, AND INSTALLATION OF LOW AND MEDIUM PRESSURE STEEL DUCTWORK. ALL DUCT SEAMS AND JOINTS SHALL BE
SEALED WITH A NON HARDENING, NON MIGRATING 4" WIDE MASTIC (SIMILAR TO PERMACELL #691AF) OR EQUIVALENT, SEALING SHALL BE DONE
AS RECOMMENDED BY SEALER MANUFACTURER TO OBTAIN A CLASS "A" SEAL.
DUCTWORK INSULATION: PROVIDE ALL INSULATION MATERIALS WITH A FLAME SPREAD CLASSIFICATION OF 25 FT —MIN OR LESS, SMOKE DEVELOPED
CLASSIFICATION OF 50 FT —MIN OR LESS, AND FUEL CONTRIBUTED CLASSIFICATION OF 25 FT —MIN OR; LESS AS TESTED BY NFPA -255 — "METHOD OF
TESTING THE SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS." INSULATE ALL AIR CONDITIONING DUCTWORK AND INDICATED VENTILATION
DUCTWORK WITH ONE OF THE FOLLOWING INSULATION TYPES:
1.— FLEXIBLE EXTERIOR INSULATION: 1" THICK, 3 LB /CF DENSITY FEDERAL SPEC. HH -1 -558, FORM B, TYPE I, CLASS #6.
DUCT REINFORCEMENT: FABRICATED IN ACCORDANCE WITH "SMACNA" DUCT CONSTRUCTION STANDARDS. ALL METALLIC DUCT REINFORCEMENT SUPPORT
AND DUCT EQUIPMENT SLEEVES SHALL BE MADE OF HEAVY GAGE GALVANIZED STEEL.
FLEXIBLE DUCT CONNECTIONS: AIR TRACK, TWIST LOCK CONNECTIONS MANUFACTURED FROM HEAVY GAUGE GALVANIZED STEEL, FACTORY ASSEMBLED
WITH ADJUSTABLE DAMPER MOUNTED ON BEARINGS AND POSITIVE LOCKING HARDWARE.
4
HVAC SPECIFICATIONS
AIR CONDITIONING UNITS:
FACTORY SELF CONTAINED AIR COOLED A/C UNIT:
1. SELF CONTAINED, FACTORY PREPACKAGED AND ASSEMBLED SUITABLE FOR OUTDOOR INSTALLATION. AC UNITS TO BE CONSTRUCTED FROM HEAVY
GAUGE GALVANIZED STEEL WITH RUST RESISTANT EPDXY FINISH, EASILY REMOVABLE ACCESS PANELS, OUTSIDE AIR INTAKE WITH VOLUME DAMPER
AND ALUMINUM BIRD SCREEN, ONE (1) INCH THICK NEOPRENE COATED FIBERGLASS INTERNAL INSULATION THROUGH OUT ENTIRE CABINET. AC
UNITS TO BE FACTORY ASSEMBLED WITH THE FOLLOWING COMPONENTS:
A. COMPRESSOR(S) TO BE HERMETICALLY SEALED OF THE 1750 RPM TYPE, RESILIENTLY MOUNTED WITH POSITIVE LUBRICATION, CRANKCASE
HEATER, MOTOR OVERLOAD PROTECTION, SERVICE VALVES, FILTER DRYER, WITH SUCTION AND DISCHARGE SHUT OFF VALVES.
B. CONDENSER COIL: CONSTRUCTED OF COOPER TUBING WITH ALUMINUM FINS.
C. CONDENSER FAN: VERTICAL DISCHARGE, DIRECT DRIVE, AXIAL TYPE, RESILIENTLY MOUNTED WITH ALUMINUM GUARD AND TOTALLY
ENCLOSED, PERMANENTLY LUBRICATED BALL BEARING MOTOR WITH BUILT IN CURRENT AND OVERLOAD PROTECTION.
D. EVAPORATOR COIL: EVENLY SPACED ALUMINUM FINS MECHANICALLY BONDED TO COPPER TUBES (DESIGNED FOR 250 PSIG.) NTH A 16
GAGE GALVANIZED STEEL INSULATED INTERNAL DRAIN PAN NTH DRAIN CONNECTION.
E. EVAPORATOR FAN: SINGLE INLET TYPE WITH STATICALLY AND DYNAMICALLY BALANCED CENTRIFUGAL WHEEL WITH FORWARD CURVED
SINGLE WIDTH BLADES, DIRECT DRIVEN, RESILIENTLY MOUNTED ON SLEEVE BEARINGS.
F. AIR FILTER: TWO (2) INCH THICK FIBERGLASS THROWAWAY OR PERMANENT WASHABLE TYPE, FILTER TO BE LOCATED IN FACTORY
FABRICATED FILTER RACK UPSTREAM OF EVAPORATOR COIL.
FACTORY PREPACKAGED SPLIT AC UNITS: SHALL CONSIST OF THE FOLLOWING:
1. CONDENSING UNITS: FACTORY PREPACKAGED AND ASSEMBLED SUITABLE FOR OUTDOOR INSTALLATION CONSTRUCTED FROM HEAVY GAUGE
GALVANIZED STEEL WITH RUST RESISTANT EPDXY FINISH. AC UNITS TO BE FACTORY ASSEMBLED WITH THE FOLLOWING COMPONENTS:
A. COMPRESSOR TO BE HERMETICALLY SEALED OF THE 1750 RPM TYPE, RESILIENTLY MOUNTED WITH POSITIVE LUBRICATION, CRANKCASE
HEATER, MOTOR OVERLOAD PROTECTION, SERVICE VALVES, FILTER DRYER, WITH SUCTION AND DISCHARGE SHUT OFF VALVES.
B. CONDENSER COIL: CONSTRUCTED OF COOPER TUBING WITH ALUMINUM FINS.
C. CONDENSER FAN: VERTICAL DISCHARGE, DIRECT DRIVE, AXIAL TYPE, RESILIENTLY MOUNTED WITH ALUMINUM GUARD AND TOTALLY
ENCLOSED, PERMANENTLY LUBRICATED BALL BEARING MOTOR WITH BUILT IN CURRENT AND OVERLOAD PROTECTION.
2. AIR HANDLING UNIT: SELF CONTAINED, DRAW THROUGH, FACTORY ASSEMBLED, PACKAGED AND PREWIRED AIR HANDLING UNITS, UL LISTED, ARI
AND AMCA RATED, OF CAPACITIES AND SIZES SHOWN ON DRAWINGS AND /OR HEREIN SPECIFIED AS FOLLOWS:
A. CABINET: HEAVY GAGE GALVANIZED STEEL WITH EXPOSED CORNERS AND EDGES ROUNDED, EASILY REMOVABLE PANELS, WITH INTERNAL
ONE (1) IN THICK NEOPRENE COATED FIBERGLASS INSULATION. FINISHED WITH STANDARD FACTORY BAKED ENAMEL FINISH.
B. EVAPORATOR COIL: EVENLY SPACED ALUMINUM FINS MECHANICALLY BONDED TO COPPER TUBES (DESIGNED FOR 150 PSIG.) WITH A 16
GAGE GALVANIZED STEEL INSULATED INTERNAL DRAIN PAN WITH DRAIN CONNECTION.
C. EVAPORATOR FAN: SINGLE INLET TYPE WITH STATICALLY AND DYNAMICALLY BALANCED CENTRIFUGAL WHEEL WITH FORWARD CURVED
SINGLE WIDTH BLADES, DIRECT DRIVEN, RESILIENTLY MOUNTED ON SLEEVE BEARINGS.
D. AIR FILTER: ONE (1) INCH THICK FIBERGLASS THROWAWAY OR PERMANENT WASHABLE TYPE, FILTER TO BE LOCATED IN FACTORY
FABRICATED FILTER RACK UPSTREAM OF EVAPORATOR COIL. PROVIDE ONE (1) SET OF REPLACEMENT FILTERS TO OWNER UPON
SUBSTANTIAL COMPLETION.
3. REFRIGERANT PIPING: SEAMLESS, HARD DRAWN, TYPE "L" COPPER TUBING OF SIZES RECOMMENDED BY UNIT'S MANUFACTURER FOR THE
APPLICATION SHOWN ON DRAWINGS. REFRIGERANT SUCTION LINES SHALL BE INSULATED USING 1" THICK FLEXIBLE UNICELLULAR PIPING UNSPLIT
INSULATION. ALL INSULATION SHALL COMPLY WITH NFPA 90 —A.
C
1. ` )" ROG, PMABLE ELECTRONIC THERMOSTATS: MANUFACTURED BY THE AC UNIT MANUFACTURER, THERMOSTAT SHALL HAVE THE FOLLOWING
FE�TtJRES.;,. ,AY PROGRAMMING CAPABILITY, DIGITAL DISPLAY, INSTANT OVERRIDE, AUTOMATIC ADJUSTMENT OF TEMPERATURES UP TO 4 TIMES
A DAY L ROAD% T IN FAHRENHEIT OR CELSIUS 24 HOUR CLOCK TAMPER RESISTANT, 1 I T
00 o SOLID STATE.
2. SMOKD�j CT��t,,,S: ROVIDE AN IONIZATION SMOKE DETECTOR SUITABLE FOR AIR DUCT INSTALLATION TO EACH AIR CONDITIONING UNIT.
SMOKE "DET 60 SHc BE AS FOLLOWS: LINE VOLTAGE (120/1/60) IONIZATION SMOKE DETECTORS OF THE MULTIPLE SAMPLE ELEMENTS TYPE,
WITH A "PO' 0
IN LIGHT. INSTALL SAMPLING ELEMENTS IN BOTH MAIN SUPPLY AND MAIN RETURN AIR DUCTS. ELECTRICALLY
CONNECT THE 10 IZATION SMOKE DETECTORS TO STOP ALL AIR CONDITIONING UNITS OPERATION IF PARTICLES OF SMOKE ARE DETECTED IN THE
AIR STREAM.
SEQUENCE OF CONTROL:
1. EQUIPMENT START SEQUENCE: THROUGH THE PROGRAMMABLE THERMOSTAT, UPON A CALL FOR COOLING, THE FOLLOWING EQUIPMENT SHALL
START IN SEQUENCE:
A. AIR COOLED CONDENSING UNIT
B. EVAPORATOR FAN
GUARANTEE & WARRANTY:
1. FABRICATE ALL DUCTWORK AND PROVIDE AND INSTALL ALL EQUIPMENT IN COMPLIANCE WITH THE CODES HAVING JURISDICTION, AS ENFORCED BY
THE LOCAL BUILDING OFFICIALS.
2. PROVIDE WRITTEN GUARANTEE STATING THAT THE CONTRACTOR, WILL REPLACE OR REPAIR, FREE OF CHARGE, ANY EQUIPMENT OR MATERIAL
WHICH FAILS DURING A ONE YEAR PERIOD FROM DATE OF SUBSTANTIAL COMPLETION.
ENGINEERING ASSURANCE:
1. THE EQUIPMENT HAS BEEN SELECTED, AND THE HVAC SYSTEM HAS BEEN DESIGNED, TO COMPLY WITH NATIONAL FIRE PROTECTION ASSOCIATION
AND WITH THE FLORIDA BUILDING CODE.
diez
architecture,
inc.
7430 sw 48th
street
miami, florida
33155
phone: (305)
663 -1970
fax: (305)
663 -2312
e —mail: peter®diezarchitecture.com
pedro diez, ra
president ar
0008996
ENGINEERING CONSULTANT
'.tom+,}
so
f tL
G141
Office Building
4th Floor
6141 SUNSET DRIVE
SOUTH MIAMI, FLORIDA
PROJECT No. 04- 158.04
REVISIONS
HVAC
SPECIFICATIONS
SCALE: AS SHOWN
DATE: DECEMBER 12, 2005
M -1.01