06-51-016DUCTWORK LEGEND
24x12
UP DN
IIIIIIIIIIIIIIIIIIIIIII
10x8 80
I
I�
101 IIIII
Ec� I
UC
r�
M -1
-NEW DUCTWORK, FIRST DIMENSION 15 SIDE SHOWN
- CHANGE OF ELEVATION
- FLEXIBLE DUCT
- TRANSITION, CONCENTRIC
- TRANSITION, ECCENTRIC
- TRANSITION, SQUARE -TO -ROUND
- SQUARE THROAT ELBOW
W /TURNING VANES
- RADIUS ELBOW
- RECTANGULARROUND BRANCH TAKE -OFF
OR ROUND /ROUND BRANCH TAKE -OFF
- MANUAL BALANCING DAMPER
- RECTANGLE -TO -ROUND TAKE -OFF
- STANDARD BRANCH TAKE -OFF
- SPIN -IN TAKE -OFF
- CEILING DIFFUSER, ROUND NECK
(CEILING DIFFUSERS ARE 4 -WAY THROW UNO)
-ROUND DIFFUSER
- CEILING RETURN
- CEILING EXHAUST FAN
- CEILING DIFFUSER, RECTANGULAR OR
SQUARE NECK (CEILING DIFFUSERS
ARE 4 -WAY THROW UNO)
- SUPPLY REGISTER OR GRILLE
(VERTICAL MOUNT, SIDEWALL)
-DOOR GRILLE
- UNDERCUT DOOR
- FLEXIBLE CONNECTION
- REVISION REFERENCE
- DETAIL REFERENCE: TOP - DETAIL,
BOTTOM - DRAWING' SHOWN ON
- THERMOSTAT /TEMPERATURE SENSOR
- CONNECT TO EXISTING
- DEMOLISH TO POINT INDICATED
AIR HANDLING UNIT SCHEDULE (DX
SPLIT)
MODEL
NO.
COOLING CAPACITY
PLAN
MODEL
MATCHING
OUTSIDE
TOTAL AIR
EXT.
ENT /LVG CONDITIONS
SAT
SUCT
TEMP
ELECTRICAL DATA
COMP.
RLA(EA)
ENT
ENT
LVG
L
HEATING
RS
O.D.
FAN
FLA
MAX
VOLT/
WEIGHT
MARK
NO.
COND. UNIT
AIR CFM
CFM
S.P.
2.2
38..0
50
208/3
I -1/8
1/2
llB
WB
DB
WB
KW /STEPS
H.P.
41.1
FUSE
PHASE
(LBS)
AHU -4 -1
RHGG -090
CU -4 -1
480
2400
1.0
18
ro5
5 r
55
305
9/2
1 -1/2
13
15
208/3
341
AHU -4 -2
RBHK -25
CU -4 -2
400
2000
0.15
18
r05
56
55
9.0
10.5/2
3/4
1.4
15
208/1
341
AHU -4 -3
RHGG -120
CU -4 -3
C 40
3200
1.25
18
r05
5ro
55
;
-
2
15
15
208/3
341
F 3
NOTES:
1 ALL MODELS BASED ON UNITS BY: METALAIRE
2 VERFIY MODELS AND FINISH WITH ARCHITECT
3 VERIFY MOUNTING FRAMES WITH ARCHITECT
4 PROVIDE SQUARE TO ROUND ADAPTER FOR CG.
5 PROVIDE PLASTER FRAMES FOR ALL AIR DEVICES.
TOTA O/A SUPPLIED =
1,520
NOTES:
I. MODEL NUMBERS ARE BASED ON RHEEM.
2. REFRIGERANT PIPING SIZED BASED ON USING LONG RADIUS ELBOWS EXCEPT FOR SUCTION LINE TRAP AT CONDENSING UNIT.
3, TABULATED REFRIGERATION CAPACITIES ARE REQUIRED CAPACITIE5 AT ENTERING, LEAVING AND CONDENSING TEMPERATURES INDICATED.
NOTE5:
I. MODEL NUMBERS ARE BASED ON RHEEM.
2. AIR HANDLING UNIT AND ASSOCIATED EXHAUST FAN SHALL SHUT DOWN UPON FIRE ALARM SIGNAL, DUCT SMOKE DETECTOR SENSING PRODUCTS OF COMBUSTION OR MANUAL ACTUATION OF AHU OR
EXHAUST STARTER TO "OFF" POSITION.
3. PROVIDE WITH 30% EFFICIENCY FILTERS IN COMPLIANCE WITH A5HRAE STANDARD 52 -16,
4. HEAD PRE55URE CONTROLLER FOR OPERATION IN AMBIENT TEMPERATURES DOWN TO 30 T,
5, PROVIDE SINGLE POINT ELECTRICAL CONNECTION. STARTER, RELAY, HEATING ELEMENT AND CONTROLS TO BE PART OF PACKAGED UNIT.
6. AMBIENT DESIGN TEMP 15 $5 T.
AIR COOLED CONDENSING UNIT SCHEDULE
PLAN
MARK
MODEL
NO.
COOLING CAPACITY
ELECTRICAL DATA
PIPING DATA
SEER
WEIGHT
(LBS)
GTC
(mbb)
TSC
(mbb)
AMB.
TEMP
SAT
SUCT
TEMP
NO.
COMP.
COMP.
RLA(EA)
NO.
FANS
COND.
FLA(EA)
MCA
MAX
FUSE
VOLT/
PHASE
RS
O.D.
RL
O.D.
F
GU -4 -1
BAWD -090
89.2
14.1
95
40
1
28.9
1
2.2
38..0
50
208/3
I -1/8
1/2
1
9.0
350
CU -4 -2
RANC -060
5/0.2
41.1
95
40
1
19.9
1
1.5
21,0
35
208/1
1 -1/8
1/2
1
13.0
305
CU -4 -3
BAWD -100
12(o.5
63.3
95
40
1
33.ro
2
2.2
41.0
80
208/3
1 -1/8
1/2
1
9.0
509
600 -WO
16x16
16x16
ROUND OR SQUARE
800 -1500
2040
2q 0
NECK AS REOD
1500 -3000
24x24
24x24
;
F 3
NOTES:
1 ALL MODELS BASED ON UNITS BY: METALAIRE
2 VERFIY MODELS AND FINISH WITH ARCHITECT
3 VERIFY MOUNTING FRAMES WITH ARCHITECT
4 PROVIDE SQUARE TO ROUND ADAPTER FOR CG.
5 PROVIDE PLASTER FRAMES FOR ALL AIR DEVICES.
NOTES:
I. MODEL NUMBERS ARE BASED ON RHEEM.
2. REFRIGERANT PIPING SIZED BASED ON USING LONG RADIUS ELBOWS EXCEPT FOR SUCTION LINE TRAP AT CONDENSING UNIT.
3, TABULATED REFRIGERATION CAPACITIES ARE REQUIRED CAPACITIE5 AT ENTERING, LEAVING AND CONDENSING TEMPERATURES INDICATED.
VAV UNIT SCHEDULE
FAN SCHEDULE
PLAN
MARK
MODEL
N0.
MFG.
TYPE
CFM
STAT IC
PRESS.
FAN
RPM
MOTOR
VOLT/
PHASE
DRIVE
TYPE
FAN
SERVICE
ACCESSORIES
RPM
HP/ W
EF -I
120C35
LOREN -COOK
CENTRIFUGAL
980
0.15
1315
1315
y HP
115/1
DIRECT
TOILET ROOMS
BIRD SCREENi SPEED CONTROLS FACTORY 12 "Hl ROOF CURB
95
8
0.15
2
1
V4 -3 -4
800
1200
125
10
0.15
3
1
NOTE:
I. REPLACE FAN EF -I 45 SHOWN ON 3RD FLOOR DRAWINGS WITH THE NEW FAN EF -I SHOWN HERE.
2, PROVIDE DIRECT DRIVE FANS WITH VARIABLE SPEED CONTROLLER
100
VAV UNIT SCHEDULE
PLAN
(MARK
DESIGN
CFM
MAX.
CFM
MIN.
CFM
INLET
SIZE
MAX.
APD
(IN WG)
HEATING COIL
KW
STEPS
V4 -3 -1
550
800
95
8
0.15
2
1
V4 -3 -2
600
800
95
8
0.15
2
1
V4 -3 -3
600
800
95
8
0.15
2
1
V4 -3 -4
800
1200
125
10
0.15
3
1
V4 -3 -5
100
1200
125
10
0.15
3
1
501 -WO
2424
16 "0
RA
RH
0 -250
10x6
12 10
FINISH: SEE ARCH DM
ER
250.400
12x8
14 110
DAMPER YES
400 -600
12x12
16 110
MATERIAL: ALA' AN
600 -WO
16x16
16x16
ROUND OR SQUARE
800 -1500
2040
2q 0
NECK AS REOD
1500 -3000
24x24
24x24
;
F 3
NOTES:
1 ALL MODELS BASED ON UNITS BY: METALAIRE
2 VERFIY MODELS AND FINISH WITH ARCHITECT
3 VERIFY MOUNTING FRAMES WITH ARCHITECT
4 PROVIDE SQUARE TO ROUND ADAPTER FOR CG.
5 PROVIDE PLASTER FRAMES FOR ALL AIR DEVICES.
NOTES:
1. 5A515 OF DESIGN: TITU5 MODEL "DESV"
2. ALL HEATING COILS UNDER 5K SHALL BE 208VA VERIFY WITH ELECTRICAL
DRAWINGS AVAILABLE VOLTAGE PRIOR ORDERING A/C EQUIPMENT,
3, SEQUENCE OF CONTROL: ON A RISE OF ROOM TEMPERATURE THE ELECTRIC HEAT
WILL DE- ENERGIZE. ON A FURTHER R15E OF ROOM TEMPERATURE THE VAV
CONTROLLER WILL MODULATE COOL AIRFLOW FROM MINIMUM (SEE SCHEDULE) TO
MAXIMUM SETTING.
AIR DISTRIBUTION SCHEDULE
YES
TAG
MODEL
AIRFLOW
DIFF
DUCT
I ACCESSORIES/
505
SMOKE DAMPER(S)
(CFM)
SIZE
SIZE
CONSTRUCTION
A
LTCD
0-25
6x6
4 10
FINISH: SEE ARCH DIW
100
SMOKE CONTROL
25 -15
8x8
6 110
O.B.D.: YE5
0
3
80 - 150
10x10
8 "0
MATERIAL: ALUMINUM
1
136 -250
124
10 "0
ROUND NECK
251.400
16x16
12 "0
316 -650
2Cx20
14 "0
501 -WO
2424
16 "0
RA
RH
0 -250
10x6
12 10
FINISH: SEE ARCH DM
ER
250.400
12x8
14 110
DAMPER YES
400 -600
12x12
16 110
MATERIAL: ALA' AN
600 -WO
16x16
16x16
ROUND OR SQUARE
800 -1500
2040
2q 0
NECK AS REOD
1500 -3000
24x24
24x24
;
F 3
NOTES:
1 ALL MODELS BASED ON UNITS BY: METALAIRE
2 VERFIY MODELS AND FINISH WITH ARCHITECT
3 VERIFY MOUNTING FRAMES WITH ARCHITECT
4 PROVIDE SQUARE TO ROUND ADAPTER FOR CG.
5 PROVIDE PLASTER FRAMES FOR ALL AIR DEVICES.
HVAC DESIGN "Q
YES
NO
DUCT SMOKE DETECTOR(S)
CFM /
SQ. FT.
PEOPLE
DENSITY
FIRE DAMPER (S)
RECEPTION
505
SMOKE DAMPER(S)
15
FIRE RATED ENCLOSURE
454
OFFICE
FIRE RATED ROOF/FLOOR CEILING ASSEMBLY
1
20
FIRE STOPPING
39
100
SMOKE CONTROL
1,485
N/A
1
ily i .: F-Aly 1,611VII v a 9
1. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH
MANUFACTURER'S CERTIFIED DRAWINGS. TRANSITIONS TO ALL
EQUIPMENT SHALL BE VERIFIED AND PROVIDED FOR EQUIPMENT
FURNISHED.
2. VERIFY AT JOB SITE AVAILABLE VOLTAGE PRIOR TO ORDERING
EQUIPMENT.
3. NOTIFY ARCHITECT OF ANY DISGRE PANG IES BETWEEN
CONSTRUCTION DOCUMENTS AND ACTUAL FIELD CONDITIONS.
4, DIMEN31ON3 SHALL BE FIELD - VERIFIED AND COORDINATED
PRIOR TO PROCUREMENT OR FABRICATION. COORDINATE THE
WORK WITH OTHER TRADES INVOLVED. FIELD MODIFICATIONS
SUCH AS OFFSETS IN PIPING OR DUCTWORK (INCLUDING DIVIDED
DUCTWORK) NEEDED DUE TO OBSTRUCTIONS OR INTERFERENCE
SHALL BE PROVIDED AT NO ADDITIONAL COST. FOR PROJECTS
INVOLVING RENOVATION, COORDINATE NEW WORK WITH EXISTING
ELEMENTS SUCH AS THE BUILDING STRUCTURE AND
ARCHITECTURAL FEATURES, 5PRINKLER PIPING, LIGHTS,
PLUMBING, AND ELECTRICAL CONDUIT.
5. DUCT CONSTRUCTION SHALL E3E IN ACCORDANCE WITH THE
LATEST EDITION OF THE 5MACNA HVAG DUCT CONSTRUCTION
STANDARD.
ro. PROVIDE AIR TURNING VANES IN ALL 90 DEGREE RECTANGULAR
DUCT ELBOWS.
7, DUCT SIZES AND ALL OPENINGS THROUGH BUILDING
CONSTRUCTION SHALL SUIT EQUIPMENT FURNISHED.
S. COORDINATE DIFFUSER, GRILLE AND REGISTER LOCATIONS WITH
ARCHITECTURAL CEILING PLANS AND EQUIPMENT FROM ALL
TRADES.
9, PROVIDE PROGRAMMABLE THERMOSTAT FOR ALL AIR HANDLING
UNITS.
10. LOCATE THERMOSTATS, TEMPERATURE SENSORS, HUMIDISTATS,
AND HUMIDITY 5EN50R5 AT 48" ABOVE FINISHED FLOOR UNLE55
NOTED OTHERUJi5E. COORDINATE LOCATIONS WITH OTHER
EQUIPMENT, FURNITURE, AND DOOR SWINGS.
11. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS
DETAILED AND /OR SPECIFIED. PROVIDE ADDITIONAL
5UPPORTS AS REQUIRED TO PROVIDE A VIBRATION -FREE, RIGID
INSTALLATION.
12. ALL DUCT SIZES SHOWN ARE IN51DE CLEAR DIMENSIONS.
13. DAMPER5 AND IN51DE5 OF DUCTS V151BLE THROUGH GRILLES,
REGISTERS AND DIFFU5ER5 SHALL BE PAINTED FLAT BLACK.
14. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF
EQUIPMENT.
15. TRAPPED CONDENSATE DRAINS FROM ALL MECHANICAL
EQUIPMENT SHALL BE PROVIDED FOR PROPER DRAINAGE TO
SUIT EQUIPMENT FURNISHED.
fro. ACCE55 PANELS IN DUGTWORK AND CEILING5 SHALL BE
PROVIDED WHERE REQUIRED FOR OPERATION, BALANCING OR
MAINTENANCE OF ALL MECHANICAL EQUIPMENT.
11. ALL DUCTWORK AND PIPING 15 SHOWN SCHEMATICALLY. PROVIDE
ALL TRANSITIONS, TURNING VANES, ELBOW5, FITTINGS, ETC., TO
ALLOW SMOOTH FLOWS.
18. ALL SPLIT DUCT FITTINGS SHALL TRANSITION TO FULL 51ZE OF THE
SUM OF BOTH BRANCHES, UPSTREAM OF SPLIT,
19. VERIFY MODELS AND FINISH WITH ARCHITECT PRIOR TO
PURCHASING GRILLES, REGISTERS, DIFFUSERS, LOUVERS AND
OTHER AIR DISTRIBUTION DEVICES.
20.PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTWORK
CONNECTING TO EAGH FAN, AIR HANDLING UNITS, AND FAN COIL
UNITS.
21, PROVIDE TRAN5ITION3 AT DIFFUSER NECKS AS REQUIRED TO
MATCH SIZES OF FLEX DUCTS TO BE CONNECTED.
22. INTERRUPTIONS TO EXISTING SERVICE5 SHALL BE SCHEDULED
FOR TIMES OTHER THAN NORMAL OPERATING HOURS (SUCH AS
NI(SHT5 AND WEEKENDS). SUCH INTERRUPTIONS TO 5ERVICE5
SHALL NOT BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF
THE OWNER'5 REPRESENTATIVE AND PROPER COORDINATION
WITH OTHER TRADES. PRE -WORK SHALL BE PERFORMED TO
MAKE THE SHUTDOWN PERIOD AS BRIEF AS POSSIBLE,
23. MAINTAIN CLEARANCE OF A MINIMUM OF r0" BETWEEN DUCTWORK,
PIPING, EQUIPMENT, ETC., AND ALL FIRE RATED AND FIRE /SMOKE
RATED PARTITIONS TO ALLOW FOR INSPECTIONS OF RATED
WALL5.
24, DUCT RUNOUT5 TO DIFFUSERS SHALL MATCH THE SIZE OF THE
DIFFUSER NECK. UNLE55 OTHERWISE NOTED,
25. ALL EQUIPMENT AND VALVE DRAINS SHALL BE INDEPENDENTLY
PIPED FULL 51ZE TO THE NEAREST PLUMBING DRAIN.
ASIIRAE STANDARD 62 -2001
OUTDOOR AIR REQUIREMENTS FOR VENTILATION
APPLICATION
AREA
(SF)
PEOPLE /
1000 SF
CFM /
PERSON
CFM /
SQ. FT.
PEOPLE
DENSITY
O/A
CFM
RECEPTION
505
60
15
30
454
OFFICE
5,555
1
20
39
100
STORAGE / CORRIDORS
1,485
N/A
N/A
0.05
0
3
BREAK ROOM
145
5
20
1
20
TOTAL
1,690
10
1,262
diez
architecture,
inc.
7430 sw 48th
street
miami, florida
33155
phone: (305)
663 -1970
fax: (305)
663 -2312
e -mail: peter ®diezarchitecture.com
pedro diez, ra
president or
0008996
ENGINEERING CONSULTANT
AJ • t+. '•
U �• *' 4 r ..1 3
J
�'{� �.+' •�•• 'J /tom`` �,
6747
Office Building
4th Floor
6141 SUNSET DRIVE
SOUTH MIAMI, FLORIDA
PROJECT No. 04- 158.04
REVISIONS
FOURTH FLOOR
HVAC SCHEDULES
NOTES AND LEGEND
SCALE: AS SHOWN
DATE: DECEMBER 12, 2005
M -1.00