06-51-007PENETRATION AS LISTED BELOW I HOUR FIRE RATED WALL ASSEMBLY REFER TO WALL TYPE FOR ADDITIONAL INFORMATION FILL MATERIAL ER AL TO B FORCED INTO ANNUL TO MAXIMUM EXTENC POSSIBLE 1/4' TO 1/2' LARGER THAN OUTSIDE DIAP' OF PENETRANT FILL MATERIAL A MINIMUM 1/2' CROWN TO FORM AROUND PENETRATING ITEM AND LAPPING 1/4' BEYOND PERIPHERY SECTION A -A I- PENETRANT TYPE ( ONE OF THE FOLLOWING) A. STEEL PIPE NOMINAL 12' DIA OF SMALLER, SCHEDULED OR HEAVIER B. CONDUIT NOMINAL 6' DIA OR SMALLER, EMT OR STEEL CONDUIT C. COPPER TUBING NOMINAL 6' DIA OR SMALLER TYPE L OR HEAVIER D. COPPER TUBING NOMINAL 6' DIA OR SMALLER, REGULAR OR HEAVIER 2- FIRESTOP SYSTEM NILTI CONSTRUCTION CHEMICALS INC. TYPE F5 605 OR F5 ONE SEALANT q 1 HR FIRE RATING UL DESIGN NO: W -L- 1085 rED r REFER -OR ADDITIONAL A SLANT TO COMPLETELY FILL - IULAR SPACE BETWEEN THE E AND GYPSUM BOARD iEMBLY 4 3/4, MAX 11/4' 'PE AS LISTED SECTION A -A I- PENETRANT TYPE ( ONE OF THE FOLLOWING) A. NON METALLIC PIPE, POLY VINYL. CLORIDE (PVC) NOM 2' DIA OR SMALLER 2- FIRE5TOP SYSTEM NILTI CONSTRUCTION CHEMICALS INC. TYPE F5 611A OR FS ONE SEALANT C 1 HR FIRE RATING UL DESIGN NO: W -L- 2098 I_1 K IR FIRE RACED WALL AVE, EMBLY :FER TO WALL TYPE FOR ADDITIONAL =ORMAT I ON EENETRANT TYPE A L157ED BELOW N SEALANT TYPICAL 30TH ENDS 1 -11 5/8' 1 KNE55 OF FI.__ APPLIED WITH THE ANNUL.US, FLUSH WITH BOTH 5URFACE5 OF WALL - A� SECTION A -A 1. PENETRANT TYPE (ONE OR MORE NOMINAL I' DIA) A STEEL ELECTRIC TUBING; MINIMUM 1/2' MAX 1' CONDUIT RIGIDL'r1' SUPPORTED ON BOTH SIDES OF WALL 2. FIRESTOP SYSTEM HILTI CONSTRUCTION CHEMICALS INC. TYPE F5 ONE SEALANT 1 HR FIRE RATING 3" UL DESIGN NO W -L -1095 1/2' MIN THICKNESS APPLIED WITHIN ANNULU* FLUSH WITH BOTH 51DE5 OF WALL SEALANT AND PACKING MATERIAL MIN 3' THK OF 5 PCF MINERAL WOOD BATT FOR PIPES 4' SMALLER 12' MAX DIA OF OPENING ANNULAR SPACE SHALL BE 0 AT THE POINT OF CONTACT TO A MAX OF 11/4' OF OUT51DE DIAMETER OF PENETRANT 6' CMU ASSEMBLY 1 HOUR RATED REFER TO WALL TYPES AND LIFE SAFETY PLANS FOR ADDITIONAL INFORMATION SECTION A -A 1- PENETRANT TYPE ( ONE OF THE FOLLOWING) A. STEEL PIPE NOMINAL 10' DIA OF SMALLER, SCHEDULED OR HEAVIER B. CONDUIT NOMINAL 4' DIA OR SMALLER, EMT OR STEEL CONDUIT C. COPPER TUBING NOMINAL 4' DIA OR SMALLER TYPE L OR HEAVIER D. COPPER TUBING NOMINAL 4' DIA OR SMALLER, REGULAR OR HEAVIER 2- FIRESTOP SYSTEM NILTI CONSTRUCTION CHEMICALS INC. TYPE F5 601 / OR F5 604 / F5 ONE SEALANT 1 HR FIRE RATING UL DESIGN NO: C -AJ -1149 ■! ®1 IHR FIRE RATED WALL ASSEMBLY REFER TO WALL TYPE NON -RATED Al,l. A ",MB -Y IRE F R- L TYPE R 1 HR FIRE RATED PARTITION JOINT DETAIL GENERAL NOTES I. ALL THROUGH PENETRATIONS SHOWN ABOVE ARE BASED UPON SPECIFIC PRODUCTS AND MANUFACTURERS. FOR OTHER ACCEPTABLE MANUFACTURER'S REFER TO PROJECT SPECIFICATIONS, 2. ALL ASSEMBLIES SHOWN ABOVE ARE REPRESENTATIVE ONLY FOR COMPLETE CONSTRUCTION REQUIREMENT. REFER TO EACH ASSEMBLY NUMBER IN THE 'UL' MANUAL, VOLUME 2, 1999 EDITION, 3. FOR OTHER APPLICABLE REQUIREMENTS REFER TO PROJECT SPECIFICATIONS. 4. FOR FIRE RATED WALL ASSEMBLY TYPES BEARING UL LABILE REFER TO PARTITION TYPES. ENGINEERING CONSULTANT G141 Office Building 4th Floor 6141 SUNSET DRIVE SOUTH MIAMI, FLORIDA PROJECT No. 04- 158.04 REVISIONS FIRE PENETRATION DETAILS 00 i -, o r I SCALE: AS SHOWN f S