06-1828R-005GENERAL ELECTRICAL NOTES
— ALL ELECTRICAL WORK PERFORMED UNDER THIS CONTRACT SHALL
COMPLY WITH LOCAL CODES AND ORDINANCES AND ALL STANDARDS
OF CONSTRUCTION ESTABLISHED BY THE LANDLORD.
— SUBMIT SHOP DRAWINGS FOR ACCEPTANCE BY THE ARCHITECT
AND /OR ENGINEER BEFORE PROCEEDING WITH THE PURCHASE OR
INSTALLATION OF THE EQUIPMENT AND MATERIALS. NO FACSIMILES
OR FACSIMILE COPIES SHALL BE ACCEPTED.
— ALL CONDUCTORS SHALL BE THW OR THWN COPPER. ALL EXPOSED
CONDUITS SHALL BE RUN AS NEAT AS POSSIBLE. P.V.C. CONDUIT
SHALL ONLY BE USED IN SLAB OR UNDERGROUND AT A MINIMUM
DEPTH OF 24 INCHES.
— ALL DEDICATED OUTLETS SERVING EQUIPMENT SUCH AS REFRIGERATORS,
WATER COOLERS, COPIERS, FAXES, ETC. SHALL HAVE SEPARATE NEUTRAL
CONDUCTORS TO EACH DEVICE OR APPLIANCE.
— FLEXIBLE CONDUIT SHALL BE USED FOR CONNECTION TO ALL
VIBRATING EQUIPMENT SUCH AS MOTORS, ETC.
— ALL WIRING DEVICES SHALL BE LEVITON COMMERCIAL GRADE (WHITE
DECORA) OR EQUAL AS APPROVED BY ARCHITECT OR ENGINEER.
— ALL RECEPTACLES SHALL BE INSTALLED AT 18" A.F.F. UNLESS
OTHERWISE NOTED.
— ELECTRICAL POWER AND CONTROL WIRING FOR H.V.A.C. AND
MECHANICAL EQUIPMENT SHALL BE FURNISHED AND INSTALLED BY THE
ELECTRICAL CONTRACTOR.
— ELECTRICAL CONTRACTOR SHALL VERIFY THE CEILING FINISHES AND
SUSPENSION SYSTEMS FOR SELECTION OF THE PROPER TRIM AND
SUPPORT ARRANGEMENTS OF THE FIXTURE.
— ELECTRICAL CONTRACTOR SHALL COORDINATE HIS WORK WITH THE
ARCHITECT BEFORE ROUGH INSTALLATION OF LIGHTS, RECEPTACLES,
SWITCHES AND EQUIPMENT FOR EXACT LOCATION.
— ALL ELECTRICAL EQUIPMENT SHALL BE APPROVED AS SAFE FOR USE
IN THE U.S. WORKPLACE, AS PER A "NRTL" RECOGNIZED ORGANIZATION.
(U.L., C.S.A., ETC.)
— ALL BRANCH CIRCUITS SHALL BE SIZED IN ACCORDANCE WITH N.E.C.
210 -19 REGARDLESS OF SIZES SHOWN ON PLANS OR PANEL SCHEDULES.
— PROVIDE EXPANSION JOINTS WHERE REQUIRED AS PER N.E.C. 300 -7(b).
— ALL UNDERGROUND CONDUIT INSTALLATIONS SHALL COMPLY WITH N.E.C.,
TABLE 300 -5.
— IF ANY COF +LICT IS ENCOUNTERED WITHIN THE DESIGN DOCUEMNTS,
REGARDLESS OF TRADE OR RESPONSIBILITY, THE GREATER SCOPE OF
WORK SHALL PREVAIL.
0
ELECTRICAL POWER PLAN
VERIFY WITH OWNER CABLE TYPE TO BE
INSTALLED BETWEEN CPU'S AND DISPLAY
MONITORS FOR THE DIGITAL X —RAY SYSTEM IN
PATIENT CARE ROOMS. ENSURE CONDUITS FOR
DATA DROPS ARE LARGE ENOUGH TO ACCEPT
THESE CABLES. VERIFY EXACT MOUNTING
HEIGHT PRIOR TO INSTALLATION.
VERIFY ALL DETAILS FOR THE X —RAY ROOM AND
EQUIPMENT PRIOR TO INSTALLATION. CONTACT
CARLOS VELOSO OF DIEZ ARCHITECTURE INC.
3/16n
THE OWNER HAS REQUESTED THAT PHONE LINES
ONLY BE INSTALLED WHERE THE PHONE SYMBOLS
DENOTE. THE DATA SYMBOLS DENOTE LOCATIONS
FOR INSTALLATION OF DATA CABLING.
diez
archit
inc.
ecture,
7430 sw 48th
street
miami, florida
33155
phone: (305)
663 -1970
fax: (305)
663 -2312
e —mail: peter®diezarchitecture.com
pedro diez, ra
president ar
0008996
ENGINEERING CONSULTANT
Puga and Associates, Inc.
Engineers /Consultants
# EB 0005813
7326 S.W. 48th Street
Miami, Florida 33155
(305) 661 -7700
`l�tt. jq"
elmm
4th FLOOR
6141 SUNSET DRIVE
SOUTH MIAMI, FLORIDA
PROJECT No. 04.158.041
REVISIONS
&1 03/13/07 Owner Revision
SCALE: AS SHOWN
DATE: October 9, 2006
E -1
1 200
LnAul`,.b:.
SCALE: AS SHOWN
DATE: October 9, 2006
E -1