06-1828R-004LEGEND
ABV
ABOVE
CD
CEILING DIFFUSER
CFM
CUBIC FEET PER MINUTE
CLG.
CEILING
CONN
CONNECT, CONNECTION
DB
DRY BULB
DDC
DIRECT DIGITAL CONTROL
DI
DIGITAL INPUT
DN
DOWN
DP
DIFFERENTIAL PRESSURE
DR
DRAIN
DWG
DRAWING
EA.
EACH
ENT
ENTERING
EQUIP
EQUIPMENT
GA.
GAUGE
GALV.
GALVANIZED
HTR.
ELECTRICAL HEATER
HP
HORSEPOWER
KW
KILOWATTS
IN
INCHES
MAX.
MAXIMUN
MIN
MINIMUN
No.
NUMBER
NTS
NOT TO SCALE
0/A
OUTSIDE AIR
P.D.
PRESSURE DROP
PSF
POUND PER SQUARE FOOT
QTY
QUANTITY
R/A
RETURN AIR
RPM
REVOLUTIONS PER MINUTE
RTU
ROOFTOP UNIT
S/A
SUPPLY AIR
S.P.
STATIC PRESSURE
SPS
STATIC PRESSURE SENSOR
TEMP.
TEMPERATURE
TRF
TRANFER
TS
TEMPERATURE SENSOR
TYP.
TYPICAL
UC
UNDERCUT
UP
UP
VAV
VARIABLE AIR VOLUME
VD
MANUAL VOLUME DAMPER
VEL
VELOCITY
VVT
VARIABLE VOLUME AND TEMPERATURE
V /PH
VOLTAGE /PHASE
WB
WET BULB
- - -�
DASHED LINES DEPICT EXISTING
0.8
DUCTWORK / DEVICES TO REMAIN.
BRANCH TAKEOFF WITH 450 SHOE FITTING
WITH MANUAL VOLUME DAMPER.
DUCT ELBOW WITH DOUBLE
THICKNESS TURNING VANES
CJOCXXXX)•
FLEXIBLE ROUND DUCT. INSIDE DIMENSIONS.
1
-- ®-- SUPPLY AIR, CEILING MOUNTED REGISTER
RETURN AIR, CEILING MOUNTED REGISTER
DIFFUSER GRILLE TAG WITH REQUIRED
O560 AIR VOLUME. SEE SCHEDULE FOR SIZES
CFM AND THROW PATTERN.
DIAMETER
O T� ROOM THERMOSTAT OR THERMIDISTAT.
1 NUMBER NEXT TO SYMBOL DENOTES
A/C UNIT MARK.
FD FIRE DAMPER, EQUAL TO AIR BALANCE INC.,
A MODEL 119C, LEAKAGE CLASS II. SIZE
DAMPER AS REQUIRED TO MAINTAIN SAME
FREE AREA AS DUCT.
VD MANUAL VOLUME DAMPER
SD DUCT MOUNTED SMOKE SENSOR
HVAC DESIGN REQUIRES:
YES
NO
DUCT SMOKE DETECTOR
AHU -2
AHU -3
FIRE DAMPER(S)
CEILING
e -mail: peter®diezarchitecture.com
SMOKE DAMPER(S)
WAITING ROOD
SYSTEM /AREA SERVED
FIRE RATED ENCLOSURE
0008996
FIRE RATED ROOF FLOOR
CEILING ASSEMBLY
MANUFACTURER
COOK
FIRE STOPPING
TRANE
= - - - - -
SMOKE CONTROL
GC -140
MODEL NUMBER
J
EXHAUST FAN SCHEDULE
MARK
EF -1,2
AHU -1
AHU -2
AHU -3
LOCATION
CEILING
e -mail: peter®diezarchitecture.com
AREA SERVED
WAITING ROOD
SYSTEM /AREA SERVED
RESTROOMS
0008996
MANUFACTURER
COOK
TRANE
TRANE
= - - - - -
MODEL NUMBER
GC -140
MODEL NUMBER
TWEO49E13FB
TWEO49E13FB
WEIGHT (LBS) APPROX.
18
NOMINAL TONS
SYSTEM TYPE
EXHAUST
5.0
DESIGN CFM SETTING
75
14.00
14.00
13.50
E.S.P. (IN WATER)
0.25
TOTAL AIR SUPPLY CFM
1,490
FAN TYPE
CENTRIFUGAL
FAN RPM
1,058
200
280
MOTOR SIZE HP
43 WATTS
ELECTRICAL SERVICE
115/1/60
z
DRIVE TYPE
DIRECT
CONTROL
FSC 5
1,230
1,310
1,360
SONE RATING (MAX.)
1.9
c�
BACKDRAFT DAMPER MODEL No.
100 SERIES
z
ACCESSORIES /REMARKS
GEMINI ISO KIT
0
EXTERNAL STATIC PRESSURE I.W.G.
0.6
0.6
0.8
z
NOTES:
1 FANS LOCATED ON THE EXTERIOR OF THE BUILDING SHALL BE CONSTRUCTED AND INSTALLED TO WITHSTAND A
WIND PRESSURE OF FROM ANY DIRECTION AS PER F.B.C.
2 ALL FANS SHALL HAVE UL APPROVED LOCAL DISCONNECT MEANS, SUPPLIED BY ELECTRICAL CONTRACTOR.
3 ROOF FANS AND VENTS SHALL HAVE BACK -DRAFT DAMPERS AND BIRD SCREENS.
4 FANS SHALL BE OF WELDED CONSTRUCTION UTILIZING CORROSION RESISTANT FASTENERS. ALL STEEL FAN
COMPONENTS SHALL HAVE A SUPERFICIAL ELECTROSTATIC COATING TREATMENT TO PREVENT CORROSION.
5 MOTORS SHALL BE HEAVY DUTY TYPE WITH PERMANENTLY LUBRICATED SEALED BALL BEARINGS AND FURNISHED
TO THE SPECIFIED VOLTAGE, PHASE AND ENCLOSURE.
6 FAN SHALL BE OF AN AMERICAN MANUFACTURER AND MANUFACTURED AT AN ISO 9001 CERTIFIED FACILITY.
7 ALL FAN SHALL BEAR AMCA CERTIFIED RATING AND UL LISTING.
8 FANS EF -1 AND 2 SHALL BE SWITCHED BY LIGHTS.
--- - - -----
A/C EQUIPMENT SCHEDULE
street
UNIT DESIGNATION
AHU -1
AHU -2
AHU -3
fax: (305)
663 -2312
e -mail: peter®diezarchitecture.com
AREA SERVED
WAITING ROOD
OFFICES
OFFICES
0008996
UNIT MANUFACTURER
TRANE
TRANE
TRANE
= - - - - -
. L _ISYytm dL L.�
MODEL NUMBER
TWEO49E13FB
TWEO49E13FB
TWE065EIYB
NOMINAL TONS
4.0
4.0
5.0
SYSTEM (S)EER
14.00
14.00
13.50
TOTAL AIR SUPPLY CFM
1,490
1,510
1,640
OUTSIDE AIR CFM
260
200
280
z
RETURN AIR CFM
1,230
1,310
1,360
c�
z
0
EXTERNAL STATIC PRESSURE I.W.G.
0.6
0.6
0.8
z
=
FAN SIZE HP
3/4
3/4
3/4
a
FAN MOTOR FLA AMP
7.0
7.0
7.0
ENTERING AIR TEMPERATURE (DB /WB)° F
79.3 66.7
779 64.0
79'1 65.5
LEAVING AIR TEMPERATURE (DB /WB)° F
0 56.0
%8 53.1
55.5 54.0
TOTAL COOLING COIL CAPACITY MBH
46.9
49.0
56.5
TOTAL SENSIBLE CAPACITY MBH
33.0
38.9
41.7
TOTAL HEATING CAPACITY MBH
12.3
12.3
12.3
ELECTRIC HEATER SIZE (230 V) Kw
5
5
5
HEATER MCA / MOCP AMP
24
24
24
25
25
25
ELECTRICAL CHARACTERISTICS V /O /Hz
208/1/60
208/1/60
208/1/60
WEIGHT lbs.
196
196
196
DIMENSIONS (HxWxD) INCH
63x26x21
63x26x21
63x26x21
UNIT DESIGNATION
CU -1
CU -2
CU -3
UNIT MANUFACTURER
TRANE
TRANE
TRANE
MODEL NUMBER
2TTA3048A3000A
2TTA3048A3000A
2TTA3060A3000A
LOCATION
ROOF
ROOF
ROOF
Fz
AMBIENT TEMPERATURE ° F
95
95
95
z
z
REFRIGERANT R
22
22
22
0
v
COMPRESSOR MOTOR RLA AMP
11.6
11.6
17.3
0
w
o
FAN MOTOR SIZE HP
1/6
1/6
1/5
0
o:
FAN MOTOR FLA AMP
1.4
1.4
1.2
a
MCA / MOCP AMP
16
16
23
25
25
40
ELECTRICAL CHARACTERISTICS V /O /Hz
208/3/60
208/3/60
208/3/60
WEIGHT lbs.
267
267
256
DIMENSIONS (HxWxD) INCH
410704
410704
41x37x34
NOTES:
1 ALL UNITS SHALL BE HORIZONTALLY MOUNTED WITH TOP SUPPLY AND BOTTOM RETURN AS INDICATED ON
DRAWINGS.
2 SIZE REFRIGERATION PIPING AS PER MANUFACTURER RECOMMENDATIONS. OVERSIZE LINES AS REQUIRED TO
COMPENSATE FOR LINE LOSS WITH MINIMUM CAPACITY REDUCTION. SUBMIT SHOP DRAWINGS.
3 AIR HANDLING UNIT SHALL CONTAIN SOLID STATE INTERLOCK BOARD WITH BUILT IN FUSE AND TIME DELAY RELAY.
4 PROVIDE 5 YEAR WARRANTY ON ALL REFRIGERATION COMPONENTS.
5 PROVIDE ALL RELAYS, TRANSFORMERS, ETC. AS REQUIRED FOR COMPLETE OPERATING SYSTEM.
6 UNITS SHALL BE PROVIDED WITH A 4 INCH THICK PLEATED FILTER WITH A 30% MINIMUM EFFICIENCY. UNIT
CONSTRUCTION AND INSTALLATION SHALL GUARANTEE AN EASY ACCESS TO FILTER SECTION FOR PROPER FILTER
INSPECTION AND REPLACEMENT.
7 UNIT INSULATION AND ADHESIVE SHALL COMPLY WITH NFPA 90A REQUIREMENTS FOR FLAME SPREAD AND SMOKE
GENERATION. INSULATION SHALL CONTAIN AN EPA REGISTERED IMMOBILIZED ANTI - MICROBIAL AGENT TO EFFECTIVELY
RESIST THE GROWTH OF BACTERIA AND FUNGI IN ACCORDANCE WITH ASTM STANDARDS G21 AND G22.
8 FAN MOTOR SHALL BE HIGH EFFICIENCY TYPE.
9 FAN AND MOTORS SHALL BE PROVIDED WITH CIRCUIT PROTECTION.
10 CONDENSATE DRAIN PANS SHALL BE INSULATED AND SLOPED TO OUTLET. PANS SHALL HAVE STAINLESS STEEL
LINERS. PROVIDE A OVERFLOW DETECTION SYSTEM CAPABLE OF SHUTDOWN THE UNIT UPON DECTTON OF HIGH
LEVELS CONDENSATE DRAIN.
11 SUPPORT UNIT HIGH ENOUGH ABOVE CEILING TO ACCOMMODATE CONDENSATE DRAIN TRAPS IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS.
12 THE FAN DRIVE SHALL BE SELECTED FOR 125% OF THE MOTOR RATED HORSEPOWER.
13 CONTRACTOR SHALL GUARANTEE ADECUATE CLEARANCE ALL AROUND THE UNIT FOR MAINTENANCE ACCESS.
14 CONDENSING UNIT SHALL BE INSTALLED TO WITHSTAND WIND PRESSURE FROM ANY DIRECTION AS PER THE
"HVHZ" REQUIREMENTS OF THE F.B.C.
15 ALL UNITS SHALL BE OF DOUBLE WALL CONSTRUCTION. ALL UNITS SHALL BE PROVIDED WITH ADEQUATE
INSULATION. PROVIDE INSULATION LINERS TO PREVENT SURFACE CONDENSATION UNDER ALL CONDITIONS.
16 ALL UNITS SHALL HAVE A STAINLESS STEEL, DOUBLE SLOPED DRAIN PAN WITH INSULATION LINERS IN
ACCORDANCE WITH ASHORE 62.
17 UNITS SHALL BE OF AMERICAN MANUFACTURER, DESIGNED AND RATED IN ACCORDANCE WITH ALL APPLICABLE
ASHRAE, AIR AND NFPA CODES AND STANDARDS AND SHALL BE UL LISTED.
18 CONDENSER COILS SHALL BE PROVIDED WITH A PROTECTIVE GUARD.
19 ALL UNITS SHALL BE PROVIDED WITH A 2 -STAGE PROGRAMMABLE, DIGITAL THERMOSTAT WITH DEHUMIDIFICATION
CONTROL EQUAL TO HONEYWELL MODEL No. TH8321U1006 AND SHALL BE CAPABLE OF PROVIDING AFTER HOURS
SET BACK FOR ENERGY CONSERVATION PURPOSES.
20 DUCT MOUNTED SMOKE DETECTOR FOR ALL UNITS SHALL BE PROVIDED AND INSTALLED BY MECHANICAL
CONTRACTOR AND WIRED BY FIRE ALARM CONTRACTOR.
i
c
diez
architecture
inc.
7430 sw 48th
street
miami, florida
33155
phone: (305)
663 -1970
fax: (305)
663 -2312
e -mail: peter®diezarchitecture.com
^
pedro diez, ro
president ar
0008996
ENGINEERING CONSULTANT
Puga and Associates, Inc.
Engineers /Consultants
# EB 0005813
7326 S.W. 48th Street
Miami, Florida 33155
(305) 661 -7700
1�. IT. jq"
elf cea
4th FLOOR
6141 SUNSET DRIVE
SOUTH MIAMI, FLORIDA
PROJECT No. 04.158.041
REVISIONS
,1 03/13/07 Owner Revision
SCALE: AS SHOWN
DATE: October 9, 2006
M -3
�,•,
t:
^
} I,
. r� ( r
MA
'•t I
. L _ISYytm dL L.�
SCALE: AS SHOWN
DATE: October 9, 2006
M -3