06-1828-020PANEL A TYPE SQD -NQOD MAINS 400A M.L.O. W/ FEED THRU LUGS SECTION I MNT FLUSH BUS 400A LOC TENANT SPACE VOLTS 120/208, 3PHS, 4W FEEDER 2 SETS OF 4 - #3/0, 2.0" A.I.C. 10,000 ELECTRICAL SYMBOL TABLE SYMBOL DESCRIPTION WIRE, C DUPLEX RECEPTACLE -MOUNT 18" A.F.F. UNLESS OTHERWISE NOTED KVA 20 AMP /125 VOLT WIRE, C 1 DUPLEX RECEPTACLE - SWITCHED RECEPTACLE REFRIGERATOR 20 AMP /125 VOLT AS PER PLANS 1/15 DUPLEX RECEPTACLE - VERIFY MOUNTING HEIGHT 3 - #12, 1/2" 20 AMP /125 VOLT 1/20 M G.F.I. RECEPTACLE - VERIFY MOUNTING HEIGHT W 20 AMP /125 VOLT 30.00 X -RAY MACHINE DUPLEX RECEPTACLE - DEDICATED CIRCUIT, SEPARATE NEUTRAL D 20 AMP /125 VOLT RUN #12 GROUND WIRE BACK TO PANEL }{-�� DUPLEX RECEPTACLE - ISOLATED CIRCUIT, LEVITON ##5362 -10 0I.G. 20 AMP /125 VOLT RUN #12 GROUND WIRE BACK TO PANEL 7 QUAD RECEPTACLE -MOUNT 18" A.F.F. UNLESS OTHERWISE NOTED RECEPTACLES 20 AMP /125 VOLT 8 SINGLE RECEPTACLE -MOUNT 18" A.F.F. UNLESS OTHERWISE NOTED 20 AMP /125 VOLT VOLTAGE AND AMPACITY AS PER PLANS 1.92 CLOCK HANGER RECEPTACLE - VERIFY MOUNTING HEIGHT 0C 15 AMP /125 VOLT 1.02 LIGHTING EQUIPMENT RECEPTACLE -MOUNT 18" A.F.F. UNLESS OTHERWISE NOTED 1/20 208/240 VOLT VOLTAGE AND AMPACITY AS PER PLANS 3 - #12, 1/2" 12 SWITCH, SINGLE POLE -MOUNT 44" A.F.F. UNLESS OTHERWISE NOTED LIGHTING 3 - #12, 1/2" 20 AMP /120 -277 VOLT 1/20 0.90 SWITCH, DOUBLE POLE -MOUNT 44" A.F.F. UNLESS OTHERWISE NOTED DP 20 AMP /120 -277 VOLT 0.93 LIGHTING SWITCH, THREE —WAY —MOUNT 44" A.F.F. UNLESS OTHERWISE NOTED 3 20 AMP /120 -277 VOLT RECEPTACLES 3 - #12, 1/2" 16 SWITCH, FOUR —WAY —MOUNT 44" A.F.F. UNLESS OTHERWISE NOTED LIGHTING 4 20 AMP /120 -277 VOLT 1/20 0.90 SWITCH, DIMMER —SIZE DIMMER WITH TOTAL LAMP WATTAGE $D 120 -277 VOLT 0.38 LIGHTING 3 - #12, 1/2" SWITCH, FAN DIMMER —SIZE DIMMER WITH TOTAL MOTOR LOAD 0.72 $R 120 VOLT RHEOSTAT 20 1/20 SWITCH, MOTOR RATED -RATED FOR USE WITH TOTAL MOTOR LOADS $M 20 AMP, 120 -277 VOLT 1/20 $K SWITCH, KEY -AS MANUFACTURED BY "LEVITON" 22 20 AMP, 120 -277 VOLT MODEL #1221 -2L / 55500 $0 SWITCH, OCCUPANCY SENSOR -AS MANUFACTURED BY "SENSOR SWITCH" 1/20 20 AMP /120 -277 VOLT MODEL #WSD -I 3 - #12, 1/2" $L LUTRON SMART SWITCH -AS MANUFACTURED BY " LUTRON" A.R.U. #1 3 - #10, 1/2" 20 AMP /120 VOLT MODEL # 0 TELEPHONE OUTLET -MOUNT 18" A.F.F. UNLESS OTHERWISE NOTED 26 -EMPTY 3/4" EMT STUBBED ABOVE CEILING W/ BUSHING (HEAT) DATA /PHONE OUTLET -MOUNT 18" A.F.F. UNLESS OTHERWISE NOTED 1/20 1.00 -EMPTY 3/4" EMT STUBBED ABOVE CEILING W/ BUSHING O TELEPHONE JUNCTION BOX -EMPTY 1.25" EMT STUBBED ABOVE CEILING W/ BUSHING WALL MOUNT O DATA JUNCTION BOX -EMPTY 1,25" EMT STUBBED ABOVE CEILING W/ BUSHING RECEPTACLES WALL MOUNT UNLESS OTHERWISE NOTED. © POWER JUNCTION BOX - CONNECT TO ELECTRICAL PANEL AS PER PLANS 3 - #10, 1/2" WALL MOUNT 1/20 O JUNCTION BOX - VERIFY MOUNTING HEIGHT 32 5.00 PP POWER POLE ANDLIDATAEQUIREMENTS 1/20 0.54 DUAL CHANNEL FOR POWER D DISCONNECT -SIZED AND FUSED AS PER EQUIPMENT NAMEPLATE RATING 35 H.O.A. STARTER - VERIFY HEATER STRIP SIZE WITH EQUIPMENT ® MOTOR STARTER - VERIFY HEATER STRIP SIZE WITH EQUIPMENT FD VARIABLE FREQUENCY - PROVIDED BY MECHANICAL CONTRACTOR 3 - #10, 1/2" DRIVE 1/20 /v EXHAUST FAN /MOTOR -SEE MECHANICAL DRAWINGS FOR DETAILS LC LIGHTING CONTACTOR - VERIFY NUMBER OF POLES a CARD READER / KEYPAD -EMPTY 3/4" EMT STUBBED ABOVE CEILING W/ BUSHING I ❑ INTERCOM -EMPTY 3/4" EMT STUBBED ABOVE CEILING W/ BUSHING O DOME CAMERA IN CEILING -EMPTY 3/4" EMT STUBBED ABOVE CEILING W/ BUSHING C� MONITOR CAMERA -EMPTY 3/4" EMT STUBBED ABOVE CEILING W/ BUSHING „ ALARM CONTACTS 0.50 I DOOR BUZZER 42 ® LOW VOLTAGE CEILING MOUNTED SPEAKERS r DENOTES FLOOR OR ROOF MOUNT L PANEL A TYPE SQD -NQOD MAINS M.L.O. SECTION II MNT FLUSH BUS 400A LOG TENANT SPACE VOLTS 120/208, 3PHS, 4W FEEDER 2 SETS OF 4 - #3/0, 2.0" A.I.C. 10,000 CKT (^ DENOTES CEILING MOUNT DESCRIPTION WIRE, C CKT POLE KVA DENOTES CORD DROP DEVICE - VERIFY MOUNTING HEIGHT PANEL A TYPE SQD -NQOD MAINS 400A M.L.O. W/ FEED THRU LUGS SECTION I MNT FLUSH BUS 400A LOC TENANT SPACE VOLTS 120/208, 3PHS, 4W FEEDER 2 SETS OF 4 - #3/0, 2.0" A.I.C. 10,000 CKT POLE KVA DESCRIPTION WIRE, C CKT POLE KVA DIESCRIPTION WIRE, C 1 1/20 1.20 REFRIGERATOR 2 - #12, 1/2" 2 1/15 1.80 TUBE STAND 3 - #12, 1/2" 3 1/20 1.50 UTILITY OUTLET 2 - #12, 1/2" 4 2/100 30.00 X -RAY MACHINE 3 - #3 1.25" 5 1 1/20 1.50 UTILITY OUTLET 2 - #12, 1/2" 6 1 W/ #6 GND. 7 1/20 0.72 RECEPTACLES 3 - #12, 1/2" 8 SHUNT TRIP 9 1/20 1.92 DEXA MACHINE 3 - #12, 1/2" 10 1/20 1.02 LIGHTING 3 - #12, 1/2" 11 1/20 0.72 RECEPTACLES 3 - #12, 1/2" 12 1/20 1.28 LIGHTING 3 - #12, 1/2" 13 1/20 0.90 RECEPTACLES 3 - #12, 1/2" 14 1/20 0.93 LIGHTING 3 - #12, 1/2" 15 1/20 0.72 RECEPTACLES 3 - #12, 1/2" 16 1/20 1.79 LIGHTING 3 - #12, 1/2"_ 17 1/20 0.90 RECEPTACLES 3 - #12, 1/2" 18 1/20 0.38 LIGHTING 3 - #12, 1/2" 19 1/20 0.72 RECEPTACLES 3 - #12, 1/2" 20 1/20 1.28 LIGHTING 3 - #12, 1/2° 21 1/20 0.72 RECEPTACLES 3 - #12, 1/2" 22 23 1/20 1.08 RECEPTACLES 3 - #12, 1/2" 24 3/25 1.55 A.R.U. #1 3 - #10, 1/2" 25 1 1/20 0.54 RECEPTACLES 2 - #12, 1/2" 26 5.00 (HEAT) 27 1/20 1.00 RECEPTACLES 2 - #12, 1/2" 28 29 1/20 0.50 RECEPTACLES 2 - #12, 1/2" 30 3/25 2.52 A.H.U. #2 3 - #10, 1/2" 31 1/20 0.90 RECEPTACLES 2 - #12, 1/2" 32 5.00 (HE -AT) 33 1/20 0.54 RECEPTACLES 2 - #12, 1/2" 34 35 1/20 1.00 COPIER 3 - #12, 1/2" 36 3/25 2.52 A.H.U. #3 3 - #10, 1/2" 37 1/20 0.50 RECEPTACLES 2 - #12, 1/2" 38 5.00 (HE -AT) 39 1/20 0.54 RECEPTACLES 2 - #12, 1/2" 40 41 1/20 0.50 RECEPTACLES 2 - #12, 1/2" 42 SUB -TOTAL 18.62 KVA SUB -TOTAL 58.45 KVIA PANEL A TYPE SQD -NQOD MAINS M.L.O. SECTION II MNT FLUSH BUS 400A LOG TENANT SPACE VOLTS 120/208, 3PHS, 4W FEEDER 2 SETS OF 4 - #3/0, 2.0" A.I.C. 10,000 CKT POLE KVA DESCRIPTION WIRE, C CKT POLE KVA DESCRIPTION WIRE, C 43 44 D 45 3/20 2.70 C.U. -1 3 — #10, 1/2" 46 3/25 1.55 A.HI.U. #4 3 — #10, 1/2" 47 1 1 48 5.00 1 (HEAT) 49 50 1/20 1.50 SERVER 3 — #12, 1/2" 51 3/25 4.18 C.U. -2 3 — #10, 1/2" 52 1/20 1.50 SERVER 3 — #12, 1/2" 53 54 1/20 1.50 SERVER 3 — #12, 1/2" 55 56 1/20 0.50 T. T.. B. 3 - #12, 1/2" 57 3/25 4.18 C.U. -3 3 — #10, 1/2" 58 1/20 1.08 RECEPTACLES 3 — #12, 1/2" 59 60 1/20 0.50 RECEPTACLE 3 — #12, 1/2"_ 61 62 2/80 14.04 PANEL 'Al' 3 — #4, 1.25" 63 3/20 2.70 C.U. -4 3 — #12, 1/2" 64 65 66 1/20 0.40 CONDENSATE PUMPS 2 — #12, 1/2" 67 68 69 70 71 72 73 74 75 - 76 77 ! `s 78 79 80 81 82 83 84 TOTAL 32.38 KVA 118.36 108.75 1.67 110.42 KVA / 208 X I = 3063 AMPS TOTAL 85.98 KWA KVA — TOTAL CONNECTED LOAD KVA — TOTAL DEMAND LOAD (HEATING AND COOLING LOADS ARE NON— CONCURRENT) KVA — 25% OF CONTINUOUS LOAD PANEL Al TYPE SQD -NQOD MAINS M.L.O. MNT FLUSH BUS 100A LOC TENANT SPACE VOLTS 120/208, 1PHS, 4W FEEDER 3 - #4, 1.25" A.I.C. 10,000 CKT POLE KVA DESCRIPTION WIRE, C CKT POLE KVA DESCRIPTION WIRE, C 1 1/20 2.40 TABLE 3 - #12, 1/2" 2 1/15 1.80 TUBE STAND 3 - #12, 1/2" 3 1/15 1.80 GENERATOR 3 - #12, 1/2" 4 1/15 1.80 WAILL STAND 3 - #12, 1/2" 5 2/30 6.24 SPARE 6 7 8 9 10 11 12 TOTAL 10.44 KVA 14.04 KVA / 208 = NUM8FREG ELECTRICAL NOTES U1 PRIOR TO BID, THE CONTRACTOR SHALL VISIT THE JOB SITE AND BECOME FAMILIAR WITH ALL EXISTING CONDITIONS. NOTIFY THE ARCHITECT OR ENCINEE4 Or ANY DISCREPANCIES. THE CONTRACTOR SHALL QUALIFY THE BID ACCORD-NGLY. O2 SUBMIT SHOP DRAVNNGS FOR ACCEPTANCE BY THE ARCHITECT AND /OR ENGINEER BEFORE PROCEEDING WITH THE PURCHASE OR INSTALLATION OF THE EQUIPMENT AND MATERIALS. O3 THE DESIGNATED NUMBERS ARE SHOWN ON THESE PLANS AS PER THE ORIGINAL DOCUMENTS FOR THE EXISTING PANEL AND ARE FOR IDENTIFICATION ONLY. CONTRACTOR SHALL SHOW THE CIRCUIT NUMBERS ACTUALLY USED IN THE INSTALLATION ON THE "AS- BUILT" DRAWINGS. ® MAINTAIN FIRE RATING IN ALL PENETRATIONS THRU DEMISING AND FIRE RATED WALLS. O5 REPORT ANY DISCREPANCIES TO THE ARCHITECT OR ENGINEER PRIOR TO BID. © CONNECT EXIT AND EMERGENCY LIGHTS AHEAD OF SWITCH LEG ON EACH LIGHTING CIRCUIT AS PER PLANS. O7 EXISTING FUTURE FLOOR SPACE. NO ELECTRICAL WORK TO BE PERFORMED IN THIS AREA UNDER THIS PERMIT AND /OR CONTRACT DOCUMENTS. ® NEW RECEPTACLES TO BE INSTALLED IN COUNTER SPACE. VERIFY EXACT LOCATION AND MOUNTING HEIGHT OF EACH DEVICE PRIOR TO ROUGH INSTALLATION. COORDINATE ALL WORK WITH MILLWORK DRAWINGS AND DETAILS PROVIDED BY THE ARCHITECT AND /OR MILLWORK CONTRACTOR. O9 HN.A.C. DUCT SMOKE DETECTORS SHALL BE INSTALLED AS PART OF THE EXISTING FIRE ALARM SYSTEM. DETECTORS SHALL BE INSTALLED BY MECHANICAL CONTRACTOR AND FURNISHED AND WIRED BY ELECTRICAL CONTRACTOR. COORDINATE ALL FIRE ALARM WORK WITH THE BUILDING FIRE ALARM MAINTENANCE CONTRACTOR. 10 NEW FIRE ALARM DEVICES SHALL BE INSTALLED TO MATCH EXISTING, CONNECT INITIATING AND SIGNALING DEVICES TO EXISTING ZONE(S). COORDINATE ALL WORK WITH THE BUILDING FIRE ALARM MAINTENANCE CONTRACTOR. 11 FIRE ALARM SHOP DRAWINGS, SIGNED AND SEALED, AS REQUIRED BY THE JURISDICTION HAVING AUTHORITY SHALL BE PROVIDED BY THE FIRE ALARM CONTRACTOR AND THEIR OWN RESPECTIVE ENGINEER. 12 ALL ELECTRICAL WRING IN TREATMENT ROOMS SHALL CONFORM WITH N.E.C., ARTICLE 517, SECTION II. 13 ALL ELECTRICAL WIRING IN X -RAY ROOMS SHALL CONFORM WITH N.E.C., ARTICLE 517, SECTION V. 14 FIELD VERIFY EXISTING CHASE OR CONDUITS TO PROVIDE ELECTRICAL SERVICE TO THIS TENANT. 15 INSTALL NEW 2.0" CONDUIT FOR TELEPHONE. EXTEND CONDUIT OVERHEAD TO NEW T.T.B. FROM EXISTING TELEPHONE ROOM ON THIRD FLOOR LOCATION 16 ALL WORK SHALL CONFORM TO THE FLORIDA BUILDING CODE AND ALL OTHER APPLICABLE STATE AND LOCAL REGULATIONS AND ORDINANCES. 17 CONTRACTOR SHALL WARRANT ALL WORK TO BE FREE OF DEFECT IN WORKMANSHIP AND MATERIALS FOR A PERIOD OF ONE YEAR AFTER ACCEPTANCE OF THE PROJECT. 18 VERIFY EXACT LOCATION OF ALL EQUIPMENT WITH TENANT PRIOR TO ROUGH INSTALLATION. FOURTH FLOOR ALL SWITCHGEAR, BOXES, DEVICES, CONDUIT AND WIRE INDICATED ON THIS PLAN BY A DASHED LINE ARE EXISTING TO REMAIN. ALL DOTTED LINES INDICATE EXISTING EQUIPMENT TO BE REMOVED OR REPLACED. ALL SWITCHGEAR, BOXES, DEVICES, CONDUIT AND WIRE INDICATED ON THIS PLAN BY A SOLID LINE ARE NEW. SECOND FLOOR PANEL PANEL PANEL DISC. 'A' 'A' 'A1' _ 1oa 400A 100A 3 �� MLO MLO SEC. I SEC. II 1 PHASE FIELD VERIFY EXISTING CHASE AND OR CONDUITS FROM SECOND FLOOR ELECTRIC ROOM TO THIS TENANT. rlsj.-] J roISC� j E<­a400A 10 I 101 6 K -7 CAN E - -� T 0 I 11 TOTAL 3.60 KVA p FIRST FLOOR 14.04 KVA —TOTAL CONNECTED LOAD I 67.5 AMPS ( ELECTRICAL FEEDER SCHEDULE NEW 2 SETS OF 4 - #3/0 THWN CU WIRE IN 2.0 C W / #3 CU GND EACH 1 H 2 NEW 3 - #4 THWN CU WIRE IN 1.25" C W / #6 CU GND 1sT. 3 NEW 3 - #3 THWN CU WIRE IN 1.25" C W / #6 CU GND 4 EXISTING 2 SETS OF 4 - #600 MCM THWN CU WIRE IN 4.0" C W1#110 CU GND EACH [_ [)• I 5 EXISTING 4 - #1 MCM THWN CU WIRE IN 2.0" C W /#6 CU GND 6 EXISTING 2 SETS 4 - #1 MCM THWN CU WIRE IN 2.0" C W / #4 CU GND FL I F---TM � I � I PARTIAL RISER N.T.S. 9 d i e I ,Irz ar �tcture, inc, 7430 sw 48th street' miami, florido 33155 phone: (305) 6619 0 fax: (305) 66x- 12 e -mail: peter0die chitecture.com pedro diez, ro president or 0008996 ENGINEERING CONSULTANT Puga and Associates, Inc. Engineers /Consultants # EB 0 05613 7326 S. W. 48th treet Miami, orida 93155 (305 dbl'- h0 v • -OU ., ��* • • t� 4th FLOOR 6141 SUNSET EWIVE SOUTH MIAMI, „RIDA �F4 PROJECT No. 04.158.041 REVISIONS A SCALE: AS SHOWN r {J * "y ,va ): DNViO PUI RIL No. 4111 SCALE: AS SHOWN