06-1828-015BRANCH TAKEOFF WITH 450 SHOE FITTING
WITH MANUAL VOLUME DAMPER.
Lk
t�
DUCT ELBOW WITH DOUBLE
THICKNESS TURNING VANES
(�C�OC{XXX)'
FLEXIBLE ROUND DUCT. INSIDE DIMENSIONS.
i
-- ®-- SUPPLY AIR, CEILING MOUNTED REGISTER
RETURN AIR, CEILING MOUNTED REGISTER
DIFFUSER GRILLE TAG WITH REQUIRED
O560 AIR VOLUME. SEE SCHEDULE FOR SIZES
CFM AND THROW PATTERN.
0 DIAMETER
O ROOM THERMOSTAT OR THERMIDISTAT.
1 NUMBER NEXT TO SYMBOL DENOTES
A/C UNIT MARK.
FD FIRE DAMPER, EQUAL TO AIR BALANCE INC.,
MODEL 119C, LEAKAGE CLASS II. SIZE
DAMPER AS REQUIRED TO MAINTAIN SAME
FREE AREA AS DUCT.
VD MANUAL VOLUME DAMPER
SD DUCT MOUNTED SMOKE SENSOR
HVAC DESIGN REQUIRES:
LEGEND
ABV
ABOVE
CD
CEILING DIFFUSER
CFM
CUBIC FEET PER MINUTE
CLG.
CEILING
CONN
CONNECT, CONNECTION
DB
DRY BULB
DDC
DIRECT DIGITAL CONTROL
DI
DIGITAL INPUT
ON
DOWN
DP
DIFFERENTIAL PRESSURE
DR
DRAIN
DWG
DRAWING
EA.
EACH
ENT
ENTERING
EQUIP
EQUIPMENT
GA.
GAUGE
GALV.
GALVANIZED
HTR.
ELECTRICAL HEATER
HP
HORSEPOWER
KW
KILOWATTS
IN
INCHES
MAX.
MAXIMUN
MIN
MINIMUN
No.
NUMBER
NTS
NOT TO SCALE
0/A
OUTSIDE AIR
P.D.
PRESSURE DROP
PSF
POUND PER SQUARE FOOT
QTY
QUANTITY
R/A
RETURN AIR
RPM
REVOLUTIONS PER MINUTE
RTU
ROOFTOP UNIT
S/A
SUPPLY AIR
S.P.
STATIC PRESSURE
SPS
STATIC PRESSURE SENSOR
TEMP.
TEMPERATURE
TRF
TRANFER
TS
TEMPERATURE SENSOR
TYP.
TYPICAL
UC
UNDERCUT
UP
UP
VAV
VARIABLE AIR VOLUME
VD
MANUAL VOLUME DAMPER
VEL
VELOCITY
VVT
VARIABLE VOLUME AND TEMPERATURE
V /PH
VOLTAGE /PHASE
WB
WET BULB
OPERATION UNDER ALL LOAD CONDITIONS AS PER ASHIRAE -62 VENTILATION RATE PROCEDURE.
DASHED LINES DEPICT EXISTING
DETERMINED ON THE BASIS OF AVERAGE OCCUPANCY FOR BUILDINGS, FOR THE DURATION OF OPERATION OF THE
DUCTWORK / DEVICES TO REMAIN.
BRANCH TAKEOFF WITH 450 SHOE FITTING
WITH MANUAL VOLUME DAMPER.
Lk
t�
DUCT ELBOW WITH DOUBLE
THICKNESS TURNING VANES
(�C�OC{XXX)'
FLEXIBLE ROUND DUCT. INSIDE DIMENSIONS.
i
-- ®-- SUPPLY AIR, CEILING MOUNTED REGISTER
RETURN AIR, CEILING MOUNTED REGISTER
DIFFUSER GRILLE TAG WITH REQUIRED
O560 AIR VOLUME. SEE SCHEDULE FOR SIZES
CFM AND THROW PATTERN.
0 DIAMETER
O ROOM THERMOSTAT OR THERMIDISTAT.
1 NUMBER NEXT TO SYMBOL DENOTES
A/C UNIT MARK.
FD FIRE DAMPER, EQUAL TO AIR BALANCE INC.,
MODEL 119C, LEAKAGE CLASS II. SIZE
DAMPER AS REQUIRED TO MAINTAIN SAME
FREE AREA AS DUCT.
VD MANUAL VOLUME DAMPER
SD DUCT MOUNTED SMOKE SENSOR
HVAC DESIGN REQUIRES:
YES
NO
DUCT SMOKE DETECTOR
•
OUTSIDE AIR
FIRE DAMPER(S)
AIR EXHAUSTED
EXH. EQUIP.
SMOKE DAMPER(S)
AREA SERVE
NET. SQ. FT.
FIRE RATED ENCLOSURE
CFM /PERSON
OR TRANSFER
FIRE RATED ROOF FLOOR
CEILING ASSEMBLY
REQUIRED
USED_.!
FIRE STOPPING
WAITING ROOM
275
SMOKE CONTROL
10 ( +)
100
BUILDING AIR PLOW RECAPITULATION SCHgDULE
A/C EQUIP.
INxINECK
AREA SERVED
UNIT DESIGNATION AHU -1 AHU -2 AHU -3
OUTSIDE AIR
TOTAL OUTSIDE AIR
AIR EXHAUSTED
EXH. EQUIP.
TAG No.
AREA SERVE
NET. SQ. FT.
PEOPLE
CFM /PERSON
OR TRANSFER
TAG No.
REQUIRED
USED_.!
AHU -1
WAITING ROOM
275
10
10 ( +)
100
100
-
-
OFFICES
781
4
20
80
100
-75
EF -2
24x24
AHU -2
OFFICES
581
10
20
200
200
-75
EF -1
AHU -3
OFFICES
649
12
20
240
240
-
-
MOTOR SIZE HP
LOUVERED FACE DIRECTIONAL
O
24x24
0
PRICE
AMD- 3P -B12
AHU -4
OFFICES
596
4
20
80
80
-
-
- --
LOUNGE
176
6
10 ( *)
60
80
-
-
TOTALS
O
1 +800
-150
PRICE
BUILDING PRESSURIZATION
+ 650 CFM
NOTES: l�
1 OUTDOOR AIR PROVISIONS FOR VENTILATION SHALL SATISFY THE MINIMUM REQUIREMENTS FOR ACCEPTABLE INDOOR
AIR QUALITY AS PER ASHARE;62 -19p', VENTILATION RATE PROCEDURE.
2 THE FULL VOLUME OF OUTSID�• AIA "ESTABLISHED IN THIS SCHEDULE SHALL BE DELIVER TO THE SPACE AT ALL
TIMES THAT THE BUILDING IS OCCUPIED 3 FOR ALL VARIABLE AIR VOLUME MACHINES, CONTROL SYSTEM SHALL
GUARANTEE THAT THE REQUIRED AMOUNT OF OUTSIDE AIR IS DELIVERED TO EVERY SPACE DURING BUILDING
OPERATION UNDER ALL LOAD CONDITIONS AS PER ASHIRAE -62 VENTILATION RATE PROCEDURE.
( +) 6.1.3.4 ... "WHERE PEAK OCCUPANCIES OF LESS THAN TFHREE HOURS OCCUR, THE OUTDOOR AIR FLOW RATE MAY BE
DETERMINED ON THE BASIS OF AVERAGE OCCUPANCY FOR BUILDINGS, FOR THE DURATION OF OPERATION OF THE
SYSTEM, PROVIDED THE AVERAGE OCCUPANCY USED I& NOT LESS THAN ONE -HALF THE MAXIMUM."
AIR DISTRIBUTIION SCHEDULE
MARK
INxINECK
33155
UNIT DESIGNATION AHU -1 AHU -2 AHU -3
AHU -4
SYMBOLS
MFGR
MODEL SERIES
REMARKS
FACE
NECK
RESTROOMS
0008996
UNIT MANUFACTURER
TRANE
MANUFACTURER
COOK
TRANE
LOUVERED FACE DIRECTIONAL
O
24x24
5 "0
PRICE
AMD- 3P -B12
SUPPLY DIFFUSER
NOMINAL TONS
2.5
4.0
SYSTEM TYPE
EXHAUST
LOUVERED FACE DIRECTIONAL
O
24x24
6"0
PRICE
AMD -3P -812
SUPPLY DIFFUSER
E.S.P. (IN WATER)
0.25
930
1,510
LOUVERED FACE DIRECTIONAL
C
24x24
8 "0
PRICE
AMD- 3P -B12
SUPPLY DIFFUSER
1,058
160
MOTOR SIZE HP
LOUVERED FACE DIRECTIONAL
O
24x24
10 "o
PRICE
AMD- 3P -B12
SUPPLY DIFFUSER
DRIVE TYPE
DIRECT
LOUVERED FACE DIRECTIONAL
O
12x12
- --
PRICE
AMD -1 -1312
SUPPLY DIFFUSER
SONE RATING (MAX.)
1.9
LOUVERED FACE DIRECTIONAL
O
12x8
- --
PRICE
620DAL- F -L -B12
SUPPLY REGISTER
Q
EXTERNAL STATIC PRESSURE I.W.G.
0.6
LOUVERED FACE DIRECTIONAL
O
26x10
- --
PRICE
620DAL- F -L -B12
SUPPLY REGISTER
NOTES:
1 FANS LOCATED ON THE EXTERIOR OF THE BUILDING SHALL BE CONSTRUCTED AND INSTALLED TO WITHSTAND A
WIND PRESSURE OF FROM ANY DIRECTION AS PER F.B.C.
2 ALL FANS SHALL HAVE UL APPROVED LOCAL DISCONNECT MEANS, SUPPLIED BY ELECTRICAL CONTRACTOR.
3 ROOF FANS AND VENTS SHALL HAVE BACK -DRAFT DAMPERS AND BIRD SCREENS.
4 FANS SHALL BE OF WELDED CONSTRUCTION UTILIZING CORROSION RESISTANT FASTENERS. ALL STEEL FAN
COMPONENTS SHALL HAVE A SUPERFICIAL ELECTROSTATIC COATING TREATMENT TO PREVENT CORROSION.
5 MOTORS SHALL BE HEAVY DUTY TYPE WITH PERMANENTLY LUBRICATED SEALED BALL BEARINGS AND FURNISHED
TO THE SPECIFIED VOLTAGE, PHASE AND ENCLOSURE.
6 FAN SHALL BE OF AN AMERICAN MANUFACTURER AND MANUFACTURED AT AN ISO 9001 CERTIFIED FACILITY.
7 ALL FAN SHALL BEAR AMCA CERTIFIED RATING AND UL LISTING.
8 FANS EF -1 AND 2 SHALL BE SWITCHED BY LIGHTS.
=
FAN SIZE HP
1/2
3/4
3/4
1/2
LOUVERED EXHAUST
O2
12x12
- --
PRICE
635- F -L -B12
SURFACE MOUNTED
Ly
LOUVERED RETURN
O
24x24
22x22
PRICE
635 -TB -L -812
24x24 PANEL
NOTES:
1- REFER TO PLAN FOR QUANTITY, LOCATION AND FAIR THROW PATTERN.
EXHAUST FAN SCHEDULE
MARK
EF -1,2
33155
UNIT DESIGNATION AHU -1 AHU -2 AHU -3
AHU -4
LOCATION
CEILING
WAITING ROOM
OFFICES
OFFICES
SYSTEM /AREA SERVED
RESTROOMS
0008996
UNIT MANUFACTURER
TRANE
MANUFACTURER
COOK
TRANE
MODEL NUMBER
GC -140
TWE049E13FB
TWE049E13FB
TWEO31E13F8
WEIGHT (LBS) APPROX.
18
NOMINAL TONS
2.5
4.0
SYSTEM TYPE
EXHAUST
SYSTEM (S)EER
DESIGN CFM SETTING
75
14.00
14.00
E.S.P. (IN WATER)
0.25
930
1,510
1,390
FAN TYPE
CENTRIFUGAL
OUTSIDE AIR CFM
200
FAN RPM
1,058
160
MOTOR SIZE HP
43 WATTS
ELECTRICAL SERVICE
115/1/60
DRIVE TYPE
DIRECT
RETURN AIR CFM
CONTROL
FSC 5
1,150
730
SONE RATING (MAX.)
1.9
BACKDRAFT DAMPER MODEL No.
100 SERIES
z
ACCESSORIES /REMARKS
GEMINI ISO KIT
Q
EXTERNAL STATIC PRESSURE I.W.G.
0.6
0.6
0.6
0.6
NOTES:
1 FANS LOCATED ON THE EXTERIOR OF THE BUILDING SHALL BE CONSTRUCTED AND INSTALLED TO WITHSTAND A
WIND PRESSURE OF FROM ANY DIRECTION AS PER F.B.C.
2 ALL FANS SHALL HAVE UL APPROVED LOCAL DISCONNECT MEANS, SUPPLIED BY ELECTRICAL CONTRACTOR.
3 ROOF FANS AND VENTS SHALL HAVE BACK -DRAFT DAMPERS AND BIRD SCREENS.
4 FANS SHALL BE OF WELDED CONSTRUCTION UTILIZING CORROSION RESISTANT FASTENERS. ALL STEEL FAN
COMPONENTS SHALL HAVE A SUPERFICIAL ELECTROSTATIC COATING TREATMENT TO PREVENT CORROSION.
5 MOTORS SHALL BE HEAVY DUTY TYPE WITH PERMANENTLY LUBRICATED SEALED BALL BEARINGS AND FURNISHED
TO THE SPECIFIED VOLTAGE, PHASE AND ENCLOSURE.
6 FAN SHALL BE OF AN AMERICAN MANUFACTURER AND MANUFACTURED AT AN ISO 9001 CERTIFIED FACILITY.
7 ALL FAN SHALL BEAR AMCA CERTIFIED RATING AND UL LISTING.
8 FANS EF -1 AND 2 SHALL BE SWITCHED BY LIGHTS.
0
diez
architecture,
inc.
7430 sw 48th
A/C EQUIPMENT SCHEDULE
miami, florido
33155
UNIT DESIGNATION AHU -1 AHU -2 AHU -3
AHU -4
fax: (305)
AREA SERVED
WAITING ROOM
OFFICES
OFFICES
OFFICES
president ar
0008996
UNIT MANUFACTURER
TRANE
TRANE
TRME
TRANE
MODEL NUMBER
TK031El3F9
TWE049E13FB
TWE049E13FB
TWEO31E13F8
NOMINAL TONS
2.5
4.0
4.0
2.5
SYSTEM (S)EER
14.00
14.00
14.00
14.00
TOTAL AIR SUPPLY CFM
930
1,510
1,390
890
OUTSIDE AIR CFM
200
200
240
160
z
RETURN AIR CFM
730
1,310
1,150
730
0
z
Q
EXTERNAL STATIC PRESSURE I.W.G.
0.6
0.6
0.6
0.6
=
FAN SIZE HP
1/2
3/4
3/4
1/2
Ly
a
FAN MOTOR FLA AMP
4.3
7.0
7.0
4.3
ENTERING AIR TEMPERATURE (DB /WB)° F
80.0 67.9
77.9 64.0
79'0 65.4
80'1 66.4
LEAVING AIR TEMPERATURE (DB /W8)° F
58.5 6
54.8 531
55.5 54.0
55.2 54.0
TOTAL COOLING COIL CAPACITY MBH
29.1
49.0
48.4
29.5
TOTAL SENSIBLE CAPACITY MBH
19.1
38.9
35.7
21.0
TOTAL HEATING CAPACITY MBH
12.3
12.3
12.3
12.3
ELECTRIC HEATER SIZE (230 V) Kw
5
5
5
5
HEATER MCA / MOCP AMP
24 25
24
25
24
25
24
25
ELECTRICAL CHARACTERISTICS V /O /Hz
208/1/60
208/1/60
208/1/60
208/1/60
WEIGHT I b s.
118
196
196
118
DIMENSIONS (HxWxD) INCH
43x22x21
63x26x21
63x26x21
43x22x21
UNIT DESIGNATION
CU -1
CU -2
CU -3
CU -4
UNIT MANUFACTURER
TRANE
TRANE
TRANE
TRANE
MODEL NUMBER
2TTA303OA3000A
2TTA3048A3000A
2TTA306OA3000A
2TTA303OA30WA
LOCATION
ROOF
ROOF
ROOF
ROOF
N
AMBIENT TEMPERATURE ° F
95
95
95
95
z
Z
REFRIGERANT R
22
22
22
22
0
0
COMPRESSOR MOTOR RLA AMP
6.8
11.6
11.6
6.8
0
0
FAN MOTOR SIZE HP
1/8
1/6
1/6
1/8
0
Of
FAN MOTOR FLA AMP
03
1.4
1.4
0.7
MCA / MOCP AMP
13
20
16
25
16
25
13
20
ELECTRICAL CHARACTERISTICS V /O /Hz
208/3/60
208/3/60
208/3/60
208/3/60
WEIGHT Ibs.
197
267
267
197
DIMENSIONS (HxWxD) INCH
330300
410704
41x37x34
33x33x30
NOTES:
1 ALL UNITS SHALL BE HORIZONTALLY MOUNTED WITH TOP SUPPLY AND BOTTOM RETURN
AS INDICATED ON
DRAWINGS.
2 SIZE REFRIGERATION PIPING AS PER MANUFACTURER RECOMMENDATIONS. OVERSIZE LINES AS REQUIRED TO
COMPENSATE FOR LINE LOSS WITH MINIMUM CAPACITY REDUCTION. SUBMIT SHOP DRAWINGS.
3 AIR HANDLING UNIT SHALL CONTAIN SOLID STATE INTERLOCK BOARD WITH BUILT IN FUSE AND TIME DELAY RELAY.
4 PROVIDE 5 YEAR WARRANTY ON ALL REFRIGERATION COMPONENTS.
5 PROVIDE ALL RELAYS, TRANSFORMERS, ETC. AS REQUIRED FOR COMPLETE OPERATING SYSTEM.
6 UNITS SHALL BE PROVIDED WITH A 4 INCH THICK PLEATED FILTER WITH A 30% MINIMUM EFFICIENCY. UNIT
CONSTRUCTION AND INSTALLATION SHALL GUARANTEE AN EASY ACCESS TO FILTER SECTION FOR PROPER FILTER
INSPECTION AND REPLACEMENT.
7 UNIT INSULATION AND ADHESIVE SHALL COMPLY WITH NFPA 90A REQUIREMENTS FOR FLAME SPREAD AND SMOKE
GENERATION. INSULATION SHALL CONTAIN AN EPA REGISTERED IMMOBILIZED ANTI - MICROBIAL AGENT TO EFFECTIVELY
RESIST THE GROWTH OF BACTERIA AND FUNGI IN ACCORDANCE WITH ASTM STANDARDS
G21 AND G22.
8 FAN MOTOR SHALL BE HIGH EFFICIENCY TYPE.
9 FAN AND MOTORS SHALL BE PROVIDED WITH CIRCUIT PROTECTION.
10 CONDENSATE DRAIN PANS SHALL BE INSULATED AND SLOPED TO OUTLET. PANS SHALL
HAVE STAINLESS STEEL
LINERS. PROVIDE A OVERFLOW DETECTION SYSTEM CAPABLE OF SHUTDOWN THE UNIT
UPON DECTION OF HIGH
LEVELS CONDENSATE DRAIN.
11 SUPPORT UNIT HIGH ENOUGH ABOVE CEILING TO ACCOMMODATE CONDENSATE DRAIN TRAPS IN ACCORDANCE WITH
MANUFACTURER'S RECOMMENDATIONS.
12 THE FAN DRIVE SHALL BE SELECTED FOR 125% OF THE MOTOR RATED HORSEPOWER.
13 CONTRACTOR SHALL GUARANTEE ADECUATE CLEARANCE ALL AROUND THE UNIT FOR MAINTENANCE ACCESS.
14 CONDENSING UNIT SHALL BE INSTALLED TO WITHSTAND WIND PRESSURE FROM ANY DIRECTION AS PER THE
"HVHZ" REQUIREMENTS OF THE F.B.C.
15 ALL UNITS SHALL BE OF DOUBLE WALL CONSTRUCTION. ALL UNITS SHALL BE PROVIDED
WITH ADEQUATE
INSULATION. PROVIDE INSULATION LINERS TO PREVENT SURFACE CONDENSATION UNDER ALL CONDITIONS.
16 ALL UNITS SHALL HAVE A STAINLESS STEEL, DOUBLE SLOPED DRAIN PAN WITH INSULATION
LINERS IN
ACCORDANCE WITH ASHORE 62.
17 UNITS SHALL BE OF AMERICAN MANUFACTURER, DESIGNED AND RATED IN ACCORDANCE
WITH ALL APPLICABLE
ASHRAE, AIR AND NFPA CODES AND STANDARDS AND SHALL BE UL LISTED.
18 CONDENSER COILS SHALL BE PROVIDED WITH A PROTECTIVE GUARD.
19 ALL UNITS SHALL BE PROVIDED WITH A 2 -STAGE PROGRAMMABLE, DIGITAL THERMOSTAT
WITH DEHUMIDIFICATION
CONTROL EQUAL TO HONEYWELL MODEL No. TH8321U1006 AND SHALL BE CAPABLE OF
PROVIDING AFTER HOURS
SET BACK FOR ENERGY CONSERVATION PURPOSES.
20 DUCT MOUNTED SMOKE DETECTOR FOR ALL UNITS SHALL BE PROVIDED AND INSTALLED
BY MECHANICAL
CONTRACTOR AND WIRED BY FIRE ALARM CONTRACTOR.
diez
architecture,
inc.
7430 sw 48th
street
miami, florido
33155
phone: (305)
663 -1970
fax: (305)
663 -2312
e -mail: peter @diezorchitecture.com
pedro diez, ra
president ar
0008996
ENGINEERING CONSULTANT
Puga and Associates, Inc.
Engineers /Consultants
# EB 0005813
7326 S.W. 48th Street
Miami, Florida 33155
(305) 661 -7700
17a. jq"
(99k"
4th FLOOR
6141 SUNSET DRIVE
SOUTH MIAMI, FLORIDA
PROJECT No. 04.158.041
REVISIONS
c ; bc 2006
.4 1 15AVID PUOA
v D.� M- w.44 �
Ivi