06-1828-00711 FIRE RATED
LL ASSEMBLY
FER TO WALL TYPE
D A
A
MAX ANULAR SPACE 3/4'
MIN ANULAR SPACE 1/4'
SECTION A -A
PENETRANT TYPE
A. MAX 24' X 12' RECTANGULAR STEEL DUCT. W/ MIN 24 GAGE
MAX AREA OF OPENING 325 SQ /IN W/ A MAX DIMENSION OF 25'
1. MIN, 5/5' DEPTH HILTI CP 601 5 ELA5TOMERIC FIRE STOP SEAL
2. FASTEN STEEL ANGLE L2'X2'XI /8' TO DUCT W/NO 8 OR LARGER
STEEL SHEET METAL 5CREW5.
SMOKE BARRIER 1HR FR
UL DESIGN NO: W —L -2003
PENETRATION AS LISTED
BELOW
I HOUR FIRE RATED
WALL ASSEMBLY REFER
TO WALL TYPE FOR ADDITIONAL
INFORMATION
FILL MATERIAL TO a
FORCED INTO ANNUL
TO MAXIMUM EXTENC
P0561BLE
1/4' TO 1/2' LARGER
THAN OUTSIDE DIAL'
OF PENETRANT
FILL MATERIAL A MINIMUM 1/2'
CROWN TO FORM AROUND
PENETRATING ITEM AND LAPPING 1/4'
BEYOND PERIPHERY
SECTION A -A
I- PENETRANT TYPE ( ONE OF THE FOLLOWING)
A. STEEL PIPE NOMINAL 12' DIA OF SMALLER, SCHEDULED OR HEAVIER
B. CONDUIT NOMINAL 6' DIA OR SMALLER, EMT OR STEEL CONDUIT
C. COPPER TUBING NOMINAL 6' DIA OR SMALLER TYPE L OR HEAVIER
D . CO PPER TU ING NOMINAL 6 D IA OR SMALLER, RE GU L A R R H
HEAVIER
2- FIRE6TOP SYSTEM HILTI CONSTRUCTION CHEMICALS INC. TYPE F5 6m5
OR FS ONE SEALANT
11/2 77
/ a
TED
'( REFER
=0R ADDITIONAL
SLANT TO COMPL
,IULAR SPACE BE
'E AND GYPSUM E
iEMBLY
q 3/4', MAX 11/4'
APE AS LISTED
SECTION A -A
1- PENETRANT TYPE ( ONE OF THE FOLLOWING)
A. NON METALLIC PIPE, POLY VINYL. CLORIDE (PVC)
NOM 2' DIA OR SMALLER
2- FIRE5TOP 6Y5TEM HILTI CONSTRUCTION CHEMICALS INC. TYPE FS 611A
OR F5 ONE SEALANT
SMOKE BARRIER 1HR FR
UL DESIGN NO W —L— 2098
FAI .A __ U11
UL DESIGN NO: W —L— 1085
1/2' MIN THICKNESS APPLIED WITHIN ANNULUS
FLUSH WITH BOTH SIDES OF WALL
SEALANT AND PACKING MATERIAL
MIN 3' THK OF 5 PCF MINERAL
WOOD GATT FOR PIPES 4' SMALLER
12' MAX DIA OF OPENING
ANNULAR SPACE SHALL BE
0 AT THE POINT OF CONTACT
TO A MAX OF 11/4' OF
OUTSIDE DIAMETER OF PENETRANT
6' CMU ASSEMBLY 1 HOUR RATED
REFER TO WALL TYPES AND LIFE SAFETY
PLANS FOR ADDITIONAL INFORMATION
SECTION A -A
1- PENETRANT TYPE ( ONE OF THE FOLLOWING)
Q STEEL PIPE NOMINAL 10' DIA OF SMALLER, SCHEDULED OR HEAVIER
B. CONDUIT NOMINAL 4' DIA OR SMALLER, EMT OR STEEL CONDUIT
C. COPPER TUBING NOMINAL 4' DIA OR SMALLER TYPE L OR HEAVIER
D. COPPER TUBING NOMINAL 4' DIA OR SMALLER, REGULAR OR HEAVIER
2- FIRESTOP 5Y5TEM HILTI CONSTRUCTION CHEMICALS INC. TYPE F5 601 /
OR FS 604 / FS ONE SEALANT
NA 0 a iiiii 11
UM1 1141111
UL DESIGN NO C —AJ -1149
V~:loyi1•1,121
IX t-1FZE XArI =V WALL A55EN3LY
:FER TO WALL TYPE FOR ADDITIONAL
=ORMATION
--NETRANT TYPE A LISTED BELOW
A �(
'n QQE
i
SEALANT TYPICAL
30TH ENDS
MIN /;:S' I HIC:KNk55 C,'- i=.__ .. .. _. _..
APPLIED WITH THE ANNULUS, FLUSH
WITH BOTH SURFACES OF WALL
A
I' -6'
1. PENETRANT TYPE (ONE OR MORE NOMINAL I' DIA)
A STEEL ELECTRIC TUBING MINIMUM 1/2' MAX 1' CONDUIT RIGIDLY
SUPPORTED ON BOTH 51DE5 OF WALL
2. FIRESTOP SYSTEM HILTI CONSTRUCTION CHEMICALS INC.
TYPE F5 ONE SEALANT
SMOKE BARRIER 1HR FR 3"
UL DESIGN NO W -L -1095
1HR FIRE RATED
WALL ASSEMBLY
REFER TO WALL TYPE
NON -RATED
WALL ASSEMBLY
REFER TO WALL TYPE
GENERAL NOTES
I. ALL THROUGH PENETRATIONS SHOWN ABOVE ARE BASED UPON
SPECIFIC PRODUCTS AND MANUFACTURERS FOR OTHER ACCEPTABLE
MANUFACTURER'S REFER TO PROJECT SPECIFICATIONS,
2. ALL ASSEMBLIES SHOWN ABOVE ARE REPRESENTATIVE ONLY FOR
COMPLETE CONSTRUCTION REQUIREMENT.
REFER TO EACH A66EMBLY NUMBER IN THE 'UL' MANUAL, VOLUME 2, 1399
EDITION.
3. FOR OTHER APPLICABLE REQUIREMENTS REFER TO PROJECT
SPECIFICATIONS,
4. FOR FIRE RATED WALL A56EM13LY TYPES BEARING UL LABLE REFER
TO PARTITION TYPES.
SMOKE BARRIER PARTITION
JOINT DETAIL
It
7430 sw 48th
street
miami, florida
33155
phone: (305)
663 -1970
fax: (305)
663 -2312
e —mail: peter®diezarchitecture.corn
pedro diez, ro
A
president or
0008996
...
U-1 ,
»,
V
n
7430 sw 48th
street
miami, florida
33155
phone: (305)
663 -1970
fax: (305)
663 -2312
e —mail: peter®diezarchitecture.corn
pedro diez, ro
president or
0008996
...
ENGINEERING CONSULTANT
\
R
.
V
n
r
.
4th FLOOR
6141 SUNSET DRIVE
SOUTH MIAMI, FLORIDA
PROJECT No. 04.158.041
REVISIONS
PENETRATION
DETAILS
wwol