06-1828-00711 FIRE RATED LL ASSEMBLY FER TO WALL TYPE D A A MAX ANULAR SPACE 3/4' MIN ANULAR SPACE 1/4' SECTION A -A PENETRANT TYPE A. MAX 24' X 12' RECTANGULAR STEEL DUCT. W/ MIN 24 GAGE MAX AREA OF OPENING 325 SQ /IN W/ A MAX DIMENSION OF 25' 1. MIN, 5/5' DEPTH HILTI CP 601 5 ELA5TOMERIC FIRE STOP SEAL 2. FASTEN STEEL ANGLE L2'X2'XI /8' TO DUCT W/NO 8 OR LARGER STEEL SHEET METAL 5CREW5. SMOKE BARRIER 1HR FR UL DESIGN NO: W —L -2003 PENETRATION AS LISTED BELOW I HOUR FIRE RATED WALL ASSEMBLY REFER TO WALL TYPE FOR ADDITIONAL INFORMATION FILL MATERIAL TO a FORCED INTO ANNUL TO MAXIMUM EXTENC P0561BLE 1/4' TO 1/2' LARGER THAN OUTSIDE DIAL' OF PENETRANT FILL MATERIAL A MINIMUM 1/2' CROWN TO FORM AROUND PENETRATING ITEM AND LAPPING 1/4' BEYOND PERIPHERY SECTION A -A I- PENETRANT TYPE ( ONE OF THE FOLLOWING) A. STEEL PIPE NOMINAL 12' DIA OF SMALLER, SCHEDULED OR HEAVIER B. CONDUIT NOMINAL 6' DIA OR SMALLER, EMT OR STEEL CONDUIT C. COPPER TUBING NOMINAL 6' DIA OR SMALLER TYPE L OR HEAVIER D . CO PPER TU ING NOMINAL 6 D IA OR SMALLER, RE GU L A R R H HEAVIER 2- FIRE6TOP SYSTEM HILTI CONSTRUCTION CHEMICALS INC. TYPE F5 6m5 OR FS ONE SEALANT 11/2 77 / a TED '( REFER =0R ADDITIONAL SLANT TO COMPL ,IULAR SPACE BE 'E AND GYPSUM E iEMBLY q 3/4', MAX 11/4' APE AS LISTED SECTION A -A 1- PENETRANT TYPE ( ONE OF THE FOLLOWING) A. NON METALLIC PIPE, POLY VINYL. CLORIDE (PVC) NOM 2' DIA OR SMALLER 2- FIRE5TOP 6Y5TEM HILTI CONSTRUCTION CHEMICALS INC. TYPE FS 611A OR F5 ONE SEALANT SMOKE BARRIER 1HR FR UL DESIGN NO W —L— 2098 FAI .A __ U11 UL DESIGN NO: W —L— 1085 1/2' MIN THICKNESS APPLIED WITHIN ANNULUS FLUSH WITH BOTH SIDES OF WALL SEALANT AND PACKING MATERIAL MIN 3' THK OF 5 PCF MINERAL WOOD GATT FOR PIPES 4' SMALLER 12' MAX DIA OF OPENING ANNULAR SPACE SHALL BE 0 AT THE POINT OF CONTACT TO A MAX OF 11/4' OF OUTSIDE DIAMETER OF PENETRANT 6' CMU ASSEMBLY 1 HOUR RATED REFER TO WALL TYPES AND LIFE SAFETY PLANS FOR ADDITIONAL INFORMATION SECTION A -A 1- PENETRANT TYPE ( ONE OF THE FOLLOWING) Q STEEL PIPE NOMINAL 10' DIA OF SMALLER, SCHEDULED OR HEAVIER B. CONDUIT NOMINAL 4' DIA OR SMALLER, EMT OR STEEL CONDUIT C. COPPER TUBING NOMINAL 4' DIA OR SMALLER TYPE L OR HEAVIER D. COPPER TUBING NOMINAL 4' DIA OR SMALLER, REGULAR OR HEAVIER 2- FIRESTOP 5Y5TEM HILTI CONSTRUCTION CHEMICALS INC. TYPE F5 601 / OR FS 604 / FS ONE SEALANT NA 0 a iiiii 11 UM1 1141111 UL DESIGN NO C —AJ -1149 V~:loyi1•1,121 IX t-1FZE XArI =V WALL A55EN3LY :FER TO WALL TYPE FOR ADDITIONAL =ORMATION --NETRANT TYPE A LISTED BELOW A �( 'n QQE i SEALANT TYPICAL 30TH ENDS MIN /;:S' I HIC:KNk55 C,'- i=.__ .. .. _. _.. APPLIED WITH THE ANNULUS, FLUSH WITH BOTH SURFACES OF WALL A I' -6' 1. PENETRANT TYPE (ONE OR MORE NOMINAL I' DIA) A STEEL ELECTRIC TUBING MINIMUM 1/2' MAX 1' CONDUIT RIGIDLY SUPPORTED ON BOTH 51DE5 OF WALL 2. FIRESTOP SYSTEM HILTI CONSTRUCTION CHEMICALS INC. TYPE F5 ONE SEALANT SMOKE BARRIER 1HR FR 3" UL DESIGN NO W -L -1095 1HR FIRE RATED WALL ASSEMBLY REFER TO WALL TYPE NON -RATED WALL ASSEMBLY REFER TO WALL TYPE GENERAL NOTES I. ALL THROUGH PENETRATIONS SHOWN ABOVE ARE BASED UPON SPECIFIC PRODUCTS AND MANUFACTURERS FOR OTHER ACCEPTABLE MANUFACTURER'S REFER TO PROJECT SPECIFICATIONS, 2. ALL ASSEMBLIES SHOWN ABOVE ARE REPRESENTATIVE ONLY FOR COMPLETE CONSTRUCTION REQUIREMENT. REFER TO EACH A66EMBLY NUMBER IN THE 'UL' MANUAL, VOLUME 2, 1399 EDITION. 3. FOR OTHER APPLICABLE REQUIREMENTS REFER TO PROJECT SPECIFICATIONS, 4. FOR FIRE RATED WALL A56EM13LY TYPES BEARING UL LABLE REFER TO PARTITION TYPES. SMOKE BARRIER PARTITION JOINT DETAIL It 7430 sw 48th street miami, florida 33155 phone: (305) 663 -1970 fax: (305) 663 -2312 e —mail: peter®diezarchitecture.corn pedro diez, ro A president or 0008996 ... U-1 , », V n 7430 sw 48th street miami, florida 33155 phone: (305) 663 -1970 fax: (305) 663 -2312 e —mail: peter®diezarchitecture.corn pedro diez, ro president or 0008996 ... ENGINEERING CONSULTANT \ R . V n r . 4th FLOOR 6141 SUNSET DRIVE SOUTH MIAMI, FLORIDA PROJECT No. 04.158.041 REVISIONS PENETRATION DETAILS wwol