06-113(2)-021OUTSIDE AIR FLOOR SLAB CEMENT GROUT TROWEL SM00T SEQUENCE OF OPERATION A. THE UNIT EVAPORATOR FAN SHALL RUN CONTINUOUSLY. B. A RISE OF LEAVING AIR TEMPERATURE ABOVE SETPOINT WILL CAUSE THE COMPRESSOR TO START. THE ELECTRONICALLY CONTROLLED HOT GAS VALVE WILL MODULATE IN RESPONSE TO THE ELECTRONIC LEAVING AIR TEMPERATURE SENSOR TO MAINTAINING LEAVING AIR TEMPERATURE SETPOINT. C. WHEN THE RETURN AIR TEMPERATURE FALLS BELOW THE LEAVING AIR TEMPERATURE SET POINT, THE COMPRESSOR SHALL TURNOFF AND THE BYPASS VALVE SHALL CLOSE. D. THE STATIC PRESSURE SENSOR SHALL MODULATE THE BYPASS DAMPER TO MAINTAIN THE SUPPLY DUCT PRESSURE SETPOINT. E. BOTH, THE RETURN AND OUTSIDE AIR DAMPERS SHALL WORK IN CONJUNCTION TO MAINTAIN SPECIFIED OUTSIDE - RETURN AIR RATIO DURING NORMAL OPERATING HOURS. OUTSIDE AIR DAMPER SHALL GO TO MINIMUM POSITION AND RETURN AIR DAMPER TO MAXIMUM DURING UNOCCUPIED TIME SCHEDULE. DOC CONTROLLER 120 VAC POWER SOURCE (BY DIVISION 16) NOTE: 1. PROVIDE ALL SYSTEM INFORMATION AT ONE CENTRAL LOCATION. CONTROLLER TO HAVE LCD OPERATOR'S DISPLAY PROVIDE SCHEDULING & EXPANSION CAPABILITY 2. DUCT SMOKE DETECTOR AS REQUIRED BY NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) REGULATIONS AND IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR LOCATION AND QUANTITIES. PROVIDED & WIRED BY DIVISION 16. TO VAV UNITS CONSTANT VOLUME AC UNIT WITH HOT GAS BYPASS CONTROL SEE MECHANICAL PLANS AND SCHEDULES FOR QUANTITIES FAN SECTION ISULATION AS SPECIFIED PASSES (ROUGH PIPE SLEEVE. PROVIDE DAMGLAS INSULATION THROUGH SMOKE VIBRATION ISOLATION ND /OR FIRE FLOOR SLAB. PAD ALL AROUND TOP OF CURB UNDER RTU IPE CLAMP. TYPICAL II —COIL SECTION FILTER SECTION M VD I I BIRDSCREEN ROOF � W, LJ 30" MIN. FACTORY FABRICATED FLEX CONN. (TYP.) ROOF CURB SUPPLY RETURN DUCT DUCT ROUTE CONDENSATE LINE TO NEAREST ROOF DRAIN, FULL SIZE HROMED PIPE COLLARS USED IN XPOSED AREAS. NOTE: ALL ROOF MOUNTED EQUIPMENT MUST ADHERE TO CURRENT HURRICANE CODES REGARDING ROOF TIE-IN AND WIND RESISTANCE. ROOFTOP UNIT No Scale PIPE FLOOR SLAB PENETRATION No Scale PROVIDE MANUF. RECOMMENDED — (CONDENSING UNITS SERVICE CLEARANCES GALV. STEEL CURB BY A/C MANUF. W602 CROSSBEAM r WITH r GUSSET PLATE L t/ WELDED ON SITE. W6x15 WELDED \—'W6xl5 3 "- GALV. STEEL PIPE 6' -0" MAX. (TYPICAL) x10 "x10" GALV. BOTTOM WELDED PLATE (TYPICAL)) IN d 4 4 4 4. d 4, 5/8" GALV. THRU BOLTS" PLATE WASHEF2 (TYPICAL) j" BOLTS 12" O.C. 4, BOLTS 1` J WIDTH OF MECHAINCAL UNIT (A) BAS INPUT /OUTPUT POINTS LIST TAG POINT NAME AIP AOP DIP DOP NOTES: 1 OUTSIDE /RETURN AIR DAMPERS 48 X 2 DIRTY FILTER SWITCH X 3 BY -PASS AIR DAMPER I X 4 CONDENSING UNIT - COMPRESSOR X 5 FAN STATUS SWITCH X 6 SUPPLY FAN START /STOP X 7 LEAVING AIR TEMPERATURE X 8 THERMOSTATIC EXPANSION VALVE X 9 STATIP PRESSURE SENSOR X 10 RETURN AIR TEMPERATURE X 11 ELECTRONIC HOT GAS VALVE X DOC CONTROLLER 120 VAC POWER SOURCE (BY DIVISION 16) NOTE: 1. PROVIDE ALL SYSTEM INFORMATION AT ONE CENTRAL LOCATION. CONTROLLER TO HAVE LCD OPERATOR'S DISPLAY PROVIDE SCHEDULING & EXPANSION CAPABILITY 2. DUCT SMOKE DETECTOR AS REQUIRED BY NATIONAL FIRE PROTECTION ASSOCIATION (NFPA) REGULATIONS AND IN ACCORDANCE WITH NATIONAL AND LOCAL ELECTRICAL CODES. SEE MECHANICAL AND ELECTRICAL DRAWINGS FOR LOCATION AND QUANTITIES. PROVIDED & WIRED BY DIVISION 16. TO VAV UNITS CONSTANT VOLUME AC UNIT WITH HOT GAS BYPASS CONTROL SEE MECHANICAL PLANS AND SCHEDULES FOR QUANTITIES FAN SECTION ISULATION AS SPECIFIED PASSES (ROUGH PIPE SLEEVE. PROVIDE DAMGLAS INSULATION THROUGH SMOKE VIBRATION ISOLATION ND /OR FIRE FLOOR SLAB. PAD ALL AROUND TOP OF CURB UNDER RTU IPE CLAMP. TYPICAL II —COIL SECTION FILTER SECTION M VD I I BIRDSCREEN ROOF � W, LJ 30" MIN. FACTORY FABRICATED FLEX CONN. (TYP.) ROOF CURB SUPPLY RETURN DUCT DUCT ROUTE CONDENSATE LINE TO NEAREST ROOF DRAIN, FULL SIZE HROMED PIPE COLLARS USED IN XPOSED AREAS. NOTE: ALL ROOF MOUNTED EQUIPMENT MUST ADHERE TO CURRENT HURRICANE CODES REGARDING ROOF TIE-IN AND WIND RESISTANCE. ROOFTOP UNIT No Scale PIPE FLOOR SLAB PENETRATION No Scale PROVIDE MANUF. RECOMMENDED — (CONDENSING UNITS SERVICE CLEARANCES GALV. STEEL CURB BY A/C MANUF. W602 CROSSBEAM r WITH r GUSSET PLATE L t/ WELDED ON SITE. W6x15 WELDED \—'W6xl5 3 "- GALV. STEEL PIPE 6' -0" MAX. (TYPICAL) x10 "x10" GALV. BOTTOM WELDED PLATE (TYPICAL)) IN d 4 4 4 4. d 4, 5/8" GALV. THRU BOLTS" PLATE WASHEF2 (TYPICAL) j" BOLTS 12" O.C. 4, BOLTS 1` J WIDTH OF MECHAINCAL UNIT (A) MIN. CLEARANCE ABOVE ROOF SURFACE (B) (INCHES) < 24" 14 24" < 36" 18 36"<48" 24 48"< 60" 30 > 60" 48 SEE TABLE TABLE 1511.7 FBC MULTIPLE CONDENSING UNIT MOUNTING DETAIL 4 .4 ROOF TOP UNIT HOUSING OR FAN HOUSING. ROOFING - SEE ARCH. DRAWINGS 3/8" x 3" "TAPCON" GALVANIZED CONCRETE ANCHORS (TYPICAL OF EIGHT - 2 PER UNIT SIDE) 3/8" BASE PLATE +r `• ' .. ''.:;�''��, >�::� �, < %:` ;''` ��' ATTACHED TO MFR'S ROOF CURB 3/8" x 2" GALVANIZED CARRIAGE BOLTS WITH 1 -1/2" FENDER WASHERS (TYPICAL OF EIGHT -2 PER SIDE OF UNIT.) CURB GASKETING (CONTINUOUS) AIR CONDITIONING UNIT MFG. PREFABRICATED CURB PITCHED TO MATCH ROOF SLOPE TYPICAL ROOFTOP EQUIPMENT CURB MOUNTING 4,4'91/4, 5� 8 WIDTH OF MECHAINCAL UNIT (A) MIN. CLEARANCE ABOVE ROOF SURFACE (B) < 24 14 24 < 36 18 36 < 48 24 48 < 60 30 > 60 48 TABLE 1511.7 FBC SINGLE CONDENSING UNIT MOUNTING DETAIL N.T.S. NOTE: ALL ROOF MOUNTED EQUIPMENT SHALL COMPLY WITH FLORIDA MECHANICAL CODE SECTION 301.13 FASTENERS SUPP BAND /AN I DUCT SIZE ANGLE 30 "x12" 1 "x1 "x " 1" x1 x 1-1 "x1- "x " 1- "xt- "x DUCT SIZE BAND 18 "x12" 1-4"x 16 G . 1%i" �pgNRl 9gHp Qf IR( N FqS 4RS EXPANSION �� WALL BOLT ANCH ANGLE IRON RISER SUPPORTS N TS 1 kAPANSIN 80I1 SLIP ON NEOPRENE BOOT CLAMPS 2" INSULATION — BUILT -UP ROOFING (REF.) PIPE SUPPORT /ANCHOR N.T.S. PIPING ACRYLIC CLAD 18 GA. GALV. COVER NAILER 2" INSULATION CANT. STRIP AND COUNTER FLASHING (REF.) CURB INSULATION (REF.) VSEE PIPING FLOOR STRUCTURAL ROOF PENETRATION DETAIL (REF.) ROOF PIPING PENETRATION No Scale diez architecture, inc. 7430 sw 48th street miami, florida 33155 phone: (305) 663 -1970 fax: (305) 663 -2312 e —mail: peter @diezorchitecture.com pedro diez, ra president or 0008996 ENGINEERING CONSULTANT PRV ENGINEERING, INC. Mechanical - Electrical - Plumbing - Fire Protection 6452 NW 77 CL, Miami, F4 0,1 F6 -Ph: 305.659.8827 - Fx. 305.656.5955 Board of Profewj& al Emiceam A.uthorcation No.: 00009635 Mochanica Eli jr r. + •F3 Ri-AW! Valdes, PE PE 31326 Eledriq+ n�F� er• ° Rgob 10 Vurjdw, Pt~ PE 32076 'ti t• {BERT VALDES,P'E PE #: 31326 6747 Office Building 4th Floor 6141 SUNSET DRIVE SOUTH MIAMI, FLORIDA PROJECT No. 04- 158.04 REVISIONS HVAC DETAILS