06-113(2)-019CONTRACTOR SHALL VERIFY ALL SPACE CONDITIONS AT JOB SITE PRIOR To FABRICATION OF DUCTWORK AND PURCHASE OF EQUIPMENT.
REFERENCES:
A ABC ASSOCIATED AIR BALANCE COUNCIL.
B. ADC AIR DIFFUSION COUNCIL.
C. MCA AIR MOVEMENT AND CONTROL ASSOCIATION.
D. AN51 AMERICAN NATIONAL STANDARDS INSTITUTE.
E. API AMERICAN PIPE INSTITUTE.
F. ARI AMERICAN REFRIGERATION INSTITUTE.
G. ASHRAE AMERICAN 60CIETY OF HEATING REFRIGERATION AND AIR CONDITIONING ENGINEERS.
H. AWE AMERICAN SOCIETY OF MECHANICAL ENGINEERS.
I. ASTM AMERICAN STANDARDS FOR TESTING MATERIALS.
J. AW6 AMERICAN WELDING SOCIETY.
K FM FACTORY MUTUAL.
L. N135 NATIONAL BUREAU OF STANDARDS.
M. NEC NATIONAL ELECTRIC CODE.
N. NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION.
0. NFPA NATIONAL FIRE PROTECTION ASSOCIATION.
P. OSHA OCCUPATIONAL SAFETY AND HEALTH ACT UNITED STATES DEPARTMENT OF LABOR STANDARDS.
Q. FBC FLORIDA BUILDING CODE.
R $MAGNA SHEET METAL AND /AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION.
5. $MC STANDARD MECHANICAL CODE.
T. UL UNDERWRITERS LABORATORIES INC.
U. FMC - FLORIDA MECHANICAL CODE.
DRAWING5: ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEM AND WORK INCLUDED IN CONTRACT. FOLLOW DRAWINGS
IN INSTALLING NEW AIR CONDITIONING 5Y5TEMf CHECK DRAWINGS OF ALL TRADES To VERIFY SPACES IN WHICH WORK WILL BE INSTALLED, IF
SPACE CONDITIONS ARE INADEQUATE, OR DO NOT AGREE WITH THE CONDITIONS SHOWN ON THE DRAWINGS NOTIFY THE PROJECT
ARCHITECT/ENGINEER PRIOR TO PROCEEDING WITH THE WORK, DO NO WORK UNTIL ALL CONDITIONS ARE CORRECTED. BEGINNING OF
INSTALLATION 15 AN ACCEPTANCE OF THE EXISTING CONDITIONS.
PERFORMANCE: CONTRACTOR SHALL VERIFY EXACT DIMENSIONS AT JOB SITE PRIOR TO FABRICATION OF ACCE66ORIE5 AND PURCHASE OF
EQUIPMENT. CONTRACTOR SHALL VERIFY OPERATING CONDITION AND VOLTAGES PRIOR To ORDERING EQUIPMENT, AND COMMENCING WORK
NOTIFY THE OWNER OF ANY DEFICIENCY THAT COULD F0681BLY DELAY OR AFFECT THE COMPLETION OF THE WORK
SUBSTITUTION$: EQUIPMENT SPECIFIED SHALL BE ADHERED To. HOWEVER, OWNER HAS THE FINAL DECISION ON THE TYPE AND QUALITY OF
EQUIPMENT TO BE SUPPLIED. CONTRACTOR SHALL OBTAIN WRITTEN PERMISSION FROM THE OWNER PRIOR TO PURCHASING SUBSTITUTE
EQUIPMENT. CONTRACTOR SHALL BEAR THE C06T OF ALL ENGINEERING WORK RELATED TO SUBSTITUTED EQUIPMENT.
WORK INCLUDED:
THE EXTENT OF THE AIR CONDITIONING WORK INCLUDES, BUT IS NOT LIMITED TO THE FOLLOWING:
1. THE INSTALLATION OF ALL SPECIFIED AIR CONDITIONING EQUIPMENT SUCH AS, BUT NOT LIMITED TO: AIR CONDITIONING UNITS, PIPING,
VALVES, INSULATION, THERMOSTATS, SMOKE DETECTOR$, DUCTWORK, DAMPERS, DIFFUSERS, ETC. TO WHERE SHOWN ON DRAWINGS, AS
WELL AS THE INSTALLATION OF ALL EQUIPMENT NOT NORMALLY SHOWN ON DRAWINGS BUT NECESSARY FOR THE SYSTEM TO OPERATE
AS INTENDED.
2. THE INSTALLATION OF NEW EXHAUST FANS, WITH RELATED DUCTWORK, GRILLES, ETC. AS SHOWN ON DRAWINGS AND /OR HEREIN
SPECIFIED.
3. THE FABRICATION AND INSTALLATION OF ALL PIPE ACCESSORIES SUCH AS PIPE SUPPORTS, PIPE SLEEVE$, DRAIN LEGS, DRAIN PANS,
ETC. WHETHER SHOWN ON DRAWINGS OR NOT, AS WELL AS THE FABRICATION AND INSTALLATION OF ALL DUCTWORK ACCESSORIES
SUCH AS VOLUME EXTRACTORS, TURNING VANE$, DAMPER6, ACCESS PANELS ETC. A$ SHOWN ON DRAWINGS OR AS NECESSARY FOR A
COMPLETE AIR DISTRIBUTION SYSTEM To OPERATE AS INTENDED.
4. THE EXECUTION OF AN AIR BALANCE FOR THE NEW SYSTEM.
5. ALL CUTTING AND PATCHING ASSOCIATED WITH TH15 INSTALLATION.
6. ALL PERMITS AND FEES FOR PERMITS.
HVAC SPECIFICATIONS
AIR DISTRIBUTION DEVICES:
PROVIDE ALL AIR DISTRIBUTION DEVICES CONSTRUCTED FROM ANODIZED ALUMINUM MANUFACTURED BY A SINGLE MANUFACTURER, "MCA"
AND "ADC" RATED OF SIZES SHOWN ON DRAWINGS WITH BORDER$ AND MOUNTING FRAME$ SUITABLE FOR THE LOCATION WHERE AIR
DISTRIBUTION PRODUCTS ARE TO BE INSTALLED. PROVIDE AND INSTALL AIR DISTRIBUTION PRODUCTS AS SCHEDULED.
DUCTWO •
FIBERGLA65 DUCTWORK MATERIAL: ONE INCH THICK GLASS FIBER DUCTBOARD FABRICATED FROM NON- CORR061VE, NON - HYGROSCOPIC,
PERMANENTLY ODORLE$$, MICROBACTERIAL -GROWTH INHIBITING, RESILIENT, LONG STAPLE, FABRIC GRADE GLASS FIBERS, FACTORY
PREFORMED INTO 6EMI -RIGID OR RIGID BOARD WITH A FLEXURAL RIGIDITY RATING OF 800E1 PER A5TM TEST NUMBER 0- 1031 -64 WHERE
NEITHER WIDTH NOR DEPTH OF DUCT EXCEEDS 46 INCH. AND WITH A FLEXURAL RIGIDITY RATING OF 1400E1 PER A6TM TEST NUMBER
0- 1031 -64 WHERE WIDTH OR DEPTH EQUAL$ OR EXCEEDS 48 INCH, FIBERGLASS BOARD SHALL BE NON - EROSIVE WHEN CONVEYING AIR AT
VELOCITIES TO 2000 I=PM, AND SHALL BE COVERED WITH A FIRE RETARDANT, MOISTURE 6EALING;, FACTORY- APPLIED JACKET MADE OF
REFLECTIVE, ALUMINUM FOIL KRAFT PAPER OF 2 MIL MINIMUM THICKNE66.
MANUFACTURER AND PRODUCT: CERTAINTEED TOUGHTGARD WITH A R =65 AND A MAXIMUM THERMAL CONDUCTIVITY OF 023 AT 15 DEGREE F
MEAN TEMPERATURE.
CONSTRUCTION: COMPLETED DUCT SYSTEM SHALL BE STABLE AND AIRTIGHT AT 2 INCH W.G. 6TAT*IC PRESSURE. INSTALL IN COMPLIANCE WITH
THE MANUFACTURER'6 RECOMMENDATIONS. PROVIDE CONTINUOUS VAPOR RETARDANT CONTINUITY AND SEAL IN ACCORDANCE WITH WACNA
STANDARD$. MITER ALL LONGITUDINAL CORNER6 (EXCEPT SEAMS) WITH JACKET UNDISTURBED. ROUND CRO65- SECTION DUCTS SHALL BE
FACTORY MOLDED ONLY. SQUARE AND RECTANGULAR DUCT$ SHALL BE SHOP OR FIELD FABRICATED FROM FLAT OUCTBOARO.
DUCT REINFORCEMENT: METALLIC DUCT REINFORCEMENT SUPPORT AND DUCT EQUIPMENT SLEEVES SHALL BE GALVANIZED STEEL.
FLEXIBLE OUCTWORK: DUCTWORK MANUFACTURED FROM STEEL WIRE HELIX ENCAPSULATED IN OO1IBLE LAMINATION OF POLYESTER AND
COVERED WITH HIGH DENSITY FIBERGLASS INSULATION REINFORCED WITH SCRIM AND VAPOR BARRIER SIMILAR To "IAIR MODEL 1000,
FLEXIBLE DUCT SUPPORT AND HANGERS:
SUPPORT FLEXIBLE DUCTS AS PER MANUFACTURER'6 RECOMMENDED INTERVALS BUT AT LEAST EVERY 5 FT.
MAINTAIN A MAXIMUM PERMISSIBLE SAG OF V PER FT OR LESS. TOTAL SAG SHALL NOT EXCEED 2.5 IN. OVER THE 5 FT. INTERVAL.
SELECT FLEXIBLE DUCT HANGERS FROM TABLE 4 -2 "MINIMUM HANGER SIZE$ - ROUND DUCT" EXCEPT THAT MIN. SPACING SHALL BE KEPT AT
51 -0 BETWEEN SUPPORTS. HANGER AND SADDLE MATERIAL IN CONTACT WITH FLEXIBLE DUCT SHALL BE AT LEAST %11 WIDE SO IT DOE$ NOT
REDUCE THE INTERNAL DIAMERTER OF THE DUCT WHEN THE SUPPORTED SECTION RESTS ON THE HANGER OR SADDLE, SADDLES SHALL
COVER AT LEAST ONE -HALF U4) THE CIRCUMFERENCE OF THE OUTSIDE DIAMETER OF THE DUCT AND PIT NEATLY AROUND THE LOWER HALF OF
THE OUTER CIRCUMFERENCE.
SUSPEND HANGERS FROM BUILDING STRUCTURE AS INDICATE[) IN THE LATEST SMACNA 11HVAC DUCT CONSTRUCTION STANDARDS - METAL AND
FLEXIBLE" FIG 4 -2 AND 4 -3 "UPPER ATTACHEMENT DEVICES, TYPICAL"
SHEET METAL DUCTWORK:
VENTILATION DUCTWORK:_
RIGID: ALL VENTILATION DUCTWORK SHALL BE MANUFACTURED FROM STANDARD GAUGE GALVANIIZED SHEET STEEL IN COMPLIANCE WITH
(SMACNA) STANDARDS FOR THE FABRICATION, CONSTRUCTION, AND INSTALLATION OF LOW AND MEDIUM PRESSURE STEEL DUCTWORK ALL
DUCT SEAMS AND JOINT$ SHALL BE SEALED WITH A NON HARDENING, NON MIGRATING 4" WIDE MASTIC (SIMILAR TO PERMACELL %VAF) OR
EQUIVALENT. SEALING SHALL BE DONE AS RECOMMENDED BY SEALER MANUFACTURER TO OBTAIN A CLA65 "All SEAL.
FLEXIBLE: VENTILATIONS DUCTS MADE OF CORRUGATED ALUMINUM WITH WATER TIGHT LOCK SEAMS, DESIGNED FOR LOW PRESSURE VENTING
APPLICATION WITH A MAXIMUM WORKING PRESSURE (POSITIVE OR NEGATIVE) OF 411 WS. AND A TEMPERATURE RANGE FROM -100 OF TO 400
OF. SIMILAR TO OMNIAIR MODEL 2000,
AIR CONDITIONING DUCTWORK:
1. ROUND: SHEET METAL ROUND DUCTWORK: PROVIDE UNITED MCGILL'5 "UNIRIB" ROUND DUCTWORK AND FITTINGS IN SIZE$ SHOWN ON
DRAWINGS, MACHINED FROM GALVANIZED STRIP -COIL STEEL WITH A STANDING RIB PROJECTING RADIALLY FROM THE OUTSIDE OF THE
FORMED ROUND DUCT AND PARALLELING TO THE CONTINUOUS HELICAL LOCK6cAM DUCT PATTERN. JOINT ALL DUCTS AND FITTINGS BY
$LIP - JOINING PIECES TOGETHER AS RECOMMENDED BY DUCTWORK MANUFACTURER. APPLY INTERNAL DUCT SEALER AS REQUIRED TO
PROVIDE CLASS "All SEAL. FURNISH ALL DUCT SECTIONS WITHOUT BLEMISHES OR IMPESMCTIONS, CLEAN INSTALLED DUCT$ FROM ALL
EXCESS 6EALANT AND ALL OTHER FOREIGN MATERIAL WHICH WILL IMPAIR EXTERIOR FINISIH APPEARANCE. PAINT ALL DUCT EXPOSED
SURFACES AS REQUIRED BY OWNER
2. RECTANGULAR: MANUFACTURED FROM STANDARD GAUGE GALVANIZED SHEET STEEL IN COflPLIANCE WITH ($MAGNA) STANDARDS FOR
THE FABRICATION, CONSTRUCTION, AND INSTALLATION OF LOW AND MEDIUM PRESSURE STEEL DUCTWORK ALL DUCT SEAMS AND JOINTS
SHALL BE SEALED WITH A NON HARDENING, NON MIGRATING 411 WIDE MASTIC (SIMILAR TO PERMACELL %6 W) OR EQUIVALENT, SEALING
SHALL BE DONE A$ RECOMMENDED BY SEALER MANUFACTURER TO OBTAIN A CLASS IIA11 SEAL.
DUCTWORK INSULATION: PROVIDE ALL INSULATION MATERIALS WITH A FLAME SPREAD CLAS31FICATION OF 25 FT -MIN OR LESS, SMOKE
DEVELOPED CLASSIFICATION OF 50 FT -MIN OR LESS, AND FUEL CONTRIBUTED CLA$SINCATION OF 25 FT -MIN OR LESS AS TESTED BY NFPA -255
- 11METHOO OF TESTING THE SURFACE BURNING CHARACTERISTIC$ OF BUILDING MATERIALS." INSULATE ALL AIR CONDITIONING DUCTWORK AND
INDICATED VENTILATION DUCTWORK WITH ONE OF THE FOLLOWING INSULATION TYPES:
I.- FLEXIBLE EXTERIOR INSULATION: I" THICK, 3 LB /CF DENSITY FEDERAL SPEC. HH -1 -558, FOIRM B, TYPE I, CLASS
DUCT REINFORCEMENT: FABRICATED IN ACCORDANCE WITH 116MACNA" DUCT CONSTRUCTION STANDARDS. ALL METALLIC DUCT REINFORCEMENT
SUPPORT AND DUCT EQUIPMENT SLEEVES SHALL BE MADE OF HEAVY GAGE GALVANIZED STEEL -
FLEXIBLE DUCT CONNECTIONS: AIR TRACK, TW15T LOCK CONNECTIONS MANUFACTURED FROM HEAIVY GAUGE GALVANIZED STEEL, FACTORY
ASSEMBLED WITH ADJUSTABLE DAMPER MOUNTED ON BEARINGS AND POSITIVE LOCKING HARDWARE.
diez
HVAC SPECIFICATIONS architecture,
inc.
AIR CONDITIONING UNITS:_
FACTORY SELF CONTAINED AIR COOLED A/C UNIT: 7430 sw 48th street
miami, florida 33155
phone: (305) 663 -1970
1. $ELF CONTAINED, FACTORY PREPACKAGED AND ASSEMBLED SUITABLE FOR OUTDOOR INSTALLATION. AC UNITS TO BE CONSTRUCTED fax: (305) 663 -2312
FROM HEAVY GAUGE GALVANIZED STEEL WITH RUST RESISTANT EPDXY FINISH, EA31LY REMOVABLE ACCESS PANELS, OUTSIDE AIR INTAKE peter ®diezarchitecture.com
WITH VOLUME DAMPER AND ALUMINUM BIRD SCREEN, ONE (1) INCH THICK NEOPRENE COATED FIBERGLA66 INTERNAL INSULATION THROUGH pedro diez
OUT ENTIRE CABINET. AC UNITS TO BE FACTORY ASSEMBLED WITH THE FOLLOWING COMPONENTS: ar 0008996
A COMPRESSOR($) TO BE HERMETICALLY SEALED OF THE 1150 RPM TYPE, RESILIENTLY MOUNTED WITH POSITIVE LUBRICATION, ENGINEERING CONSULTANT
CRANKCASE HEATER, MOTOR OVERLOAD PROTECTION, SERVICE VALVES, FILTER DRYER, WITH SUCTION AND DISCHARGE SHUT OFF
VALVE$, PRV ENGINEERING, INC.
B. CONDENSER COIL: CONSTRUCTED OF COOPER TUBING WITH ALUMINUM FIN$. Mechanical - Electrical - Plumbing - Fre Protection
6452 NVY C. CONDENSER PAN: VERTICAL DISCHARGE, DIRECT DRIVE, AXIAL TYPE, RE6ILIENTLY MOUNTED WITH ALUMINUM GUARD AND TOTALLY Board of Miami,FL3cv'neQ te:?0$B69r �7•Fx:305,8 .5955
Board of Professional Engine tiorzatq� 5
ENCLOSED, PERMANENTLY LUBRICATED BALL BEARING MOTOR WITH BUILT IN CURRENT AND OVERLOAD PROTECTION. Mechanical Engime r.. .,Ry W.iQes, f f, p 'X6
D. EVAPORATOR COIL: EVENLY SPACED ALUMINUM FINS MECHANICALLY BONDED TO COPPER TUBES (DESIGNED FOR 250 P61G) WITH Electrical Engineer _ Fiigo ' q V nereo, 3
A 16 GAGE GALVANIZED STEEL INSULATED INTERNAL DRAIN PAN WITH DRAIN CONNECTION.
E. EVAPORATOR FAN: SINGLE INLET TYPE WITH STATICALLY AND DYNAMICALLY BALANCED CENTRIFUGAL WHEEL WITH FORWARD - it
CURVED SINGLE WIDTH BLADES, DIRECT DRIVEN, RESILIENTLY MOUNTED ON SLEEVE BEARINGS. 0411 ;
F. AIR FILTER: TWO (2) INCH THICK FIBERCsLA66 THROWAWAY OR PERMANENT WASHABLE TYPE, FILTER TO BE LOCATED IN FACTORY,
FABRICATED FILTER RACK UPSTREAM OF EVAPORATOR COIL. � � �•,�✓
FACTORY PREPACKAGED SPLIT AC UNITS:_ SHALL CONSIST OF THE FOLLOWING: P. ROBERT VALDESf.'��
PE #: 31326 k.
1. CONDENSING UNITS: FACTORY PREPACKAGED AND ASSEMBLED SUITABLE FOR OUTDOOR INSTALLATION CONSTRUCTED FROM HEAVY tK
GAUGE GALVANIZED STEEL WITH RUST RESISTANT EPDXY FIN15H. AC UNITS TO BE FACTORY ASSEMBLED WITH THE FOLLOWING
COMPONENTS:
A COM 650 TO HERMETICALLY SEALED OF THE 1150 RPM TYPE RESILIENTLY MOUNTED WITH POSITIVE LUBRICATION, 6141
PRE R BE ERME ,
CRANKCASE HEATER, MOTOR OVERLOAD PROTECTION, SERVICE VALVES, FILTER DRYER, WITH SUCTION AND DISCHARGE SHUT OFF
VALVES. Off ice Building
8. CONDENSER COIL: CONSTRUCTED OF COOPER TUBING WITH ALUMINUM FINS.
C. CONDENSER FAN: VERTICAL DISCHARGE, DIRECT DRIVE, AXIAL TYPE, RESILIENTLY MOUNTED WITH ALUMINUM GUARD AND TOTALLY
ENCLOSED, PERMANENTLY LUBRICATED BALL BEARING MOTOR WITH BUILT IN CURRENT AND OVERLOAD PROTECTION. 5th Floor
2. AIR HANDLING UNIT: $ELF CONTAINED, DRAW THROUGH, FACTORY ASSEMBLED, PACKAGED AND PREWIRE1) AIR HANDLING UNITS, UL
LISTED, ARI AND AMCA RATED, OF CAPACITIES AND SIZES SHOWN ON DRAWINGS AND /OR HEREIN SPECIFIED AS FOLLOWS:
A CABINET. HEAVY GAGE GALVANIZED STEEL WITH EXPOSED CORNER$ AND EDGE6 ROUNDED, EASILY REMOVABLE PANEL$, WITH
INTERNAL ONE (U IN THICK NEOPRENE COATED FIBE%LA66 INSULATION. FINISHED WITH STANDARD FACTORY BAKED ENAMEL
FINISH.
B. EVAPORATOR COIL: EVENLY SPACED ALUMINUM FIN$ MECHANICALLY BONDED TO COPPER TUBES (DESIGNED FOR 150 PSIG) WITH
A 16 GAGE GALVANIZED STEEL INSULATED INTERNAL DRAIN PAN WITH DRAIN CONNECTION.
C. EVAPORATOR PAN: SINGLE INLET TYPE WITH STATICALLY AND DYNAMICALLY BALANCED CENTRIFUGAL WHEEL WITH FORWARD
CURVED SINGLE WIDTH BLADES, DIRECT DRIVEN, RESILIENTLY MOUNTED ON SLEEVE BEARINGS. 65141 SUNSET DRIVE
D. AIR FILTER: ONE (1) INCH THICK FIBERGLASS THROWAWAY OR PERMANENT WASHABLE TYPE, FILTER TO BE LOCATED IN FACTORY SOUTH MIAMI, FLORIDA
FABRICATED FILTER RACK UPSTREAM OF EVAPORATOR COIL. PROVIDE ONE (1) SET OF REPLACEMENT FILTERS TO OWNER UPON
SUBSTANTIAL COMPLETION
PROJECT No. 04- 158.05
3. REFRIGERANT PIPING_ SEAMLE$% HARD DRAIN, TYPE 1" COPPER TUBING OF SIZES RECOMMENDED BY UNIT'$ MANUFACTURER FOR THE
APPLICATION SHOWN ON DRAWINGS. REFRIGERANT SUCTION LINES SHALL BE INSULATED USING 111 THICK FLEXIBLE UNICELLULAR PIPING
UNSPL.IT INSULATION. ALL INSULATION SHALL COMPLY WITH NFPA 90 -A REVISIONS
CONTROL PRODUCTS:
1. PROGRAMMABLE ELECTRONIC THERMOSTATS: MANUFACTURED BY THE AC UNIT MANUFACTURER, THER 108TAT SHALL HAVE THE FOLLOWING
FEATURES: 1-DAY PROGRAMMING CAPABILITY, DIGITAL DISPLAY, INSTANT OVERRIDE, AUTOMATIC ADJUSTMENT OF TEMPERATURES UP TO
4 TIME$ A DAY, LCD READOUT IN FAHRENHEIT OR CELSIUS, 24 HOUR CLOCK, TAMPER RESISTANT, 100 % SOLID STATE.
2. SMOKE DETECTORS: PROVIDE AN IONIZATION SMOKE DETECTOR SUITABLE FOR AIR DUCT INSTALLATION TO EACH AIR CONDITIONING UNIT.
SMOKE DETECTOR SHALL BE AS FOLLOWS: LINE VOLTAGE (12011160) IONIZATION SMOKE DETECTORS OF THE MULTIPLE SAMPLE
ELEMENT$ TYPE, WITH A 11POWER ON" INDICATING LIGHT. INSTALL SAMPLING ELEMENTS IN BOTH MAIN SUPPLY AND MAIN RETURN AIR DUCTS.
ELECTRICALLY CONNECT THE IONIZATION SMOKE DETECTOR$ TO STOP ALL AIR CONDITIONING UNITS OPERATION IF PARTICLES OF SMOKE
ARE DETECTED IN THE AIR STREAM.
SEQUENCE OF CONTROL: FIFTH FLOOR
1. EQUIPMENT START SEQUENCE: THROUGH THE PROGRAMMABLE THERMOSTAT, UPON A CALL FOR COOLING, THE FOLLOWING EQUIPMENT HVAC SPECS
SHALL START IN SEQUENCE:
A AIR COOLED CONDENSING UNIT
B. EVAPORATOR PAN
GUARANTEE t WARRANTY:
1. FABRICATE ALL DUCTWOW AND PROVIDE AND INSTALL ALL EQUIPMENT IN COMPLIANCE WITH THE CODES HAVING JURISDICTION, AS
ENFORCED BY THE LOCAL BUILDING OFFICIALS.
2. PROVIDE WRITTEN GUARANTEE STATING THAT THE CONTRACTOR, WILL REPLACE OR REPAIR, FREE OF CHARGE, ANY EQUIPMENT OR
MATERIAL WHICH FAILS DURING A ONE YEAR PERIOD FROM DATE OF SUBSTANTIAL COMPLETION.
ENGINEERING ASSURANCE:
1. THE EQUIPMENT HAS BEEN SELECTED, AND THE HVAC SYSTEM HAS BEEN DESIGNED, TO COMPLY WITH NATIONAL FIRE PROTECTION
ASSOCIATION AND WITH THE FLORIDA BUILDING CODE.
SCALE: AS SHOWN
DATE: JANUARY 4, 2006
M -1.01