06-113(2)-018DUCTWORK LEGEND
24x12 -NEW DUCTWORK, FIRST DIMENSION 15 SIDE SHOLLI
UP DN
- CHANGE OF ELEVATION
IIIIIIIIIIII IIIIIIIIIII - FLEXIBLE DUCT
- TRANSITION, CONCENTRIC
- TRANSITION, ECCENTRIC
10x8 80 - TRANSITION, SQUARE -TO -ROUND
- SQUARE THROAT ELBOW
W /TURNING VANES
- RADIU5 ELBOW
i
i RECTANGULAR/ROUND BRANCH TAKE -OFF
OR ROUND /ROUND BRANCH TAKE -OFF
- MANUAL BALANCING DAMPER
} - RECTANGLE -TO -ROUND TAKE -OFF
- STANDARD BRANCH TAKE -OFF
- SPIN -IN TAKE -OFF
10 I I' 11111 - CEILING DIFFUSER, ROUND NECK
(CEILING DIFFUSERS ARE 4 -WAY THROW UNO)
i -ROUND DIFFUSER
- CEILING RETURN
- CEILING EXHAUST FAN
- CEILING DIFFUSER, RECTANGULAR OR
SQUARE NECK (CEILING DIFFUSERS
ARE 4 -1.11AY THROW UNO)
- SUPPLY REGISTER OR GRILLE
(VERTICAL MOUNT, SIDEWALI
� J -DOOR GRILLE
UCH - UNDERCUT DOOR
It - FLEXIBLE CONNECTION
® - REVISION REFERENCE
0
VAV UNIT SCHEDULE
- DETAIL REFERENCE: TOP - DETAIL"
M -�
BOTTOM - DRAWING" SHOILN ON
MIN.
CFM
- THERM05TAT /TEMPERATURE SENSOR
p�
- CONNECT TO EXISTING
�-
- DEMOLISH TO POINT INDICATED
0
VAV UNIT SCHEDULE
PACKAGED ROOFTOP
UNIT SCHEDULE
MAX.
CFM
MIN.
CFM
INLET
SIZE
MAX.
APD
(1N WG)
HEATING COIL
KW
STEPS
V5 -2 -1
1250
1400
200
TAG7
MODEL
SUPPLY
AIR
RETURN
AIR CFM
OUTSIDE
AIR CFM
EXT.
S.P.
GTH
MBI1
TSC
MB[I
COMP.
QTY.
COMP.
R L A
FAN
QTY
FAN
FLA
H
KW
L FAN
HP
UNfT
MCA
UNIT
MOCP
VOLT/
WH
WEIGHT
LBS.
RTU -1
(EXISTING)
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
-
RTU -2
RLKA- A- 035 -JK -006
3000
2600
400
1.25
90.0
x73.4
1
14
1
2.8
10.5
1.5
39.0
50
20x/3
ro20
RTU -3
RLKA -A- 085 -,)K-006
3000
2600
400
1.25
90.0
63.4
1
14
2
2.8
105
1.5
39.0
50
200/3
020
RTU -4
RLKB- A- 120 -CL -000
4000
3200
800
1.5
125.0
90.0
2
20
2
3.0
14.0
3.0
59.0
10
2083/3
'1
RTU -5
RLKA- A- 035 -1oIK -006
3000
2x&00
400
1.25
90.0
ro3.4
1
14
2
2.8
10.5
1.5
39.0
50
200/3
820
NOTES:
1. ALL MODELS BASED ON UNITS
MANUFACTURED BY: RHEEM
2. PROVIDE HOT -GAS BYPASS FOR ALL RTU'S
3. PROVIDE FACTORY ROOF CURB.
COORDINATE WITH ARCHITECTURAL PLANS FOR EXACT THICKNESS OF
ROOF INSULATION PRIOR
TO ORDERING
CURB.
4. PROVIDE 6 -ROW COOLING COIL WITH STAINLESS STEEL DRAIN PAN
5. ROOFTOP UNITS AND ASSOCIATED EXHAUST FANS SHALL SHUT DOWN UPON FIRE ALARM SIGNAL
6. PROVIDE SINGLE POINT ELECTRICAL
CONNECTION
7. PROVIDE WITH 30% EFFICIENCY
FILTERS IN COMPLIANCE WITH ASHRAE STANDARDS 52.1 -1992
8. AMBIENT DESIGN TEMPERATURE
IS 105 F0
0
VAV UNIT SCHEDULE
PLAN
MARK
DESIGN
CFM
MAX.
CFM
MIN.
CFM
INLET
SIZE
MAX.
APD
(1N WG)
HEATING COIL
KW
STEPS
V5 -2 -1
1250
1400
200
12
0.15
4.5
1
V5 -2 -2
515
800
95
8
0.15
2
1
V5 -2 -3
1350
1400
200
12
0.15
4.5
1
V5 -3 -1
1100
1200
125
10
0.15
3
1
V5-3-2
900
1200
125
10
0.15
3
1
V5-3-3
1000
1200
125
10
0.15
3
1
V5 -5 -1
1025
1200
125
10
0.15
3
1
V5 -5 -2
850
1200
125
10
0.15
3
1
V5 -5 -3
1250
1 1400
200
12
0.15
4.5
1
1500 -3000
1444
24x24
NOTES:
1 ALL MODELS BASED ON UNITS BY: METALAIRE
2 VERAY MODELS AND FINISH WITH ARCHITECT
3 VERIFY MOUNTING FRAMES WITH ARCHITECT
4 PROVIDE SQUARE TO ROUND ADAPTER FOR CG.
5 PROVIDE PLASTER FRAMES FOR ALL AIR DEVICES.
NOTES:
I. BASIS OF DESIGN: TITUS MODEL "DE5V"
2. ALL HEATING COILS UNDER 5K SHALL BE 203V /I. VERIFY WITH ELECTRICAL
DRAWINGS AVAILABLE VOLTAGE PRIOR ORDERING A/C EQUIPMENT.
3. SEQUENCE OF CONTROL: ON A RISE OF ROOM TEMPERATURE THE ELECTRIC HEAT
WILL DE- ENERGIZE. ON A FURTHER RISE OF ROOM TEMPERATURE THE VAV
CONTROLLER WILL MODULATE COOL AIRFLOW FROM MINIMUM (SEE SCHEDULE) TO
MAXIMUM SETTING,
AIR DISTRIBUTION SCHEDULE
Y.
TAG
MODEL
AIR FLOW
(CFM)
DIFF
SIZE
DUCT
SIZE
ACCESSORIES/
CONSTRUCTION
A
LTC[)
0 - 25
6x6
4 "0
FINISH: SEE ARCH 016
OFFICE
FIRE RATED ROOF /FLOOR CEILING ASSEMBLY
25 15
8x3
6 "0
O.B.D.: YES
180
SMOKE CONTROL
w - 150
!0x10
64
MATERIAL: ALUMINUM
0
S
!36-250
!2x!2
100
ROTUND NECK
1
251.400
111
12 "0
3164050
2040
144
51
24,24
16 110
RA
RH
0.250
!0x.6
12 4
FINISH: SEE ARCH DA
ER
250 -400
126
14 "0
DAMPER: YES
400 -600
124
16 "0
MATERIAL: ALUMINUM
600 -300
Ibxl6
Ibxlb
ROUND OR 51
300 -1500
20x.20
20x20
NECK AS REQ'D
1500 -3000
1444
24x24
NOTES:
1 ALL MODELS BASED ON UNITS BY: METALAIRE
2 VERAY MODELS AND FINISH WITH ARCHITECT
3 VERIFY MOUNTING FRAMES WITH ARCHITECT
4 PROVIDE SQUARE TO ROUND ADAPTER FOR CG.
5 PROVIDE PLASTER FRAMES FOR ALL AIR DEVICES.
IIVAC DESIGN REQ
Y.
NO
DUCT SMOKE DETECTOR(S)
/ES
Ix
PEOPLE
DENSITY
FIRE DAMPER (S)
)/
505
SMOKE DAMPER(S)
15
FIRE RATED ENCLOSURE
1�
OFFICE
FIRE RATED ROOF /FLOOR CEILING ASSEMBLY
1
20
FIRE STOPPING
/
Ix
180
SMOKE CONTROL
1,485
N/A
J
Lf CA 1.) 111 IVA 114 5411 Z[V11 v I km
1. CONNECTION TO EQUIPMENT SHALL BE VERIFIED WITH
MANUFACTURER'S CERTIFIED DRAWINGS. TRANSITIONS TO ALL
EQUIPMENT SHALL BE VERIFIED AND PROVIDED FOR EQUIPMENT
FURNISI -QED.
2, VERIFY AT JOB SITE AVAILABLE VOLTAGE PRIOR TO ORDERING
EQUIPMENT.
3. NOTIFY ARCHITECT OF ANY DISCREPANCIES BETWEEN
CONSTRUCTION DOCUMENTS AND ACTUAL FIELD CONDITIONS.
4. DIMENSIONS SHALL BE FIELD - VERIFIED AND COORDINATED
PRIOR TO PROCUREMENT OR FABRICATION. COORDINATE THE
WORK WITH OTHER TRADES INVOLVED. FIELD MODIFICATIONS
SUCH AS OFF5ET5 IN PIPING OR DUCTWORK (INCLUDING DIVIDED
DUCTWORK) NEEDED DUE TO OBSTRUCTIONS OR INTERFERENCE
SHALL BE PROVIDED AT NO ADDITIONAL COST, FOR PROJECTS
INVOLVING RENOVATION, COORDINATE NEW WORK WITH EXISTING
ELEMENTS SUCH AS THE BUILDING STRUCTURE AND
ARCHITECTURAL FEATURES, SPRINKLER PIPING, LIGHTS,
PLUMBING, AND ELECTRICAL CONDUIT.
5. DUCT CONSTRUCTION SHALL BE IN ACCORDANCE WITH THE
LATEST EDITION OF THE SMACNA HVAC DUCT CONSTRUCTION
STANDARD.
�. PROVIDE AIR TURNING VANES IN ALL 90 DEGREE RECTANGULAR
DUCT ELBOWS.
1. DUCT SIZES AND ALL OPENINGS THROUGH BUILDING
CONSTRUCTION 5HALL SUIT EQUIPMENT FURNISHED.
8. COORDINATE DIFFUSER, GRILLE AND REGISTER LOCATIONS WITH
ARCHITECTURAL CEILING PLANS AND EQUIPMENT FROM ALL
TRADES.
9, PROVIDE PROGRAMMABLE THERMOSTAT FOR ALL AIR HANDLING
UNIT5.
10, LOCATE THERMOSTATS, TEMPERATURE SENSORS, 1HUMIDISTAT5,
AND HUMIDITY SENSORS AT 48" ABOVE FINISHED FLOOR UNLE55
NOTED OTHERWISE, COORDINATE LOCATION5 WITH OTHER
EQUIPMENT, FURNITURE, AND DOOR SWINGS.
11. ALL EQUIPMENT, DUCTWORK, ETC., SHALL BE SUPPORTED AS
DETAILED AND /OR SPECIFIED. PROVIDE ADDITIONAL
SUPPORTS AS REQUIRED TO PROVIDE A VIBRATION -FREE, RIGID
INSTALLATION.
12. ALL DUCT 31ZE5 SHOWN ARE INSIDE CLEAR DIMENSIONS.
13, DAMPERS AND INSIDES OF DUCTS V15I5LE THROUGH GRILLES,
REGISTERS AND DIFFUSERS SHALL BE PAINTED FLAT BLACK,
14. REFER TO TYPICAL DETAILS FOR PIPING AND INSTALLATION OF
EQUIPMENT.
15, TRAPPED CONDENSATE DRAINS FROM ALL MECHANICAL
EQUIPMENT SHALL BE PROVIDED FOR PROPER DRAINAGE TO
SUIT EQUIPMENT FURNISHED.
14�,. AGCE55 PANELS IN DUCTWORK AND CEILINGS SHALL BE
PROVIDED WHERE REQUIRED FOR OPERATION, BALANCING OR
MAINTENANCE OF ALL MECHANICAL EQUIPMENT.
11. ALL DUCTWORK AND PIPING IS SHOWN SCHEMATICALLY. PROVIDE
ALL TRANSITIONS, TURNING VANES, ELBOWS, FITTINGS, ETC., TO
ALLOW SMOOTH FLOWS.
18, ALL SPLIT DUCT FITTINGS SHALL TRANSITION TO FULL 51ZE OF THE
SUM OF BOTH BRANCHES, UPSTREAM OF SPLIT.
19, VERIFY MODELS AND FINISH WITH ARCHITECT PRIOR TO
PURCHASING GRILLES, REGISTERS, DIFFUSERS, LOUVERS AND
OTHER AIR DISTRIBUTION DEVICES.
20.PROVIDE FLEXIBLE DUCT CONNECTIONS ON ALL DUCTWORK
CONNECTING TO EACH FAN, AIR HANDLING UNITS, AND FAN COIL
UNIT5.
21. PROVIDE TRANSITIONS AT DIFFUSER NECKS AS REQUIRED TO
MATCH SIZES OF FLEX DUCTS TO BE CONNECTED.
22. INTERRUPTIONS TO EXISTING SERVICES SHALL BE SCHEDULED
FOR TIMES OTHER THAN NORMAL OPERATING HOURS (SUCH AS
NIGHTS AND WEEKENDS). SUCH INTERRUPTIONS TO SERVICES
SHALL NOT BE MADE WITHOUT THE PRIOR WRITTEN CONSENT OF
THE OWNER'S REPRESENTATIVE AND PROPER COORDINATION
WITH OTHER TRADES. PRE -WORK SHALL BE PERFORMED TO
MAKE THE SHUTDOWN PERIOD AS BRIEF AS POSSIBLE,
23, MAINTAIN CLEARANCE OF A MINIMUM OF 7" BETWEEN DUCTWORK,
PIPING, EQUIPMENT, ETC., AND ALL FIRE RATED AND FIRE /SMCKE
RATED PARTITION5 TO ALLOW FOR INSPECTIONS OF RATED
WALLS.
24. DUCT RUNOUTS TO DIFFUSERS SHALL MATCH THE SIZE OF THE
DIFFUSER NECK. UNLE55 OTHERWISE NOTED,
25. ALL EQUIPMENT AND VALVE DRAINS SHALL BE INDEPENDENTLY
PIPED FULL 51ZE TO THE NEAREST PLUMBING DRAIN.
ASHRAE STANDARD 62 -2001
OUTDOOR AIR REQUIREMENTS FOR VENTILATION
APPLICATION
AREA
(SF)
PEOPLE/
1000 SF
CFM /
PERSON
CFM /
SQ. FT.
PEOPLE
DENSITY
O/A
CFM
RECEPTION
505
60
15
30
454
OFFICE
5,555
1
20
39
180
STORAGE / CORRIDORS
1,485
N/A
N/A
0.05
0
S
BREAK ROOM
145
5
20
1
20
TOTAL
1,690
10
1,262
diez
architecture,
inc.
7430 sw 48th
street
miami, florido
33155
phone: (305)
663 -1970
fax: (305)
663 -2312
peter @diezarchitecture.com
pedro diez
or 0008996
ENGINEERING CONSULTANT
PRV ENGINEERING, INC.
Mechanical - Electrical - Plamb'ng - Fire Protectior
6452 NW 77 Gt., Miao, , VV jl �k 05.859_627 - Fx: 305.856.5955
Board of Profess' 1i n sneers u� No.: 00009635
k -
Mechanical Ii P. I�ope i{4� � �� PE 31326
•+ Eleqtri4l 1i Rigob�r�o�ej , �i PE 32076
04 • OL iw
4. w
to
P. R08ERT #VAL'DEB, f'l�v'
PE #: 31326
G141
Office Building
5th Floor
6141 SUNSET DRIVE
SOUTH MIAMI, FLORIDA
PROJECT No. 04- 158.05
REVISIONS
FIFTH FLOOR
HVAC SCHEDULES
NOTES AND LEGEND
SCALE: AS SHOWN
DATE: JANUARY 4, 2006
- T FalLf
6