06-113(2)-008PENETRATION AS LISTED
BELOW
I HOUR FIRE RATED
WALL ASSEMBLY REFER
TO WALL TYPE FOR ADDITIONAL
INFORMATION
FILL MATERIAL TO B
FORCED INTO ANNUL
TO MAXIMUM EXTENG
POSSIBLE
1/4' TO 1/2' LARGER
THAN OUTSIDE DIA:i~
OF PENETRANT
FILL MATERIAL A MINIMUM 1/2'
CROWN TO FORM AROUND
PENETRATING ITEM AND LAPPING 1/4'
BEYOND PERIPHERY
SECTION A -A
I- PENETRANT TYPE ( ONE OF THE FOLLOWING)
A. STEEL PIPE NOMINAL 12' DIA OF SMALLER SCHEDULED OR HEAVIER
B. CONDUIT NOMINAL 6' DIA OR SMALLER, EMT OR STEEL CONDUIT
C. COPPER TUBING NOMINAL 6' DIA OR SMALLER TYPE L OR HEAVIER
D. COPPER TUBING NOMINAL 6' DIA OR SMALLER REGULAR OR HEAVIER
2- FIRE5TOP SYSTEM HILTI CONSTRUCTION CHEMICALS INC. TYPE F5 605
OR F5 ONE SEALANT
A 1 HR FIRE RATING
UL DESIGN NOS W -L- 1085
rED
r REFER
=0R ADDITIONAL
A
ILANT TO COMPLETELY FILL -
IULAR SPACE BETWEEN THE
E AND GYPSUM BOARD
>EMBLY
4 3/4', MAX 11/4'
'PE AS LISTED
SECTION A -A
1- PENETRANT TYPE ( ONE OF THE FOLLOWING)
A. NON METALLIC PIPE, POLY VINYL. CLORIDE (PVC)
NOM V DIA OR SMALLER
2- FIRE5TOP SYSTEM HILTI CONSTRUCTION CHEMICALS INC. TYPE F5 VIA
OR F5 ONE SEALANT
C 1 HR FIRE RATING
UL DESIGN NO W -L- 2098
\K
K
IM FIRE RACED WALL A*Or- CL_Y
:FER TO WALL TYPE FOR ADDITIONAL
:ORMATION
:NETRANT TYPE A L157ED 13ELO'JJ
n �
N
SEALANT TYPICAL
30TH ENDS
MIN S /8' THICKNESS OF F.__
APPLIED WITH THE ANNULUS, FLUSH
WITH BOTH 6U5--dFACE5 OF WALL
A
SECTION A -A
1. PENETRANT TYPE CONE OR MORE NOMINAL I' DIA)
A STEEL ELECTRIC TUBING MINIMUM 1/2' MAX I' CONDUIT RICsIDLir
SUPPORTED ON E30TH 51DE5 OF WALL
2. FIRESTOP 5Y5TEM HILTI CON5TRUCTION CHEMICALS INC.
TYPE F5 ONE SEALANT
g 1 HR FIRE RATING 3r
,) UL DESIGN NOS W -L -1095
1/2' MIN THICKNESS APPLIED WITHIN ANNULUS
FLUSH WITH BOTH SIDES OF WALL
SEALANT AND PACKING MATERIAL
MIN 3' THK OF 5 PCF MINERAL
WOOD BATT FOR PIPES 4' SMALLER
12' MAX DIA OF OPENING
ANNULAR SPACE SHALL BE
0 AT THE POINT OF CONTACT
TO A MAX OF 11/4' OF
OUTSIDE DIAMETER OF PENETRANT
5' CMU ASSEMBLY I HOUR RATED
REFER TO WALL TYPES AND LIFE SAFETY
PLANS FOR ADDITIONAL INFORMATION
SECTION A -A
I. PENETRANT TYPE ( ONE OF THE FOLLOWING)
A. STEEL PIPE NOMINAL 10' DIA OF SMALLER, SCHEDULED OR HEAVIER
B. CONDUIT NOMINAL 4' DIA OR SMALLER EMT OR STEEL CONDUIT
C. COPPER TUBING NOMINAL 4' DIA OR SMALLER TYPE L OR HEAVIER
D. COPPER TUBING NOMINAL 4' DIA OR SMALLER, REGULAR OR HEAVIER
2- FIRESTOP SYSTEM HILTI CONSTRUCTION CHEMICALS INC. TYPE F5 601 /
OR FS 604 / FS ONE SEALANT
1J 1 HR FIRE RATING
I
UL DESIGN NO C -AJ -1149
IHR FIRE RATED
WALL ASSEMBLY
REFER TO WALL TYPE
NON -RATED
WALL ASSEMBLY
REFER TO WALL TYPE
1 HR FIRE RATED PARTITION
)JOINT DETAIL
GENERAL NOTES
I. ALL THROUGH PENETRATIONS SHOWN ABOVE ARE BASED UPON
SPECIFIC PRODUCTS AND MANUFACTURERS. FOR OTHER ACCEPTABLE
MANUFACTURER'S REFER TO PROJECT SPECIFICATIONS.
2. ALL ASSEMBLIES SHOWN ABOVE ARE REPRESENTATIVE ONLY FOR
COMPLETE CONSTRUCTION REQUIREMENT.
REFER TO EACH ASSEMBLY NUMBER IN THE 'UL' MANUAL, VOLUME 2, 1999
EDITION.
3. FOR OTHER APPLICABLE REQUIREMENTS REFER TO PROJECT
SPECIFICATIONS,
4. FOR FIRE RATED WALL ASSEMBLY TYPES BEARING UL LABLE REFER
TO PARTITION TYPES.
11C
7430 sw 48th street
miami, florida 33155
phone: (305) 663-1970
fax: (305) 663 -2312
peter @diezarchitecture.com
pedro diez
ar 0008996
ENGINEERING CONSULTANT
G941
Office Building
5th Floor
6141 SUNSET DRIVE
SOUTH MIAMI, FLORIDA
PROJECT No. 04- 158.05
REVISIONS
FIRE
PENETRATION
DETAILS
2
y
SCALE. AS SHOWN
:` 4...:»...... i' z✓: : >x.:.t ».'! :i'rY:i::::u�:z:>u.4 .✓.:;.:'. %ii! �. »:.e.. & %��,
DATE: JANUARY 4, 2006
A6.0