05-1856-016REF. LINES
STEEL RODS WRHREADED
ENDS (TYP. 4 PLACES)
SUPPORT FROM STRUCTURE
ABOVE AS REQ'D.
VIOL ISOLATORS
FLEX CONN. (TYPJ
8/A
SECONDARY CONDEN8,4 111�111111��111�111
LINE WITH ESCUTCHEON
PLATE At C81LNG.
TERMINATE PIPE 16"BELOW.
ROUTE MAIN CONDENSATE
LNE TO PLUMBING GOND.
SYSTEM SEE PLU M15 NG
DRAWINGS FOR SIZE.
GALVANIZED SWEET METAL SECONDARY
DRAM PAN TO EXTEND 2" BEYOND UNIT
ON ALL SIDES BY Ili ' DEEP.
•`
PROVIDE SWEET METAL
BLANK -OFF t0 SEAL
ORIGINAL FILTER ACCESS
PROVIDE 2 SETS OF
240)24 "xl" 25% 6F.
FILTERS.
FAN
10' FLEX. FIELD `
OFFSET AS REQ'D.
CEILING
FAN COIL UNIT DETAIL
N.T.B.
FLEX DUCT SHALL EXTEND
STRAIGHT FOR AT LEAST
SIX (6) INCHES FOR DUCT
CONNECTION BEFORE BENDING
�0h
Ntk, °Is
s
.
�� T
Ins
4R P s
Fl-EXIBLE DUCT SUPPORT DETAIL
NTS
a
DOME TYPE ROOF EXHAUST FAN
SECURE FAN TO CURB W/ IS SWEET
METAL SCREWS 4" FROM ALL CORNERS
4 AT CENTER POINT OF ALL FOUR SIDES
-FACTORY ROOF CURB W/ INSULATION
MINIMUM 12' ABOVE FNISWED ROOF
SECURED TO ROOF DECK WU 1/4"
BOLTS, WASHERS AND NUTS
ON ALL FOUR CORNERS
,TYPICAL BUILTUP ROOF STRUCTURE
' X I" X 1/16" STEEL ANGLE WELDED
TO TOP CHORD OF JOIST ON BOTH
SIDES
SECURE DUCT TO STEEL ANGLE W/
SWEET METAL 6CREWO
JL JL
SWEET METAL EXHAUST DUCT
ROOF MOUNTED EXHAUST FAN DETAIL
IN&I,
CONCRETE OR MASOI RW
RETAINING CONSTUCTION
I VYx 1 1/1•X1/8"
LL SI
MIN. ADES (SEE CLEARANCE VD' PER
NOTE • 2) CAULK , : ' 4' MN. LINEAR FOOT BOTH
PERIMETER, i �i DIMENSIONS.
NOTES in MIN.
U1.. LABELED FIRE DAMPER
MANUR OR Fl (bbb) SECURE TO SLEEVE
FABRICATED STEEL
SLEEVE 16 GA MIN
SWEET
DUCT PLAN "S" SLIP
168 DUCT SI
RISIBLE WRAPPED 814EET
LIMO METAL DUCT
NOTE •
FASTENER
DUCT WRAP W1VAF'OR
6' MAX BARRIER (TYPJ
EACH SIDE
FIRE RESIST CLOSURE TAPE (TYPJ
MATERIAL. (TYPJ METAL STUD CONSTRUCTION
FIRE DAMPER INSTALLATION DETAIL
N.T.S.
N1OTESS
L PROVIDE ACCESS DOOR 4 LABEL ON SIDE OR BOTTOM OF DUCT AS FOLLOWS,
DUCT UDTH DOOR SIZE
6' THIRU 18' 6' X12"
19" THIRD 36' 12" X IBM
31' AND ABOVE 18" X 18'
2. U5 x Lb x I/8" RE:TAINNG ANGLES BWALL LAP STRUCTURAL OPENING 1" MIN. 4
COVER COMERS OF OPENINGS. ANGLES MUST NOT BE ATTACHED TO EAC44 OTHER
AT COFRNEIRS OR TO WALL. ATTACH TO SLEEVE.
3. ALL ATTACFMENTS PER MANUFACTURER'S APPROVED INSTALLATION INSTRUCTION.
4. VERTICAL POSITION SHOWN. HORIZONTAL INSTALLATION SIMILAR DAMPER TO BE
SPRING LOADED WHEN HORIZONTAL
TURNING �8 A
BRANCH DUCTWORK
TRANSITION TRANSITION
BRANCH, EEAAQ4 B�I IDE OA OPENING ON
F SPLI1'TERACCORDING
TO AIR QUANITY.
4
SPLITTER DAMPER
CONTROL ROD WITH MAIN TRUNK LINE
LOCK DEVICE
SPLUTTER DAMPER DETAIL
KTA
NOTE:
AHU WIT
UNION —
..........
...........
...........
I
VIBRATION ISOLATOR
(WHEN REQ'D)
1! 6" CONCRETE PAD
REMOVEA5LE TRAP
CONDENSATE DRAIN 4 TRAP DETAIL
NTS
OF 1" IOUN
UNION
COPPER PIPE- SLOPE
TO CONDENSATE DRAIN
�Y' MIN.
TRAP SEAL
SUPPLY METAL MAIN
TYPICAL TRANSITION
MAX 20' ANGLE
VOLUME DAMPER W/
LOCKING DEVICE
STRUCTURAL CHANNEL I V�
4b' TAKEOFF SWEET I"ETAL
BRANCH DUCT
BRANCH DUCT TAKEOFF DETAIL
NTS
SWEET METAL RUtNN£R TOP AND BOTTOM
SECURED TO DUCT WITH SWEET MEtAJ. BORE••"
SWEET METAL. SINGLE alARTER ROUND
TURNING VANES
QUI
TYPICAL FABRICATED SHEET
METAL ELBOW
SHEET METAL SINGLE QUARTER ROUND
TURNING VANES WITH FLANGED FASTENERS
TOP AND BOTTOIN
SHEET METAL RUNNER ER FASTENED t0 MGT
WITH SHEET METAL BCREWB -
DUCT TURNING VANE DETAIL
NTS
SHALL C
`I' WITH
L"?A
UPPER ATTAC441ENT
_
FLEXIBLE QV=tl 8' -O" MAX
2 -0" MX LENGTH -
EU
CEILING (T -BAR S
GYP. BOARD 81
45' TAKEOFF OR ROUND
MOVHTBEM SID H CO1.AR
ADJUt3TABLE�CLAMP
ADJUSTABLE CLAMP
DUCT SEALER
INSULATE TOP PANEL
OF DIFFUSER OR GRILLE
AIR DISTRIBUTION DEVICE
LAYN SHOWN.
SURFACE MOUNT SIMILAR
NOTES
L FLEXIBLE DUCTS SHALL BE ONE PIECE AND SHALL NOT BE SPLICED TOGETHER.
2. EXTEND FLEXIBLE DUCT INSULATION TO DUCTA:o FRUSER PANEL INSULATION
AND SEAL WITH MASTIC.
3. FLEXIBLE AIR DUCT SHALL NOT EXCEED 8 FT. U4EN EXTENDED. ELBOW RADIUS
SIZED FOR NO LESS THAN R / D ■ Im .
FLEXIBLE DUCT TAKEOFF DETAIL
NTS
W&ACOE WITH
zn SAT
BRANCH DUCTWORK
TRANSITION
PROPORTIONAL OPENING ON
EACH SIDE OF SPLITTER ACCORDING
TO AIR QUANITY.
SPLITTER DAMPER
MAN TIMM LINE
d iez
architecture,
inc.
5001 sw 74th court suite 105
miami, florida 33155
phone: (305) 663 -1970
fax: (305) 663 -2312
e —mail: petermdiezarchitecture.com
pedro diez, ra
president ar 0008996
ENGINEERING CONSULTMUT
V ENGINEERING INC.
!Ilecllanl I � - Fn pmbction
rm n c>.. u6irC"Fi 33100 . R .ear► • Fz W5.0e0.5e55
Board of P?r;; W Enaineers Authorization No.: 00009635
Mechanical Enpir r rP) Robert Valdes, PE PE 31326
Electrical RrG 8 Venereo. PE PE 32076
PR 4-T NA,.� bp1
owl
6141 Sunset
J 6141 SUNSET DRIVE
SOUTH MIAMI, FLORIDA
SPLITTER DAMPER DETAIL
N.T.B. PROJECT No. 03 -115
REVISIONS
IDA MECHANICAL CODE SECTION 301.13
5RICK VENT MOUNTING DETAIL
NT6
3- :__
7
SCREEN
10" X 4" SWEET METAL
EXHAUST DUCT
STEEL HANGER WIRE
TYPICAL CEILING CABINET
EXHAUST FAN WITH BACKDRAFT
DAMPER, LOW NOISE LEVEL
AND NO VIBRATION.
FRONT FACE GRILLE WITH
FASTENING 6CREENS
EXHAUST FAN HANGING
BRACKET (ADJUSTABLE)
CEILING EXHAUST FAN MOUNTING DETAIL
NT8
HVAC
DETAILS
SCALE: 3/16" = 1' -0"
DATE: NOV -14 -2005
M�1002
6