05-1856-015HVAC SPECIFICATIONS GENERAL: CONTRACTOR SHALL VERIFY ALL SPACE CONDITIONS AT JOB SITE PRIOR TO FABRICATION OF DUCTWORK AND PURCHASE OF EQUIPMENT. REFERENCES: A. ABC ASSOCIATED AIR BALANCE COUNCIL. B. ADC AIR DIFFUSION COUNCIL. C. AMCA AIR MOVEMENT AND CONTROL ASSOCIATION. D. ANSI AMERICAN NATIONAL STANDARDS INSTITUTE. E. API AMERICAN PIPE INSTITUTE. F. ARI AMERICAN REFRIGERATION INSTITUTE. G. ASHRAE AMERICAN SOCIETY OF HEATING REFRIGERATION AND AIR CONDITIONING ENGINEERS. H. ASME AMERICAN SOCIETY OF MECHANICAL ENGINEERS. I. ASTM AMERICAN STANDARDS FOR TESTING MATERIALS. J. AWS AMERICAN WELDING SOCIETY. K FM FACTORY MUTUAL. L. NBS NATIONAL BUREAU OF STANDARDS. M. NEC NATIONAL ELECTRIC CODE. N. NEMA NATIONAL ELECTRICAL MANUFACTURERS ASSOCIATION. 0. NFPA NATIONAL FIRE PROTECTION ASSOCIATION. P. OSHA OCCUPATIONAL SAFETY AND HEALTH ACT UNITED STATES DEPARTMENT OF LABOR STANDARDS. Q FBC FLORIDA BUILDING CODE. R SMACNA SHEET METAL AND /AIR CONDITIONING CONTRACTORS NATIONAL ASSOCIATION. S. SMC STANDARD MECHANICAL CODE. T. UL UNDERWRITERS LABORATORIES INC. U. FMC - FLORIDA MECHANICAL CODE. DRAWINGS: ARE DIAGRAMMATIC AND INDICATE GENERAL ARRANGEMENT OF SYSTEM AND WORK INCLUDED IN CONTRACT. FOLLOW DRAWINGS IN INSTALLING NEW AIR CONDITIONING SYSTEMi CHECK DRAWINGS OF ALL TRADES TO VERIFY SPACES IN WHICH WORK WILL BE INSTALLED, IF SPACE CONDITIONS ARE INADEQUATE, OR DO NOT AGREE WITH THE CONDITIONS SHOWN ON THE DRAWINGS NOTIFY THE PROJECT ARCHITECT/ENGINEER PRIOR TO PROCEEDING WITH THE WORK DO NO WORK UNTIL ALL CONDITIONS ARE* CORRECTED. BEGINNING OF INSTALLATION IS AN ACCEPTANCE OF THE EXISTING CONDITIONS. PERFORMANCE: CONTRACTOR SHALL VERIFY EXACT DIMENSIONS AT JOB SITE PRIOR TO FABRICATION OF ACCESSORIES AND PURCHASE OF EQUIPMENT. CONTRACTOR SHALL VERIFY OPERATING CONDITION AND VOLTAGES PRIOR TO ORDERING EQUIPMENT, AND COMMENCING WORK NOTIFY THE OWNER OF ANY DEFICIENCY THAT COULD POSSIBLY DELAY OR AFFECT THE COMPLETION OF THE WORK SUBSTITUTIONS: EQUIPMENT SPECIFIED SHALL BE ADHERED TO. HOWEVER, OWNER HAS THE FINAL DECISION ON THE TYPE AND QUALITY OF EQUIPMENT TO BE SUPPLIED. CONTRACTOR SHALL OBTAIN WRITTEN PERMISSION FROM THE OWNER PRIOR TO PURCHASING SUBSTITUTE EQUIPMENT. CONTRACTOR SHALL BEAR THE COST OF ALL ENGINEERING WORK RELATED TO SUBSTITUTED EQUIPMENT. WORK INCLUDED: THE EXTENT OF THE AIR CONDITIONING WORK INCLUDES, BUT IS NOT LIMITED TO THE FOLLOWING: L THE INSTALLATION OF ALL SPECIFIED AIR CONDITIONING EQUIPMENT SUCH AS, BUT NOT LIMITED TO: AIR CONDITIONING UNITS, PIPING, VALVES, INSULATION, THERMOSTATS, SMOKE DETECTORS, DUCTWORK, DAMPERS, DIFFUSERS, ETC. TO WERE SHOWN ON DRAWINGS, AS WELL AS THE INSTALLATION OF ALL EQUIPMENT NOT NORMALLY SHOWN ON DRAWINGS BUT NECESSARY FOR THE SYSTEM TO OPERATE AS INTENDED. 2. THE INSTALLATION OF NEW EXHAUST FANS, WITH RELATED DUCTWORK, GRILLES, ETC. AS SHOWN ON DRAWINGS AND /OR HEREIN SPECIFIED. 3. THE FABRICATION AND INSTALLATION OF ALL PIPE ACCESSORIES SUCH AS PIPE SUPPORTS, PIPE SLEEVES, DRAIN LEGS, DRAIN PANS, ETC. WHETHER SHOWN ON DRAWINGS OR NOT, AS WELL AS THE FABRICATION AND INSTALLATION OF ALL DUCTWORK ACCESSORIES SUCH AS VOLUME EXTRACTORS, TURNING VANES, DAMPERS, ACCESS PANELS ETC. AS SHOWN ON DRAWINGS OR AS NECESSARY FOR A COMPLETE AIR DISTRIBUTION SYSTEM TO OPERATE AS INTENDED. 4. THE EXECUTION OF AN AIR BALANCE FOR THE NEW SYSTEM. 5. ALL CUTTING AND PATCHING ASSOCIATED WITH THIS INSTALLATION. 6. ALL PERMITS AND FEES FOR PERMITS. HVAC SPECIFICATIONS AIR DISTRIBUTION DEVICES: PROVIDE ALL AIR DISTRIBUTION DEVICES CONSTRUCTED FROM ANODIZED ALUIMNUM MANUFACTURED BY A SINGLE MANUFACTURER; "AMCA" AND "ADC" RATED OF SIXES SHOWN ON DRAWINGS WITH BORDERS AND MOUNTING FRAMES SUITABLE FOR THE LOCATION WHERE AIR DISTRIBUTION PRODUCTS ARE TO BE INSTALLED. PROVIDE AND INSTALL AIR DISTRIBUTION PRODUCTS AS SCHEDULED. DUCTWORK, FIBERGLASS DUCTWORK MATERIAL: ONE INCH THICK GLASS FIBER DUCTBOARD FABRICATED FROM NON - CORROSIVE, NON - HYGROSCOPIC, PERMANENTLY ODORLESS, MICROBACTERIAL- GROWTH INHIBITING, RESILIENT, LONG STAPLE, FABRIC GRADE GLASS FIBERS, FACTORY PREFORMED INTO SEMI -RIGID OR RIGID BOARD WITH A FLEXURAL RIGIDITY RATING OF 800EI PER ASTM TEST NUMBER 0- 1031 -64 WHERE NEITHER WIDTH NOR DEPTH OF DUCT EXCEEDS 48 INCH. AND WITH A FLEXURAL RIGIDITY RATING OF 1400EI PER ASTM TEST NUMBER D- 1031 -64 WHERE WIDTH OR DEPTH EQUALS OR EXCEEDS 48 INCH, FIBERGLASS BOARD SHALL BE NON - EROSIVE WHEN CONVEYING AIR AT VELOCITIES TO 2000 FPM, AND SHALL BE COVERED WITH A FIRE RETARDANT, MOISTURE SEALING, FACTORY- APPLIED JACKET MADE OF REFLECTIVE, ALUMINUM FOIL KRAFT PAPER OF 2 MIL MINIMUM THICKNESS. MANUFACTURER AND PRODUCT: CERTAINTEED TOUGHTGARD WITH A R =65 AND A MAXIMUM THERMAL CONDUCTIVITY OF 023 AT i5 DEGREE F MEAN TEMPERATURE. CONSTRUCTION: COMPLETED DUCT SYSTEM SHALL BE STABLE AND AIRTIGHT AT 2 INCH WAG. STATIC PRESSURE. INSTALL IN COMPLIANCE WITH THE MANUFACTURER'S RECOMMENDATIONS. PROVIDE CONTINUOUS VAPOR RETARDANT CONTINUITY AND SEAL IN ACCORDANCE WITH SMACNA STANDARDS. MITER ALL LONGITUDINAL CORNERS (EXCEPT SEAMS) WITH JACKET UNDISTURBED. ROUND CROSS - SECTION DUCTS SHALL BE FACTORY MOLDED ONLY. SQUARE AND RECTANGULAR DUCTS SHALL BE SHOP OR FIELD FABRICATED FROM FLAT DUCTBOARD. DUCT REINFORCEMENT: METALLIC DUCT REINFORCEMENT SUPPORT AND DUCT EQUIPMENT SLEEVES SHALL BE GALVANIZED STEEL. FLEXIBLE DUCTWORK: DUCTWORK MANUFACTURED FROM STEEL WIRE HELIX ENCAPSULATED N DOUBLE LAMINATION OF POLYESTER AND COVERED WITH HIGH DENSITY FIBERGLASS INSULATION REINFORCED WITH SCRIM AND VAPOR BARRIER SIMILAR TO OMNIAIR MODEL 1000. FLEXIBLE DUCT SUPPORT AND HANGERS: SUPPORT FLEXIBLE DUCTS AS PER MANUFACTURER'S RECOMMENDED INTERVALS BUT AT LEAST EVERY 5 FT. MAINTAIN A MAXIMUM PERMISSIBLE SAG OF )P PER FT OR LESS. TOTAL SAG SHALL NOT EXCEED 25 IN. OVER THE 5 FT. INTERVAL. SELECT FLEXIBLE DUCT HANGERS FROM TABLE 4 -2 "MINIMUM HANGER SIZES - ROUND DUCT" EXCEPT THAT MIN. SPACING SHALL BE KEPT AT 5' -0 BETWEEN SUPPORTS. HANGER AND SADDLE MATERIAL IN CONTACT WITH FLEXIBLE DUCT SHALL BE AT LEAST W' WIDE SO IT DOES NOT REDUCE THE INTERNAL DIAMERTER OF THE DUCT WHEN THE SUPPORTED SECTION RESTS ON THE HANGER OR SADDLE. SADDLES SHALL COVER AT LEAST ONE -HALF 09 THE CIRCUMFERENCE OF THE OUTSIDE DIAMETER OF THE DUCT AND FIT NEATLY AROUND THE LOWER HALF OF THE OUTER CIRCUMFERENCE. SUSPEND HANGERS FROM BUILDING STRUCTURE AS INDICATED IN THE LATEST SMACNA "HVAC DUCT CONSTRUCTION STANDARDS - METAL AND FLEXIBLE" FIG 4 -2 AND 4 -3 "UPPER ATTACHEMENT DEVICES, TYPICAL" SHEET METAL DUCTWORK: VENTILATION DUCTWORK: RIGID: ALL VENTILATION DUCTWORK SHALL BE MANUFACTURED FROM STANDARD GAUGE GALVANIZED SHEET STEEL IN COMPLIANCE WITH (SMACNA) STANDARDS FOR THE FABRICATION, CONSTRUCTION, AND INSTALLATION OF LOW AND MEDIUM PRESSURE STEEL DUCTWORK ALL DUCT SEAMS AND JOINTS SHALL BE SEALED WITH A NON HARDENING, NON MIGRATING 4' WIDE MASTIC (SIMILAR TO PERMACELL'1 SW) OR EQUIVALENT. SEALING SHALL BE DONE AS RECOMMENDED BY SEALER MANUFACTURER TO OBTAIN A CLASS "A" SEAL. FLEXIBLE: VENTILATIONS DUCTS MADE OF CORRUGATED ALUMINUM WITH WATER TIGHT LOCK SEAMS, DESIGNED FOR LOW PRESSURE VENTING APPLICATION WITH A MAXIMUM WORKING PRESSURE (POSITIVE OR NEGATIVE) OF 4"W3. AND A TEMPERATURE RANGE FROM -100 OF TO 400 OF. SIMILAR TO OMNIAIR MODEL 2000. AIR CONDITIONING DUCTWORK: I. W SHEET METAL ROUND DUCTWORK: PROVIDE UNITED MaLL'S 'UNIRIB" ROUND DUCTWORK AND FITTINGS IN SIZES SHOWN ON DRAWINGS, MACHINED FROM GALVANIZED STRIP -COIL STEEL WITH A STANDING RIB PROJECTING RADIALLY FROM THE OUTSIDE OF THE FORMED ROUND DUCT AND PARALLELING TO THE CONTINUOUS HELICAL LOCKSEAM DUCT PATTERN. JOINT ALL DUCTS AND FITTINGS BY SLIP -JOINNG PIECES TOGET1 ER AS RECOMMENDED BY DUCTWORK MANUFACTURER APPLY INTERNAL DUCT SEALER AS REQUIRED TO PROVIDE CLASS 'A" SEAL. FURNISH ALL DUCT SECTIONS WITHOUT BLEMISHES OR IMPERRf CTIONS, CLEAN INSTALLED DUCTS FROM ALL EXCESS SEALANT AND ALL OTHER FOREIGN MATERIAL WHICH WILL IMPAIR EXTERIOR FINISH APPEARANCE. PAINT ALL DUCT EXPOSED SURFACES AS REQUIRED BY OWNER 2. RECTANGULAR: MANUFACTURED FROM STANDARD GAUGE GALVANIZED SWEET STEEL N COMPLIANCE WITH (SMACNA) STANDARDS FOR THE FABRICATION, CONSTRUCTION, AND INSTALLATION OF LOW AND MEDIUM PRESSURE STEEL DUCTWORK ALL DUCT SEAMS AND JOINTS SHALL BE SEALED WITH A NON HARDENING, NON MIGRATING 4" WIDE MASTIC (SIMILAR TO PERMACELL +1 SW) OR EQUIVALENT. SEALING SHALL BE DONE AS RECOMMENDED BY SEALER MARFACTURER TO OBTAIN A CLASS "A' SEAL. DUCTWORK INSULATION: PROVIDE ALL INSULATION MATERIALS WITH A FLAME SPREAD CLASSIFICATION OF 25 FT -MN OR LESS, SMOKE DEVELOPED CLASSIFICATION OF 50 FT -MN OR LESS, AND FUEL CONTRIBUTED CLASSIFICATION OF 25 FT -MIN OR LESS AS TESTED BY NFPA -255 - "METHOD OF TESTING THE SURFACE BURNING CHARACTERISTICS OF BUILDING MATERIALS." INSULATE ALL AIR CONDITIONING DUCTWORK AND INDICATED VENTILATION DUCTWORK WITH ONE OF THE FOLLOWING INSULATION TYPES: I: FLEXIBLE EXTERIOR INSULATION: I' THICK, 3 LB /CF DENSITY FEDERAL SPEC. HH -1 -558, FORM B, TYPE I, CLASS %. DUCT REINFORCEMENT: FABRICATED IN ACCORDANCE WITH "SMACNA' DUCT CONSTRUCTION STANDARDS. ALL METALLIC DUCT REINFORCEMENT SUPPORT AND DUCT EQUIPMENT SLEEVES SHALL BE MADE OF HEAVY GAGE GALVANIZED STEEL. FLEXIBLE DUCT CONNECTIONS: AIR TRACK TWIST LOCK CONNECTIONS MANUFACTURED FROM NAVY GAUGE GALVANIZED STEEL, FACTORY ASSEMBLED WITH ADJUSTABLE DAMPER MOUNTED ON BEARINGS AND POSITIVE LOCKING HARDWARE. HVAC SPECIFICATIONS AIR CONDITIONING UNITS: FACTORY SELF CONTAINED AIR COOLED A/C UNIT: L SELF CONTAINED, FACTORY PREPACKAGED AND ASSEMBLED SUITABLE FOR OUTDOOR INSTALLATION. AC UNITS TO BE CONSTRUCTED FROM HEAVY GAUGE GALVANIZED STEEL WITH RUST RESISTANT EPDXY FINISH, EASILY REMOVABLE ACCESS PANELS, OUTSIDE AIR INTAKE WITH VOLUME DAMPER AND ALUMINUM BIRD SCREEN, ONE (1) INCH THICK NEOPRENE COATED FIBERGLASS INTERNAL INSULATION THROUGH OUT ENTIRE CABINET. AC UNITS TO BE FACTORY ASSEMBLED WITH THE FOLLOWING COMPONENTS: A. COMPRESSORS) TO BE HERMETICALLY SEALED OF THE 1150 RPM TYPE, RESILIENTLY MOUNTED WITH POSITIVE LUBRICATION, CRANKCASE HEATER, MOTOR OVERLOAD PROTECTION, SERVICE VALVES, FILTER DRYER, WITH SUCTION AND DISCHARGE SHUT OFF VALVES. 5. CONDENSER COIL: CONSTRUCTED OF COOPER TUBING WITH ALUMINUM FINS. C. CONDENSER FAN: VERTICAL DISCHARGE, DIRECT DRIVE, AXIAL TYPE, RESILIENTLY MOUNTED WITH ALUMINUM GUARD AND TOTALLY ENCLOSED, PERMANENTLY LUBRICATED BALL BEARING MOTOR WITH BUILT IN CURRENT AND OVERLOAD PROTECTION. D. EVAPORATOR COIL: EVENLY SPACED ALUMINUM FINS MECHANICALLY BONDED TO COPPER TUBES (DESIGNED FOR 250 PSIW WITH A 16 GAGE GALVANIZED STEEL INSULATED INTERNAL DRAIN PAN WITH DRAIN CONNECTION. E. EVAPORATOR FAN: SINGLE INLET TYPE WITH STATICALLY AND DYNAMICALLY BALANCED CENTRIFUGAL WHEEL WITH FORWARD CURVED SINGLE WIDTH BLADES, DIRECT DRIVEN, RESILIENTLY MOUNTED ON SLEEVE BEARINGS. F. AIR FILTER- TWO (2) INCH THICK FIBERGLASS THROWAWAY OR PERMANENT WASHABLE TYPE, FILTER TO BE LOCATED IN FACTORY FABRICATED FILTER RACK UPSTREAM OF EVAPORATOR COIL. FACTORY PREPACKAGED SPLIT AC UNITS: SHALL CONSIST OF THE FOLLOWING: L CONDENSING UNITS: FACTORY PREPACKAGED AND ASSEMBLED SUITABLE FOR OUTDOOR INSTALLATION CONSTRUCTED FROM HEAVY GAUGE GALVANIZED STEEL WITH RUST RESISTANT EPDXY FINISH. AC UNITS TO BE FACTORY ASSEMBLED WITH THE FOLLOWING COMPONENTS: A. COMPRESSOR TO BE HERMETICALLY SEALED OF THE 1150 RPM TYPE, RESILIENTLY MOUNTED WITH POSITIVE LUBRICATION, CRANKCASE HEATER, MOTOR OVERLOAD PROTECTION, SERVICE VALVES, FILTER DRYER, WITH SUCTION AND DISCHARGE SHUT OFF- VALVES. B. CONDENSER COIL: CONSTRUCTED OF COOPER TUBING WITH ALUMINUM FINS. C. CONDENSER FAN: VERTICAL DISCHARGE, DIRECT DRIVE, AXIAL TYPE, RESILIENTLY MOUNTED WITH ALUMINUM GUARD AND TOTALLY ENCLOSED, PERMANENTLY LUBRICATED BALL BEARING MOTOR WITH BUILT IN CURRENT AND OVERLOAD PROTECTION. 2. AIR HANDLING UNIT: SELF CONTAINED, DRAW THROUGH, FACTORY ASSEMBLED, PACKAGED AND PREWIRED AIR HANDLING UNITS, UL LISTED, ARI AND AMCA RATED, OF CAPACITIES AND SIXES SHOWN ON DRAWINGS AND /OR HEREIN SPECIFIED AS FOLLOWS: A. CABINET: HEAVY GAGE GALVANIZED STEEL WITH EXPOSED CORNERS AND EDGES ROUNDED, EASILY REMOVABLE PANELS, WITH INTERNAL ONE (1) IN THICK NEOPRENE COATED FIBERGLASS INSULATION. FINISHED WITH STANDARD FACTORY BAKED ENAMEL FINISH. B. EVAPORATOR COIL: EVENLY SPACED ALUMINUM FINS MECHANICALLY BONDED TO COPPER TUBES (DESIGNED FOR 150 PSIG) WITH A 16 GAGE GALVANIZED STEEL INSULATED INTERNAL DRAIN PAN WITH DRAIN CONNECTION. C. EVAPORATOR FAN: SINGLE INLET TYPE WITH STATICALLY AND DYNAMICALLY BALANCED CENTRIFUGAL WHEEL WITH FORWARD CURVED SINGLE WIDTH BLADES, DIRECT DRIVEN, RESILIENTLY MOUNTED ON SLEEVE BEARINGS. D. AIR FILTER- ONE (1) INCH THICK FIBERGLASS THROWAWAY OR PERMANENT WASHABLE TYPE, FILTER TO BE LOCATED IN FACTORY FABRICATED FILTER RACK UPSTREAM OF EVAPORATOR COIL. PROVIDE ONE (1) SET OF REPLACEMENT FILTERS TO OWNER UPON SUBSTANTIAL COMPLETION. 3. REFRIGERANT PIPING: SEAMLESS, HARD DRAWN, TYPE "L" COPPER TUBING OF SIZES RECOMMENDED BY UNIT'S MANUFACTURER FOR THE APPLICATION SHOWN ON DRAWINGS. REFRIGERANT SUCTION LINES SHALL BE INSULATED USING P THICK FLEXIBLE UNICELLULAR PIPING UNSPLIT INSULATION. ALL INSULATION SHALL COMPLY WITH NFPA W -A. CONTROL PRODUCTS: 1. PROGRAMMABLE ELECTRONIC THERMOSTATS: MANUFACTURED BY THE AC UNIT MANUFACTURER, THERMOSTAT SHALL HAVE THE FOLLOWING FEATURES: 1-DAY PROGRAMMING CAPABILITY, DIGITAL DISPLAY, INSTANT OVERRIDE, AUTOMATIC ADJUSTMENT OF TEMPERATURES UP TO 4 TIMES A DAY, LCD READOUT IN FAHRENHEIT OR CELSIUS, 24 HOUR CLOCK, TAMPER RESISTANT, 100 % SOLID STATE. 2. SMOKE DETECTORS: PROVIDE AN IONIZATION SMOKE DETECTOR SUITABLE FOR AIR DUCT INSTALLATION TO EACH AIR CONDITIONING UNIT. SMOKE DETECTOR SHALL BE AS FOLLOWS: LINE VOLTAGE (120N60) IONIZATION SMOKE DETECTORS OF THE MULTIPLE SAMPLE ELEMENTS TYPE, WITH A "POWER ON" INDICATING LIGHT. INSTALL SAMPLING ELEMENTS IN BOTH MAN SUPPLY AND MAIN RETURN AIR DUCTS. ELECTRICALLY CONNECT THE IONIZATION SMOKE DETECTORS TO STOP ALL AIR CONDITIONING UNITS OPERATION IF PARTICLES OF SMOKE ARE DETECTED IN THE AIR STREAM. SEQUENCE OF CONTROL: 1. EQUIPMENT START SEQUENCE: THROUGH THE PROGRAMMABLE THERMOSTAT, UPON A CALL FOR COOLING, THE FOLLOWING EQUIPMENT SHALL START IN SEQUENCE: A. AIR COOLED CONDENSING UNIT B. EVAPORATOR FAN GUARANTEE t WARRANTY: 1. FABRICATE ALL DUCTWORK AND PROVIDE AND INSTALL ALL EQUIPMENT IN COMPLIANCE WITH THE CODES HAVING JURISDICTION, AS ENFORCED BY THE LOCAL BUILDING OFFICIALS. 2. PROVIDE WRITTEN GUARANTEE STATING THAT THE CONTRACTOR, WILL REPLACE OR REPAIR FREE OF CHARGE, ANY EQUIPMENT OR MATERIAL WITCH FAILS DURING A ONE YEAR PERIOD FROM DATE OF SUBSTANTIAL COMPLETION. ENGINEERING ASSURANCE: 1. THE EQUIPMENT HAS BEEN SELECTED, AND THE HVAC SYSTEM HAS BEEN DESIGNED, TO COMPLY WITH NATIONAL FIRE PROTECTION ASSOCIATION AND WITH THE FLORIDA BUILDING CODE. dez architecture, inc. 5001 sw 74th court suite 105 miami, florida 33155 phone: (305) 663 -1970 fax: (305) 663 -2312 e —mail: peter®diezarchitecture.com pedro diez, ra president ar 0008996 ENGINEERING CONSULTANT PRV ENGINEERING, INC. Mechanical - Electrical - Plumbing - Fire Protection 0452 NW n CL, Mliaft. Fl. 3: 1 Ph: 305.859.9821- Fx: 305.e5e.5M Board of Profesabnal Enoin ufhorizabon No.: 00009835 Mechanical Engineer P. RobeiRl{pldes, PE PE 31328 Electrical Engin V ri , PE PE 32078 PROJEgI' No. i D "J" `/ - • L� // 4 ti 14 : r, �ffflQl,Hf�S�``� 6141 Sunset 6141 SUNSET DRIVE SOUTH MIAMI, FLORIDA PROJECT No. 03 -115 REVISIONS HVAC SPECIFICATIONS SCALE: 3/16" = V-0* DATE: 11-14-05 M -1.01 6