05-1856-011PLUMBING SYMBOL LEGEND
AFF
- ABOVE FINISH FLOOR
CD
- CONDENSATE DRAIN
CD
- CONDENSATE DRAM
REMARKS
- DOMESTIC COLD WATER
CO
- CLEANOUT
3/g"
- SANITARY
CONT
- CONTINUATION
LAVATORY
- SANITARY VENT
CW
- DOMESTIC COLD WATER
WALL HUNG
- STOR1
DN
- DOWN
3411
- DOMESTIC HOT WATER
DWG
- DRAWING
--�—
- HOSE BIBB
EXIST
- EXISTING:
WALL HUNG
- CLEAN OUT PLUG
FD
- FLOOR DRAIN
3 '6"
- OAS
HB
- HOSE BIBS
O CO
- FLOOR CLEAN OUT
IE
- INVERT ELEVATION
ANTI -SCALD MIXING VALVE
5RSK
BREAK RM. SINK
V/2 11
@C
- FLOOR DRAM
KW
- KILOWATT
JANITOR SINK
11 /2"
LBS
- POUNDS
6)
- BALL VALVE
NIC
- NOT IN CONTRACT
- BALANCWCs VALVE
NTS
- NOT TO SCALE
NOTES:_
1. SEE ARCHITECTURAL- DRAWINGS FOR EXACT MOUNTING LOCATION OF ALL WITS.
- CHECK VALVE(SWING)
PRV
- PRESSURE REDUCING VALVE
'
- PRESSURE REDUCING VALVE
PSI
- POUNDS PER SQUARE INCH
4
- SOLENOID OPERATED VALVE
FRO
- ROOF DRAIN
- REDUCED PRESSURE BACKFLOW
RPBP
- REDUCED PRESSURE BACKFLOW PREVENiER
PREVENTER WITH STRAINER
SAN
- SANITARY
- RELIEF OR SAFETY VALVE
SD
- STORM DRAM i
0
- VALVE ON RISER
SF
- SQUARE FEET
I
- CAP
ST
- STORM
- ELBOW, TURNED UP
V
-VENT
VTR
- VENT THRU ROOF
C
- ELBOW, TURNED DOWN
- TEE
- TEE, TURNED UP
- TEE, TURNED DOWN
SHEET INDEX
P -001 PLUMBING LEGEND, GENERAL NOTES,
SHEET INDEX AND SCHEDULES
P -101 PLUMBING THIRD FLOOR PLAN
P -102 PLUMBING FOURTH FLOOR PLAN
P -103 PLUMBING FIFTH FLOOR PLAN
P -201
SANITARY t VENT RISER DIAGRAM A
P-202
SANITARY a VENT RISER DIAGRAM B
P -203
DOMESTIC WATER RISER DIAGRAM
NQM:
1. ALL PIPING BETWEEN WATER HEATER AND FAUCET
SHALL BE MINIMUM Y.
2. ALL SUPPLY PIPING TO TWH SHALL BE 344 MIN.
3. COORDINATE WITH ARCHITECTURAL DRIM FOR
EXACT LOCATION OF TANKLESS WATER HEATER
PRIOR TO ROUGH -IN
COUNTERTOP
USE TWH -1 TO FEED A SINGLE MLV AND
TWH -2 FOR 2 OR 3 MLV ON S,
WATER HEATER WITH
FLOW CONTROL VALVE
FAUCET
PLUMBING SPECIFICATIONS
1. FURNISH AND INSTALL ALL MATERIALS AND EQUIPMENT SHOWN IN THESE DRAWINGS
INCLUDING THOSE ITEMS NOT NORMALLY SHOWN BUT NECESSARY FOR A COMPLETE
PLUMBING SYSTEM TO PERFORM AS INTENDED. FURNISH ALL LABOR TO INSTALL ALL
EQUIPMENT AND PIPING IN ACCORDANCE WITH THE LOCAL PLUMBING AND BUILDING
CODES AS ENFORCED BY THE AUTHORITIES HAVING JURISDICTION.
2. COORDINATE WORK WITH ALL TRADES AND NOTIFY A/E OF RECORD OF ANY
POSSIBLE CONFLICTS PRIOR TO COMMENCING WORK, DO NO WORK UNTIL ALL ISSUES
ARE RESOLVED. BEGINNING INSTALLATION IMPLIES AN ACCEPTANCE OF JOB
CONDITIONS.
3. VERIFY ALL POINTS OF CONNECTION WITH UTILITIES PRIOR TO START INSTALLATION.
4. VERIFY EXACT LOCATION OF ALL EQUIPMENT WITH ARCHITECTURAL DRAWINGS AND
COORDINATE WITH EQUIPMENT'S MANUFACTURER SHOP DRAWINGS PRIOR TO
ROUGH -IN. DO NOT SCALE PLUMBING DRAWINGS.
5. PROVIDE ALL EXCAVATION, BACKFILL AND COMPACTION REQUIRED TO COMPLETE
INSTALLATION AS INTENDED.
6. PROVIDE COMPLETE ACCESS t0 ALL SYSTEM. LOCATE GLEAN -OUTS ON WALLS AND
OR FLOORS AND PROVIDE ACCESS PANELS TO REACH WATER DISTRIBUTION
SYSTEM'S VALVES.
1. PROVIDE FLASHING AND PITCH PANS AS REQUIRED TO MAKE ALL ROOF
PENETRATIONS WATER TIGHT.
8. BUILDING DRAINAGE SYSTEM DESIGN BASED ON V8" FT. MINIMUM FALL.
S. PROVIDE P MINIMUM WATER PIPE CAPPED AT EVERY ELECTRICAL ROOM AND
METER ROOM FOR GROUND.
10. ALL VALVES UNDERGROUND TO BE INSTALLED IN PRECAST CONCRETE BOXES,
BROOKS OR EQUAL.
11. ALL MATERIALS AND EQUIPMENT SHALL BE NEW AND AS FOLLOWS:
A SANITARY WASTE AND VENT PIPES AND FITTINGS SHALL BE PVC OR DWV
(ASTM -D- 2662).
B AC CONDENSATE DRAIN SHALL BE SCHEDULE 40 P.V.C.
C HOT AND COOL WATER LINES SHALL BE COPPER (ASTM -5-88) TYPE "L"
ABOVE GROUND t TYPE "K" UNDERGROUND.
D PROVIDE DIELECTRIC COUPLINGS AS REQUIRED FOR CONNECTION TO
DIFFERENT MATERIALS SHUTOFF VALVES AT FIXTURES AND EQUIPMENT
REQUIRING WATER SUPPLY.
E INSULATE ALL HOT WATER LINES WITH }2" FIBERSLASS WITH SELF SEALING
UNIVERSAL JACKET.
F PLUMBING FIXTURES- AMERICAN STANDARD, KOHLER, CRANE OR EQUAL.
G FLOOR AND ROOF DRAINS, IF USED, JOSAN OR EQUAL, FLOOR DRAINS SHALL
BE RESEALED.
H ELECTRICAL WATER HEATERS- GLAS51LINED, 5 YEARS GUARANTEED A.O., SMITH
OR EQUAL.
I VALVES - 125 PSI N15CO SCOTT OR EQUAL.
J HOSE 5I555 CHICAGO 952, OR EQUAL.
K ALL EXPOSED PIPING AT FIXTURES AND EQUIPMENT SHALL BE CHROME
PLATED ESCUTCHEON'S AS REQUIRED.
12. PERFORM THE FOLLOWING TESTS:
A WATER PIPING SHALL BE SUBJECTED TO HYDROSTATIC PRESSURE TEST OF 100
PSIG. FOR A PERIOD OF TIME SUFFICIENT TO EXAMINE ENTIRIEE SYSTEM BUT NOT
LESS THAN ONE HOUR
B DRAINAGE PIPING INSTALLATION OF ANY DRAINS, THE ENDS OF SYSTEM SHALL
BE CAPPED AND ALL LINES FILLED WITH WATER TO HIGHEST POINT AND
ALLOWED TO STAND UNTIL INSPECTION 18 MADE AND WATER LEVEL REMAINS
CONSTANT.
C CORRECT ALL DEFECTS PRIOR TO PLACING SYSTEM IN OPERATION.
13. STERILIZE ALL WATER LINES WITH MIXTURE OF CHLORINATED LIME t0 EACH 1000
GALLONS OF WATER (50 PPM OF AVAILABLE CHLORINE), RETAIN MIXTURE IN PIPES
24 HOURS AND FLUSH THOROUGHLY WITH POTABLE WATER BEFORE PLACING IN
SERVICE.
14. COMPLETE SYSTEM, FIXTURES AND EQUIPMENT SHALL BE GIVEN AN IN- SERVICE TEST
AFTER COMPLETION OF THE INSTALLATION.
15. FURNISH A WRITTEN GUARANTEE THAT ALL PLUMBING WORK SHALL BE FREE FROM
DEFECTS OF MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM
DATE OF FINAL ACCEPTANCE. REPLACE AND REPAIR FREE OF CHARGE ANY AND
ALL EQUIPMENT AND INSTALLATION WHICH BECOMES DEFECTIVES DURING THAT
PERIOD.
PERFORATED
VENT CAP
TYPICAL MEDICAL
SINK (MLV).
Z
C.O. PLUG A/C UNIT
lV„
— 3/4110 DRAIN PAN
SLOPE Y8° UNION CW SUPPLY TO FIXTURE
3"
3�4n0
SUPPLY STOP CHROME PLATED WAL
ESCUTCHEON
CONDENSATE TRAP DETAIL SUPPLY STOP
FLOW CONTROL NOT TO SCALE
UNION
TANKLESS ELECTRIC WATER HEATER
NTS
I
PLUMBING FIXTURE CONECTION SCHEDULE
MARKS
DESCRIPTION
WASTE
C.W.
H.W.
REMARKS
WC
WATER CLOSET
3"
3/g"
-
WALL MOUNTED, FLUSH TANK
LAV
LAVATORY
11/4"
'�"
-
WALL HUNG
1-1CU1C
WATER CLOSET
HANDICAPED USE
3"
3411
_
WALL MOUNTED, FLUSH TANK
HC LAV
LAVATORY
HANDICAPED USE
I1/4"
3 /8"
_
WALL HUNG
MLV
MEDICAL
LAVATORY
11/411
3 '6"
3/8"
COUNTERTOP
SH
SHOWER
2"
J6"
)5"
ANTI -SCALD MIXING VALVE
5RSK
BREAK RM. SINK
V/2 11
VI
V"
COUNTERTOP
JSK
JANITOR SINK
11 /2"
VI
VI
SEE ARCH DWGS.
TANKLESS WATER HEATER SCHEDULE
MARK
* P.D.I. SIZE
CONN. SIZE
INPUT
TEMP
WATER
HA -2
5 (12 -32 F.U.)
3/4"
HA -3
C (33400 F.U.)
UNIT NO
MODEL
MAX/MIN
RISE
FLOW
VOLT
AMPS
CIRC.
EFF
WEIGHT
TWH -1
EEMAXSP4208
56' F
05 GPM
208 -1
19.1 EA.
1
999e
30 LBS
TWH -2
EEMAX SPW0&
51' F
1 GPM
208 -1
40 EA.
1
99go
30 LBS
TWH -3
� WATER
HEA 220
60• F
3.0 GPM
240 -1
93.6 EA.
I
985 90
120 L58
NOTES:_
1. SEE ARCHITECTURAL- DRAWINGS FOR EXACT MOUNTING LOCATION OF ALL WITS.
2. PROVIDE AX' C414 WATER LINE INSTALL A FLOW STOP ON CW SUPPLY LINE.
3. PROVIDE AN EWH -I WITH A 05 GPM AERATOR ON ALL EXAM ROOM, LABORATORY SINKS AND LAVATORIES.
4. PROVIDE AN EWH -2 WITH A 1.0 GPM AERATOR ON ALL BREAK ROOM AND KITCHEN SINKS.
5. PROVIDE AN EWH -3 FOR JANITOR SINKS AND AS INDICATED ON THE DRAWINGS.
THE HANDLE OF THE FLUSH LEVER
SHALL FACE THE WIDE SIDE OF
THE STALL(NO EXCEPTIONSU
WATER CLOSET
ACCESSIBLE
NTS
WATER HAMMER
ARRESTER SCHEDULE
MARK
* P.D.I. SIZE
CONN. SIZE
HA -1
A (1 -II RU-)
1/2"
HA -2
5 (12 -32 F.U.)
3/4"
HA -3
C (33400 F.U.)
I"
• PLUMBING AND DRAINAGE INSTITUTE STANDARD WH -201
diez
architecture,
inc.
5001 sw 74th
court suite 105
miami, florida
33155
phone: (305)
663 -1970
fax:- (305)
663 -2312
e —mail: peter®diezarchitecture.com
pedro diez, ra
president or
0008996
ENGINEERING CONSULTANT
PRV ENGINEERING, INC.
Mecha6hl - Owtricd - Plumbing y-,Fxe Protection
east NW 77 CL, Mmn,. FL,'016e - Pn 3os 859 8827. FS' I 8:8.5956
Board of Professional ineem AulhoAzation
Mechanical Eng der`` .P. Robert Aitlpsr�PE P1325
Electrical E r :' �Rigdberto nprediPE 76
PROJWp:.$ �_'DQSbg :
ri
b- o ff
CO
PE #: 31326 'fi
6141 Sunset
6141 SUNSET DRIVE
SOUTH MIAMI. FLORIDA
PROJECT No. 03 -115
REVISIONS
i
SCHEDULES
DETAILS AND
LEGEND
SCALE: AS NOTED
DATE: Nov. 14. 2005
■
3