05-1856-000
Designo odnh.g Lobd- Wm* unary; ; : . go IVPkU engineeAng, tnc. "" ' ' • 6141 SuVjgt • .: 6444 Sunfet ; S�tsfena - A�-41 • Zone - Zone - 009 ..... ... .... Latent Total CGItLocatfon - Z092.• � ;...' . • Btu/h Coil Peak Calculation Time: July, hour 21 of Total Ambient DBMB/HR: 84 / 75 / 114 0 COOLING COIL LOAD INFORMATION Load Component Sensible Latent Total Percent Btu/h Btu/h Btu/h of Total Solar Gain 0 0 0.0% Glass Transmission 0 0 0.0% Wag Transmission 1,851 1,851 5.9% Roof Transmission 0 0 0.0% Floor Transmission 0 0 0.0% Partition Transmission 0 0 0.0% Net Calling Load 0 0 0.0% Lighting 11,583 11,583 37.2% People 4,770 5,286 10,056 32.3% Misc. Equipment Loads 6,172 0 6,172 19.8% Cooling Infiltration 0 0 0 0.0% Sub -Total - 24,376 5,286 29,661 95.1% Ventilation Load -3,051 3,899 847 2.7% Exhaust Heat 103 0 103 0.3% Supply Fen Load 0 0 0.0% Return Fan Load 0 0 0.0% Net Duct Heat Pickup 0 0 0.0% Wag Load to Plenum 565 565 1.8% Roof Load to Plenum 0 0 0.0% Lighting Load to Plenum 0 0 0.0% Misc. Equip. Load to Plenum 0 0 0 0.0% Glass Transmission to Plenui 0 0 0.0% Glass Solar to Plenum 0 0 0.0% Over/Under Sizing 0 0 0.0% Terminal Bypass 0 0 0 0.0% Total Coollna Loads 21,992 9,184 31,176 100.0% COOLING COIL SELECTION Coll Selection Parameters Coil Entering Ad (DB / WB) Coil Entering Humidity -Ratio Coil Leaving Air (DB / WB) Coll Leaving Humidity Ratio Coil Sensible Load Coil Total Load Cooling Supply Air Temperature Total Cooling Airflow Resulting Room Relative Humidity General Enalneerina Checks Total Cooling Load Area / Load Total Floor Area Cooling Airflow Airflow / Load Percent Outdoor Air Cooling Load Methodology 73.2/63.1 OF 70.32 ar/Ib 55.0/53.4 OF 58.35 grAb 21.99 MBh 31.18 MBh 56.00 OF 1,084.18 cfm 48.56 % 3.7 ton 458.13 fP/ton 1,670 ft' 0.65 cfmw 297.42 cfrn/ton 22.9 % TETD -TA1 u Project Name: 6141 Sunset I TRACED 700 v4.1 calculated at 08:49 AM on 12/28/2005 Dataset Name: \ \Main -server \engineering \WORK\D05-002 6141 REVISED \DOCUMENTS \CALCULATIONS \6141 Sunset-4th Floor.TRC Alternative - 1 Design Cooling Load report page 1 Design-Gballirt� Lod,u "miary..:, ... . •Pyj9RV,Epb1aeerAg, Inc. •• • COOLING COIL LOAD INFORMATION 6141 Sunset , •. .:61¢1 SunMC •' • . . .. . 0000... Zone - Zone - 010 .... 0.... 0.. 4o41 tocatidh - Zorie • .... . 00000 . ... Coll Peak Calculation Time: December, ho Ambient DB/WB /HR: 78 / 67 / 80 0000 . 0000 • ur 13 COOLING COIL SELECTION Load Component Sensible Latent Total Percent Coil Selection Parameters Btu/h Btu/h Btu/h of Total Solar Gain 26,190 26,190 55.6% Coil Entering Air (DB / WB) 74.4/61.5 °F Glass Transmission 327 327 0.7% Coil Entering Humidity Ratio 60.94 pr/Ib Wag Transmission 327 327 0.7% Coil Leaving Air (OB / WB) 55.0/52.7 °F Roof Transmission 0 0 0.0% Coil Leaving Humidity Ratio 55.79 pr/Ib Floor Transmission 0 0 0.0% Coil Sensible Load 40.35 MBh Partition Transmission 0 0 0.0% Coil Total Load 47.06 MBh Net Calling Load 0 0 0.0% Cooling Supply Air Temperature 56.00 °F Lighting 9,249 9,249 19.7% Total Cooling Airflow 1,869.95 cfm People 3,133 3,700 6,833 14.5% Resulting Room Relative Humidity 43.74 % Misc. Equipment Loads 2,776 0 2,776 5.9 % Cooling Infiltration 0 0 0 0.0% Sub -Tote/ w 42,002 3,700 45,702 97.1% General Enalneerina Checks Ventilation Load -1,962 3,014 1,051 2-2% Total Cooling Load 4.6 ton Exhaust Heat 138 0 138 0.3% Area / Load 264.39 Won Supply Fan Load 0 0 0.0% Total Floor Area 1,215 11P Return Fan Load 0 0 0.0% Cooling Alrflow 1.54 cf nffN Net Dud Heat Pickup 0 0 0.0% Airflow / Load 406.91 dnVton Wag Load to Plenum 172 172 0.4% Percent Outdoor Air 8.6 % Roof Load to Plenum 0 0 0.0% Cooling Load Methodology TETD -TA1 LlphtUtp Load to Plenum 0 0 0.0% Misc. Equip. Load to Plenum 0 0 0 0.0% Glass Transmission to Plenui 0 0 0.0% Glass Solar to Plenum 0 0 0.0% Over/Under StrJnp 0 0 0.0% Terminal Bypass 0 0 0 0.0% Tote/ Coollna Loads 40,350 6,714 47,064 100.0% Project Name: 6141 Sunset TRACE® 700 v4.1 calculated at 08:49 AM on 12/28/2005 Dataset Name: \ 1Main -serverlengineering\WORKXDOS.002 6141 REVISEDIDOCUMENTSICALCULATIONS 16141 Sunset_4th Floor.TRt Alternative - 1 Design Cooling Load report page 2 Design.�oDh1t,1•g Lod urrimrx; • . $ Pf V ifnglnee;ng, Inc. •" ' ' 74.8/60.4 OF 55.67 grfib 55.0/52.1 OF 53.38 grfib 84.16 MBh 89.75 MBh 56.00 OF 3,804.22 cfm 40.70 % 8.0 ton 180.60 W/ton 1,450 fN 2.62 cfmtfP 473.81 cfm/ton 3.4 % TETD -TA1 Project Name: 6141 Sunset ` TRACES 700 v4.1 calculated at 08:49 AM on 12128/2005 Dataset Name: NMaln- server\engineering\WORK\D05 -002 6141 REVISED \DOCUMENTS\CALCULATIONS16141 Sunset_4th Floor.TRt Alternative -1 Design Cooling Load report page 3 6141 Supppt ... . � 61'41 Sunget: • : :. • . • • • : m - 4;344 • • ' .Sys Zone - Zone - 011 .... ..... ... ....• Colt Location - ZoQg • ' • .... ...... . . .... Coil Peak Calculation Time: September, hour 9 Ambient DB/WB/HR: 82 / 74 / 113 COOLING COIL LOAD INFORMATION COOLING COIL SELECTION Load Component Sensible Latent Total Percent Coil Selection Parameters Btu/h Btu/h Bluth of Total Solar Gain 61,585 61,585 68.6% Coll Entering Alr (DB / WB) Glass Transmission 1,611 1,611 1.8 % Coll Entering Humldtty Ratio Well Transmission 883 883 1.0 % Coil Leaving Air, (DB ),WB) Roof Transmission 0 0 0.0% Coll Leavingliumidity', Ratio Floor Transmission 0 0 0.0% 6 Load ` Partition Transmission Net Ceiling Load 0 0 0 0.0% �.. ° - �W�1 o l'LI d Lighting 11,169 0 11,169 0.0% g}§uppyy Temperature ' �. 'total People 2,723 2,774 5,497 12 .-96r ;�� Cooling 6.1?*' %\ , ',� Result] oom RdlaWe,Humidlty Misc. Equipment Loads 7,244 0 7,244 6:1, % Cooling Infiltration 0 0 0 0.0% Sub-Total -:1, 85,215 2,774 87,989 98.0% �- General Engineering Checks Ventilation Load -1,603 2,809 1,206 t 1.3 % - - Total Cooling Load Exhaust Heat 118 0 118 0.1% t -� P.Area / Load Supply Fan Load 0 0 0.0% ` �- -Total Fkxu'A'a~ Return Fan Load 0 0 0.0% .- ys iAl"Ab4+i Net Duct Heat Pickup 0 0 0.0%. .- .��./A1rflow / Load Wall Load to Plenum 433 433 0.6% ,- Percent Outdoor Alr Roof Load to Plenum 0 0 0.0% Cooling Load Methodology Lighting Load to Plenum 0 0 0.0% Misc. Equip. Load to Plenum 0 0 0 0.0% Glass Transmission to Plenui 0 0 0.0% Glass Solar to Plenum 0 0 0.0% Over/Under Sizing 0 0 0.0% Terminal Bypass 0 0 0 0.0% Total Cooling Loads 84,163 5,583 89,746 100.0% 74.8/60.4 OF 55.67 grfib 55.0/52.1 OF 53.38 grfib 84.16 MBh 89.75 MBh 56.00 OF 3,804.22 cfm 40.70 % 8.0 ton 180.60 W/ton 1,450 fN 2.62 cfmtfP 473.81 cfm/ton 3.4 % TETD -TA1 Project Name: 6141 Sunset ` TRACES 700 v4.1 calculated at 08:49 AM on 12128/2005 Dataset Name: NMaln- server\engineering\WORK\D05 -002 6141 REVISED \DOCUMENTS\CALCULATIONS16141 Sunset_4th Floor.TRt Alternative -1 Design Cooling Load report page 3 ir4 -W1 000 00000 . . • .. .. ... 0000 •000• . • • • ... . 0000. '...' • •0•• 0 9...9 • 00• 0000 • 0000 •.•• . • . 0000 • ... • . . 0000 C/ 3TR� T E CG (jR Y , aR /CAI. �. i Desigh- 6-1i13g L(pctSu im)kry; ' . 4 IAUV f-ngineeting,1nc. COOLING COIL LOAD INFORMATION 6141 SujWt • • • • 614;1 $unpt: .$yslem - AHU i. I ' Type - Single Zone .606: ••• •.•• •• • Coil LocatgQ $yetAm. . :.00 . Coll Peak Calculation Time: June, hour 18 Ambient DBNVB/HR: 86 / 75 / 115 COOLING COIL SELECTION Load Component Sensible Latent Total Percent Coil Selection Parameters Btu/h Stu/h Btu/h of Total Solar Gain 13,455 13,455 16.1% Coll Entering Air (DB / MIS) 72.3/62.8 OF Glass Transmission 3,382 3,382 4.1% Coll Entering Humidity Ratio 70.46 grAb Wall Transmission 2,349 2,349 2.8% Coil Leaving Air (DB / WB) 55.0/53.4 OF Root Transmission 0 0 0.0% Coll Leaving Humidity Ratio 58.41 grAb Floor Transmission 0 0 0.0% Coil Sensible Load 57.85 MBh Partition Transmission 0 0 0.0% Coll Total Load 83.40 MBh Net Ceiling Load 0 0 0.0% Cooling Supply Air Temperature 55.00 OF Lighting 17,587 17,587 21.1 % Total Cooling Airflow 2,998.31 elm People 13,162 14,991 28,154 33.8% Resulting Room Relative Humidity 44.46 % Misc. Equipment Loads 14,086 0 14,086 16.9% Cooling Infiltration 0 0 0 0.0% Sub -Total o2p 64,022 14,991 79,014 94.7% General Enaineerina Checks Ventilation Load -7,514 10,565 3,051 3.7% Total Cooling Load 9.8 ton Exhaust Heat 437 0 437 0.5% Area / Load 275.57 fP /ton Supply Fan Load 0 0 0.0% Total Floor Area 2,697 ft' Return Fan Load 0 0 0.0% Cooling Airflow 1.11 chum Net Duct Heat Pickup 0 0 0.0% Airflow / Load 306.36 cfrn/ton Wail Load to Plenum 902 902 1.1 % Percent Outdoor Air 22.5 % Roof Load to Plenum 0 0 0.0% Cooling Load Methodology TETD -TAI Lighting Load to Plenum 0 0 0.0% Misc. Equip. Load to Plenum 0 0 0 0.0% Glass Transmission to Plenui 0 0 0.0% Glass Solar to Plenum 0 0 0.0% Over/Under Sizing 0 0 0.0% Terminal Bypass 0 0 0 0.0% Total Cooling toads 57,848 25,556 83,404 100.0% Project Name: 6141 Sunset TRACE® 700 v4.1 calculated at 10:27 PM on 11/072005 Dataset Name: \\ Main- server\engineedrig \WORK\D05-002 6141 REVISED \DOCUMENTS \CALCULATIONS \6141 Sunset_REVISED.TF Alternative - 1 Design Cooling Load report page 1 DesigffC*.61feg LaadSuAnrn�ty; '.$y FfkV•Engine&ng,lnc' 6141 Stmt . • • • •: 6fi1 puroat� ••• • : .�ys�ern - AMU -32 ' Zone - Zone - 006 of Total ..... 53,544 Coo LocatiQp ;Zed.' :...' • 56.1% Glass Transmission Coll Peak Calction Time: December, hour 13 ula Ambient DB/WB /HR: 78 / 67 / 80 948 COOLING COIL LOAD INFORMATION Load Component Sensible Latent Total Percent Btu/h Btu/h Btu/h of Total Solar Gain 53,544 53,544 56.1% Glass Transmission 948 948 1.0% Wall Transmission 2,426 2,426 2.5% Roof Transmission 0 0 0.0% Floor Transmission 0 0 0.0% Partition Transmission 0 0 0.0% Net Calling Load 0 0 0.0% Lighting 15,167 15,167 15.9% People 5,180 4,901 10,081 10.6% Misc. Equipment Loads 9,797 0 9,797 10.3% Cooling Infiltration 0 0 0 0.0% Sub -Total 87,062 4,901 91,963 96.3% Ventilation Load -3,909 6,281 2,372 2.5% Exhaust Heat 258 0 258 0.3% Supply Fan Load 0 0 0.0% Retum Fan Load 0 0 0.0% Net Duct Heat Pickup 0 0 0.0% Wall Load to Plenum 871 871 0.9% Roof Load to Plenum 0 0 0.0% Lighting Load to Plenum 0 0 0.0% Misc. Equip. Load to Plenum 0 0 0 0.0% Glass Transmission to Plenty 0 0 0.0% Glass Solar to Plenum 0 0 0.0% Over/Under Sizing 0 0 0.0% Terminal Bypass 0 0 0 0.0% Total Cooling Loads 84,282 11,182 95,464 100.0% COOLING COIL SELECTION Coil Selection Parameters Coll Entering Air (DB / WB) Coll Entering Humidity Ratio Coll Leaving Air (DB / WB) Cott Leaving Humidity Ratio Coll Sensible Load Coll Total Load Cooling Supply Air Temperature Total Cooling Airflow Resulting Room Relative Humidity General Enalneerinfa Checks Total Cooling Load Area / Load Total Floor Area Cooling Airflow Alrflow / Load Percent Outdoor Air Cooling Load Methodology 73.5/60.8 'F 59.55 grAb 55.0/52.7 °F 65.58 gr/lb 8428' MBh 95.48 MBh 58.00 °F 4,083.64 cfm 4424 % 9.4 ton 256.07 fP/ton 2,415 ft' 1.69 cfnVft' 432.99 cfrn/ton 10.5 % TETD -TA1 Prolect Name: 6141 Sunset TRACE® 700 v4.1 calculated at 10:27 PM on 11/07/2005 = Dataset Name: \\ Main- serverlenglneering \WORK\D05-002 6141 REVISED \DOCUMENTS \CALCULATIONS16141 Sunset_REVISED.TF Alternative - 1 Design Cooling Load report page 2 Desig�l ;Codrr�g LagdSughmky; .8y' A4V 4ineeting,1nc6` COOLING COIL LOAD INFORMATION 6141 SuMpt • • • • 60•.I ., ;unw: -iyskm - ANU -3 3 • Zone - Zone - 007 reee .... • • . . Coll Coll Peak Calculation Time: October, hour 16 Ambient DB/WB /HR: 84 / 72 / 101 COOLING COIL SELECTION Load Component Sensible Latent Total Percent Coll Selection Parameters Blum Blum Blum of Total Soler Gain 95,220 95,220 66.7% Coil Entering Air (DB / WB) 73.8/60.0 OF Glass Transmission 5,705 5,705 4.0% Coll Entering Humidity Ratio 55.31 grAb Wall Transmission 799 799 0.6% Coil Leaving Air (DS / WB) 55.0/52.1 OF Roof Transmission 0 0 0.0% Coll Leaving Humidity Ratio 53.33 grAb Floor Transmission 0 0 0.0% Coil Sensible Load 134.06 MBh Partition Transmission 0 0 0.0% Coil Total Load 142.78 MBh Net Calling Load 0 0 0.0% Cooling Supply Alr Temperature 56.00 OF Lighting 17,597 17,597 12.3% Total Cooing Airflow 6,400.43 cfm People 3,163 2,939 6,102 4.3% Resulting Room Relative Humidity 41.71 % Misc. Equipment Loads 13,546 0 13,546 9.5% Cooling Infiltration 0 0 0 0.0% Sub-Total -:o 136,032 2,939 138,971 97.3% General Enalneerina Checks Ventilation load -2,790 5,779 2,989 2.1% Total Cooling Load 13.0 ton Exhaust Heat 229 0 229 0.2% Area / Load 205.81 ft'/ton Supply Fan Load 0 0 0.0% Total Floor Area 2,663 fF Return Fan Load 0 0 0.0% Cooling Airflow 2.40 cfrn/ft° Net Dud Heat Pickup 0 0 0.0% Airflow / Load 494.17 cfm/ton Well load to Plenum 593 593 0.4% Percent Outdoor Air 3.9 % Roof Load to Plenum 0 0 0.0% Cooling Load Methodology TETD -TA1 Lighting Load to Plenum 0 0 0.0% Misc. Equip. Load to Plenum 0 0 0 0.0% Glass Transmission to Plenty 0 0 0.0% Glass Solar to Plenum 0 0 0.0% Over/Under Sizing 0 0 0.0% Terminal Bypass 0 0 0 0.0% Total Cooling Loads 134,063 8,718 142,781 100.0% Project Name: 6141 Sunset TRACES 700 v4.1 calculated at 10:27 PM on 11/07/2005 Dataset Name: \\ Main- server\engineering \WORK\D05-002 6141 REVISED\DOCUMENTS \CALCULATIONS \6141 Sunset_REVISED.TF Alternative - 1 Design Cooling Load report page 3 Design: 9c Oof hg Loia0l3ui 6aiiise. • A; P'RV &91neenng,1 ' COOLING COIL LOAD INFORMATION 6141 SLWet • •. 6141 Sunset; . .System - A140 -3.4 ' •' •' • - Zone - Zone - 008 .••. ..••. CoIl Location �ZOQ0• • • i • • •' • Pea Calculation Time: July, hour 17 Coil k Ambient DB/WB/HR: 89 / 77 / 119 COOLING COIL SELECTION Load Component Sensible Latent Total Percent Coil Selection Parameters Btu/h Btu/h Btu/h of Total Solar Gain 83,904 83,904 66.4% Coll Entering Air (DB / WB) Glass Transmission 6,226 6,226 4.9% Coll Entering Humidity Ratio Wall Transmission 751 751 0.6% Coll Leaving Alr (DS / WB) Roof Transmission 0 0 0.0% Coll Leaving Humidity Ratio Floor Transmission 0 0 0.0% Coll Sensible Load Partition Transmission 0 0 0.0% Coll Toted Load Net Ceiling Load 0 0 0.0% Cooling Supply Air Temperature Lighting 12,232 12,232 9.7% _ . _ Total.Coolin9 Airflow _ People 1,951 1,561 3,512 2.8% ---- " "Resulting Room R'elative•Humliity Misc. Equipment Loads 16,526 0 16,526 13.1% '%A f e B Sri H 1Li v t Cooling Infiltration 0 0 0 0.0% Sub -Total -s 121,589 1,561 123,150 97.4% . ,General Enalnetirind CFieaksi '7 1 Ventilation Load -2,274 4,720 2,446 1.9% -Total Cooling Load Exhaust Heat 167 0 167 0.1% Area / Load. i o_ITJUF473 Supply Fan Load 0 0 0.0% - - - - - Total-Floor Area Return Fan Load 0 0 0.0% !. Cooling Airflow - Net Duct Heat Pickup 0 0 0.0% Airflow / Load - P^ AO-i Wall Load to Plenum Roof Load to Plenum 632 0 632 0 0.6% 0.0% .� - - Percent Outdoor Air �, Coolln g Load Methodol °+" f` Lighting Load to Plenum 0 0 0.0% - Misc. Equip. Load to Plenum 0 0 0 0.0% Glass Transmission to Plenui 0 0 0.0% Glass Solar to Plenum 0 0 0.0% Over/Under Sizing 0 0 0.0% Terminal Bypass 0 0 0 0.0% Total Cooling Loads 120,115 6,281 126,396 100.0% 73.8/60.0 OF 55.02 qr ib 55.0/52.1 OF 53.37 grAb 120.12 MBh 126.40 MBh 56.00 OF 5,718.66 cfm 41.57 % 11.4 ton 183.47 ft'/ton 2,090 W 2.74 cfn N 502.01 cfm/ton 4.9 % TETD -TA1 Project Name: 6141 Sunset ` TRACE® 700 v4.1 calculated at 10:27 PM on- 11/07/2005 Dataset Name: \\ Main- server\engineering \WORK\D05-002 6141 REVISED \DOCUMENTS \CALCULATIONS \6141 SunseLREVISED.Tf; " _1 - � - Alternative -1 'Design Cooling Load report page 4,'- - ciTY&S-O—tyTHWAMI, BUILDING DEPARTMENT APPROVED VED 6Y. DATE , BUILQfNG I STRUCTURAL ELlt'*lCAL _ I MECFdANICAL PLUMBWG,F . ... . ..... . .... ciTY&S-O—tyTHWAMI, BUILDING DEPARTMENT APPROVED VED 6Y. DATE , BUILQfNG I STRUCTURAL ELlt'*lCAL _ I MECFdANICAL PLUMBWG,F Ji Date: September 13, 2005 To: All Fire Alarm Contractors and Designers From: M. Mena, Division Chief Fire Prevention Subject: Fire Alarm Policy Change .� M IAM I•l]�grj� Mernofandurn , Notice of Fire Alarm Polic � Change Effective November 14 t , 2005 Pursuant to the Florida Fire Prevention Code 2004 edition and NFPA 72 2002 edition the supervision of all new fire alarm systems and all new sprinkler systems installed in the jurisdiction of Miami -Dade Fire Rescue shall be by a listed Central Station or a listed Proprietary Supervising Station in compliance with the adopted edition of NFPA 72 that is in effect at the time of permit application. All new fire alarm systems and all new sprinkler systems requiring supervision, electing to provide supervision, or providing supervision as an equivalency, installed in the jurisdiction of Miami -Dade Fire Rescue, shall meet the requirements for Central Station Service or Proprietary Supervising Station fire alarm systems and shall be either a certificated or placarded Central Station Fire Alarm System or a listed Proprietary Supervising Fire Alarm System in compliance with the adopted edition of NFPA 72 that is in effect at the time of permit application. These changes are intended to assist the efforts of Miami -Dade Fire Rescue in ensuring adequate installation and maintenance of fire alarm systems, in providing timely restoration of fire alarm systems to working order, in the regulation of supervising stations operating within the jurisdiction of Miami -Dade County Fire Rescue, and in reducing false alarms. Proof of certification or listing shall be provided at the time of final inspection and no final inspection shall be approved without proper proof and documentation. Certification or listing shall be required to remain continuously in effect for the life of the system or until replaced by a new system. All new and existing fire alarm systems are subject to the provisions of the Code of Miami -Dade County Section 14 -10 Fire Alarms, the Florida Administrative Code Rule Title 69A — 48 Fire Safety Standards for Fire Alarm Systems, and the installation, testing, and maintenance provisions of NFPA 72 National Fire Alarm Code. Increased enforcement of these provisions will begin immediately on all systems. Code of Miami -Dade County Section 14 -10 Fire Alarms (4) Fire alarms, posting requirements. A fire alarm user shall conspicuously post at the main entrance to the alarm user's premises a notice stating (1) the name of an individual or alarm company able and authorized to enter the premises and deactivate the alarm; (2) emergency telephone numbers by which those individuals can be reached at all times; and (3) the name and address of the alarm user. The information must be kept current and failure to update this information within forty -eight (48) hours of any change constitutes a violation of this section. (Penalties for violation of this section shall be from $250.00 per violation up to $1000.00.)