97-498-098FACP - BATTERY CALCULATIONS TOTAL SYSTEM STANDBY CURRENT — 1.95 AMP TOTAL SYSTEM ALARM CURRENT — 28.95 + 8.5 = 37.45 AMPS (PANEL) (FIELD) USE 110 Ah BATTERIES FIRE ALARM - CONDUCTORS PL SHIELDED SPEAKER CIRCUITS — (1) TSP #14 IDC /NAC UNSHIELDED PL — (1) TNP #14 MAPNET II, RUI, NETWORK PL — (1) TSP #18 L ENTRY LFVFL - FI F['_TR1r_A1 VWl . 1/ V - 1 V FACP - INTERFACE NOTE PROVIDE (1) ADDITIONAL ZONE AT FIRE ALARM CONTROL PANEL. LABEL NEW ZONE AS "MALL" COORDINATE WITH MALL FACILITIES PERSONNEL TO INTERFACE WITH MALL FIRE ALARM SYSTEM. ROUTE NEW CABLING FROM MALL SYSTEM TO ANUNCIATE NEW ZONE IN THEATER FACP IN THE EVENT OF MALL ALARM INITIATION. PROVIDE REMOTE LCD ANNUNCIATOR AT MALL FIRE ALARM SYSTEM FOR INTERFACE. ROUTE OUTPUT SIGNAL CABLING FROM THEATER FACP TO MALL SYSTEM TO ANNUNCIATE MALL SYSTEM IN THE EVENT OF THEATER ALARM INITIATION. CABLING, ROUTING, INTERFACE, HARDWARE, AND TERMINATIONS TO MALL SYSTEMS SHALL BE PER MALL REQUIREMENTS. FIRE ALARM SYMBOLS MANUAL STATION — FIRE ALARM. (Z =ZONE NUMBER) PHOTO— ELECTRIC SMOKE DETECTOR (D DENOTES IN DUCT). INSTALL IN SUPPLY OR RETURN AS DIRECTED BY LOCAL CODE PUBLIC ADDRESS SPEAKER FIRE ALARM CONTROL PANEL. SPRINKLER ALARM SWITCH. (TAMPER) GATE SWITCH. (FLOW) REMOTE ANNUNCIATION PANEL 'RAP' FIRE ALARM STROBE LIGHT WALL MOUNTED AT 80" ABOVE LOBBY FLOOR LEVEL ELEVATION HEAT DETECTOR GENERAL AND PALN NOTES REFER TO SHEET E1 TFN 16 GA. 1 CONNECT TO BOOTH 2 TERMINAL BOARD (AUTOMATION) FIRE ALARM TERMINALS 3 Y TO AUTOMATIC OR MANUAL SWITCH SWITCH IN FIRE ALARM PANEL (24 REQUIRED) r_jl__1 24 VOLT DC POWER SUPPLY —24 VOLT DC COIL RELAY (TYP. 24 REQ'D. MOUNTED IN FIRE ALARM CONTROL PANEL) L J LABEL SWITCHES IN FIRE ALARM PANEL WITH AUDITORIUM NUMBERS. ACTIVATION OF SWITCH WILL SHUT DOWN SOUND, PROJECTOR AND BRING HOUSE LIGHTS TO FULL BRIGHT. FIRE ALARM AUDITORIUM SOUND SHUTDOWN DETAIL NO SCALE TO REMAINING SPEAKERS THIS ZONE TYPICAL SPEAKER ZONE, 26 REQUIRED SEE SCHEDULE FIRE ALARM RISER DIAGRAM DOOR ALARM [NIT. DEVICE TYPICAL -26 ZONES REQUIRED AUTOMATION FAIL SAFE ] TYPICAL -24 REQUIRED SEE DETAIL ZN8 ZN9 EXTENDS TO REMAINING PULL STATIONS ON LOWER LEVEL CORRIDORS AND LOBBY —EXTENDS TO ON MEZZANINE LEVEL G PULL STATIONS H PE } TRASH ROOMS FIRE ALARM ZONE SCHEDULE ZONE NO. AREA SERVED 1 ENTRY LFVFL - FI F['_TR1r_A1 VWl . 1/ V - 1 V FACP - INTERFACE NOTE PROVIDE (1) ADDITIONAL ZONE AT FIRE ALARM CONTROL PANEL. LABEL NEW ZONE AS "MALL" COORDINATE WITH MALL FACILITIES PERSONNEL TO INTERFACE WITH MALL FIRE ALARM SYSTEM. ROUTE NEW CABLING FROM MALL SYSTEM TO ANUNCIATE NEW ZONE IN THEATER FACP IN THE EVENT OF MALL ALARM INITIATION. PROVIDE REMOTE LCD ANNUNCIATOR AT MALL FIRE ALARM SYSTEM FOR INTERFACE. ROUTE OUTPUT SIGNAL CABLING FROM THEATER FACP TO MALL SYSTEM TO ANNUNCIATE MALL SYSTEM IN THE EVENT OF THEATER ALARM INITIATION. CABLING, ROUTING, INTERFACE, HARDWARE, AND TERMINATIONS TO MALL SYSTEMS SHALL BE PER MALL REQUIREMENTS. FIRE ALARM SYMBOLS MANUAL STATION — FIRE ALARM. (Z =ZONE NUMBER) PHOTO— ELECTRIC SMOKE DETECTOR (D DENOTES IN DUCT). INSTALL IN SUPPLY OR RETURN AS DIRECTED BY LOCAL CODE PUBLIC ADDRESS SPEAKER FIRE ALARM CONTROL PANEL. SPRINKLER ALARM SWITCH. (TAMPER) GATE SWITCH. (FLOW) REMOTE ANNUNCIATION PANEL 'RAP' FIRE ALARM STROBE LIGHT WALL MOUNTED AT 80" ABOVE LOBBY FLOOR LEVEL ELEVATION HEAT DETECTOR GENERAL AND PALN NOTES REFER TO SHEET E1 TFN 16 GA. 1 CONNECT TO BOOTH 2 TERMINAL BOARD (AUTOMATION) FIRE ALARM TERMINALS 3 Y TO AUTOMATIC OR MANUAL SWITCH SWITCH IN FIRE ALARM PANEL (24 REQUIRED) r_jl__1 24 VOLT DC POWER SUPPLY —24 VOLT DC COIL RELAY (TYP. 24 REQ'D. MOUNTED IN FIRE ALARM CONTROL PANEL) L J LABEL SWITCHES IN FIRE ALARM PANEL WITH AUDITORIUM NUMBERS. ACTIVATION OF SWITCH WILL SHUT DOWN SOUND, PROJECTOR AND BRING HOUSE LIGHTS TO FULL BRIGHT. FIRE ALARM AUDITORIUM SOUND SHUTDOWN DETAIL NO SCALE TO REMAINING SPEAKERS THIS ZONE TYPICAL SPEAKER ZONE, 26 REQUIRED SEE SCHEDULE FIRE ALARM RISER DIAGRAM DOOR ALARM [NIT. DEVICE TYPICAL -26 ZONES REQUIRED AUTOMATION FAIL SAFE ] TYPICAL -24 REQUIRED SEE DETAIL ZN8 ZN9 EXTENDS TO REMAINING PULL STATIONS ON LOWER LEVEL CORRIDORS AND LOBBY —EXTENDS TO ON MEZZANINE LEVEL G PULL STATIONS H PE } TRASH ROOMS * = PROVIDE RELAY FOR EACH FPB BOX TO SHUT DOWN WITH CORRESPONDING SMOKE DETECTOR. a APPROVED FOR B1j1L_D1N'G PERMITTING PURPOSES fY( DAME COUNTY FIRE DEPARTMENT L A /i_M FIRE l} �eliil M CONTRACTOR'S *ORKING PLM AS PER - 60 33,7o SMALL BE SUBMITTED' FOR APPR(WAL TQ METRO DADS € BEFORE ANY FIRE SYSTBN LEGEND IAM ADRESSABLE MONITORING DEVICE IRE ALtt < :i INSTALLED IN ACCORDANCE WITH N.F.P.A. 72. 72E 7Q Article 760, 15, 16, 21t N.F.P.. 101 - 7 . g VISUAL ALARM ANSI A117.1, 4.2& V010E NOTIFICa0r4 X011 -8- 3.4.3.4 ZN24 Gould Evans Associates, LC 706 Massachusetts ]Lawrence KS 66044 -2256 913/842 3800 913/842 3830 fax internet: www.geaf.com 1 h; LIIItiCI 1wo South famn, Mod& 'J d W z V' a �I x w , gq,� A GEA Mfillate Lawrence, KS Kansan City, MO Philadelphia, PA Tampa, FL Phoenix, AZ No. Revision Date Q1 CLARIFICATIONS 6/23/97 Drawn MPP Checked MAP Project no. AMC 9 - -- Date 21 OCTOBER 1996 E 3 :h FIRE ALARM ZONE SCHEDULE ZONE NO. AREA SERVED 1 AUDITORIUM #1 PULL STATIONS 2 AUDITORIUM #2 PULL STATIONS 3 AUDITORIUM #3 PULL STATIONS 4 AUDITORIUM #4 PULL STATIONS 5 AUDITORIUM #5 PULL STATIONS 6 AUDITORIUM #6 PULL STATIONS 7 AUDITORIUM #7 PULL STATIONS 8 AUDITORIUM #8 PULL STATIONS 9 AUDITORIUM #9 PULL STATIONS 10 AUDITORIUM #11 PULL STATIONS 11 AUDITORIUM #11 PULL STATIONS 12 AUDITORIUM #12 PULL STATIONS 13 AUDITORIUM #13 PULL STATIONS 14 AUDITORIUM #14 PULL STATIONS 15 AUDITORIUM #15 PULL STATIONS 16 AUDITORIUM #16 PULL STATIONS 17 AUDITORIUM #17 PULL STATIONS 18 AUDITORIUM #18 PULL STATIONS 19 AUDITORIUM #19 PULL STATIONS 20 AUDITORIUM #20 PULL STATIONS 21 AUDITORIUM #21 PULL STATIONS 22 AUDITORIUM #22 PULL STATIONS 23 AUDITORIUM #23 PULL STATIONS 24 AUDITORIUM #24 PULL STATIONS 25 LOBBY & CORRIDOR PULL STATIONS 26 MEZZANINE PULL STATIONS 27 RTU #1 DUCT DETECTORS 28 RTU #2 DUCT DETECTORS 29 RTU #3 DUCT DETECTORS 30 RTU #4 DUCT DETECTORS 31 RTU #5 DUCT DETECTORS 32 RTU #6 DUCT DETECTORS 33 RTU #7 DUCT DETECTORS 34 FAN POWERED BOXES (FPB) DETECTS 35 -44 SPARE ZONE * = PROVIDE RELAY FOR EACH FPB BOX TO SHUT DOWN WITH CORRESPONDING SMOKE DETECTOR. a APPROVED FOR B1j1L_D1N'G PERMITTING PURPOSES fY( DAME COUNTY FIRE DEPARTMENT L A /i_M FIRE l} �eliil M CONTRACTOR'S *ORKING PLM AS PER - 60 33,7o SMALL BE SUBMITTED' FOR APPR(WAL TQ METRO DADS € BEFORE ANY FIRE SYSTBN LEGEND IAM ADRESSABLE MONITORING DEVICE IRE ALtt < :i INSTALLED IN ACCORDANCE WITH N.F.P.A. 72. 72E 7Q Article 760, 15, 16, 21t N.F.P.. 101 - 7 . g VISUAL ALARM ANSI A117.1, 4.2& V010E NOTIFICa0r4 X011 -8- 3.4.3.4 ZN24 Gould Evans Associates, LC 706 Massachusetts ]Lawrence KS 66044 -2256 913/842 3800 913/842 3830 fax internet: www.geaf.com 1 h; LIIItiCI 1wo South famn, Mod& 'J d W z V' a �I x w , gq,� A GEA Mfillate Lawrence, KS Kansan City, MO Philadelphia, PA Tampa, FL Phoenix, AZ No. Revision Date Q1 CLARIFICATIONS 6/23/97 Drawn MPP Checked MAP Project no. AMC 9 - -- Date 21 OCTOBER 1996 E 3 :h FIRE ALARM SPEAKER ZONE SCHEDULE ZONE NO. AREA SERVED 1 AUDITORIUM #1 2 AUDITORIUM #2 3 AUDITORIUM #3 4 AUDITORIUM #4 5 AUDITORIUM #5 6 AUDITORIUM #6 7 AUDITORIUM #7 8 AUDITORIUM #8 9 AUDITORIUM #9 10 AUDITORIUM #10 11 AUDITORIUM #11 12 AUDITORIUM #12 13 AUDITORIUM #13 14 AUDITORIUM #14 15 AUDITORIUM #15 16 AUDITORIUM #16 17 AUDITORIUM #17 18 AUDITORIUM #18 19 AUDITORIUM #19 20 AUDITORIUM #20 21 AUDITORIUM #21 22 AUDITORIUM #22 23 AUDITORIUM #23 24 AUDITORIUM #24 25 LOBBY AREAS 26 MEZZANINE 27 SPARE 28 SPARE 29 SPARE 36 SPARE * = PROVIDE RELAY FOR EACH FPB BOX TO SHUT DOWN WITH CORRESPONDING SMOKE DETECTOR. a APPROVED FOR B1j1L_D1N'G PERMITTING PURPOSES fY( DAME COUNTY FIRE DEPARTMENT L A /i_M FIRE l} �eliil M CONTRACTOR'S *ORKING PLM AS PER - 60 33,7o SMALL BE SUBMITTED' FOR APPR(WAL TQ METRO DADS € BEFORE ANY FIRE SYSTBN LEGEND IAM ADRESSABLE MONITORING DEVICE IRE ALtt < :i INSTALLED IN ACCORDANCE WITH N.F.P.A. 72. 72E 7Q Article 760, 15, 16, 21t N.F.P.. 101 - 7 . g VISUAL ALARM ANSI A117.1, 4.2& V010E NOTIFICa0r4 X011 -8- 3.4.3.4 ZN24 Gould Evans Associates, LC 706 Massachusetts ]Lawrence KS 66044 -2256 913/842 3800 913/842 3830 fax internet: www.geaf.com 1 h; LIIItiCI 1wo South famn, Mod& 'J d W z V' a �I x w , gq,� A GEA Mfillate Lawrence, KS Kansan City, MO Philadelphia, PA Tampa, FL Phoenix, AZ No. Revision Date Q1 CLARIFICATIONS 6/23/97 Drawn MPP Checked MAP Project no. AMC 9 - -- Date 21 OCTOBER 1996 E 3 :h