13-1358-039ELECTRICAL NOTES:
1 ALL WORK SHALL BE IN ACCORDANCE WITH THE NATIONAL ELECTRICAL
CODE 20011, FBC 2010 AND OTHER APPLICABLE CODES AND STANDARDS.
2 THE CONTRACTOR IS RESPONSIBLE FOR EVALUATING FIELD CONDITIONS
BY VISITING THE SITE PRIOR TO COMMENCING/BIDDING WORK
3. THE CONTRACTOR SHALL SATISFACTORILY REPAIR/REPLACE EQUIPMENT
OR PART OF STRUCTURE DAMAGED AS A RESULT OF HIS WORK SURFACES
AND FINISHED AREAS SHALL BE RESTORED TO MATCH ADJACENT AREAS.
4, APPROVAL SHALL BE OBTAINED FROM THE ENGINEER PRIOR TO CUTTING
OR DRILLING ANY STRUCTURAL SUPPORT MEMBER
5. ALL DEVICE BOXES SHALL BE INSTALLED FLUSH AND CONDUITS RUN
CONCEALED IN FINISHED AREAS EXCEPT AS SPECIFICALLY SHOWN/NOTED
OTHERWISE
6. WIRE SIZE SHALL BE X12 THHN/THWN STRANDED MINIMUM UNLESS OTHERWISE
NOTED ON PLANS.
7 ALL CONDUCTORS SHALL BE COPPER
8. ALL CONDUCTORS SHALL BE RUN IN CONDUIT (METALLIC TYPE). IF PVC
SCHEDULE 40 IS USED FOR UNDERGROUND FEEDERS ONLY, AN EQUIPMENT
GROUND CONDUCTOR SIZED IN ACCORDANCE WITH NEC 250 -95 MUST BE
INSTALLED AND CONDUIT SIZE INCREASED AS REQUIRED,
9. ALL MATERIAL MUST BE UL APPROVED.
1(1 ALL BRANCH CIRCUITS MUST BE PROPERLY PHASE BALANCED.
11, CONTRACTOR SHALL SEAL ALL FLOOR OPENINGS WITH A FIRE SEAL
SIMILAR TO 3M FIRE DAM 15Q
12 ALL EMPTY CONDUITS TO BE PROVIDED WITH NYLON PULL STRINGS
13. FUSES SHALL BE DUAL ELEMENT, TIME DELAY TYPE UNLESS OTHERWISE
NOTED.
14 ALL LUMINARIES SHALL BE PROPERLY SUPPORTED IN `ACCORDANCE WITH
CEILING SYSTEM MANUFACTURER RECOMMENDATIONS AND LOCAL CODE
REQUIREMENTS
15. RISERS ARE DIAGRAMMATIC ONLY. THEY DO NOT SHOW EVERY BEND
REQUIRED FOR THE INSTALLATION.
16. THIS DRAWING IS A GUIDE FOR THE INSTALLATION OF ELECTRICAL
SERVICE THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE
A FUNCTIONING SYSTEM
17. ALL CABLES SHALL BE RUN WITHOUT SPLICES EXCEPT OTHERWISE
INDICATED.
18. ALL PULL AND JUNCTION BOXES SHALL BE ACCESSIBLE AT ALL TIMES.
19. EXACT POINT AND METHODS OF CONNECTION SHALL BE DETERMINED IN
FIELD.
2Q ALL WORK SHALL BE DONE IN A NEAT WORKMANLIKE MANNER
21 NEC (203) 517 :0 NEED ISOLATED GREEN X12 CONDUCTOR FROM ALL PATIENT
CARE/EXAM ROOM OUTLETS FOR PATIENT CARE TO THE ELECTRICAL PANEL
22 AT EXAM ROOMS FOR PATIENT CARE USE HOSPITAL GRADE RECEPTACLES
FOR RECEPTACLES USED FOR THIS PURPOSE
23, IF RUNING MULTTBRANCH CIRCUITS IN SAME CONDUIT, MUST USE INDEPENDANT.
NEUTRALS OR SHOW 2 POLE 3 POLE BREAKERS AT ELECTRICAL PANEL
RECOMMEND TO USE INDIVIDUAL NEUTRALS FOR EACH CIRCUIT.
FIRE ALARM LEGEND
F❑ MANUAL PULL STATION MOUNTED AT 4&' AFF.
SL STROBE LIGHT MOUNTED AT 80" AFF, 75 cd UNO.
FH HORN MOUNTED AT W AFF.
IJ DUCT DETECTOR REMOTE TROUBLE / ALARM INDICATOR
COMBINATION HORN / STROBE MOUNTED AT 800 AFF, 75 cd UNO.
SD SMOKE DETECTOR SUFFIX 0EL' INDICATES WITH ELEVATOR RECALL FUNCTION.
HD HEAT DETECTOR SUFFIX "EL' INDICATES WITH ELEVATOR RECALL FUNCTION.
DD DUCT DETECTOR
FFA—C-Pl FIRE ALARM CONTROL PANEL
FAC FIRE ALARM COMMUNICATOR
ANN FIRE ALARM REMOTE ANNUNCIATOR PANEL
SPOT COFFEE
NEW 4 #3 &1#6(G)
COPPER IN 1 -1/2" COND.
SUB PANEL PANEL
PANEL uAu w
uLu
SECT II SECT I
NEW 2 SETS 4#3/0
i, 1#20 IN 20 C EACH
FIRE ALARM NOTES:
1. FIRE ALARM SYSTEM SHALL COMPLY WITH REQUIREMENTS OF NFPA 101
AND FLORIDA BUILDING CODE
2 FIRE ALARM SYSTEM SHALL BE POWER LIMITED.
3, THE NEW FIRE ALARM SYSTEM SHALL BE CERTIFIED AS A CENTRAL
STATION FIRE ALARM SYSTEM
4, SYSTEM SHALL BE PROVIDED WITH SECONDARY POWER SUPPLY OF
SUFFICIENT CAPACITY FOR 24 HOURS STANDBY AND 15 MINUTES OF ALARM
5 ALL EQUIPMENT SHALL BE NEW, UL LISTED, COMPATIBLE AND LISTED
FOR USE IN FIRE ALARM
& INSTALLATION SHALL COMPLY ALL CODES ADOPTED BY THE LOCAL AHU
7. INSTALLATION SHALL COMPLY WITH THE LATEST EDITION OF NFPA 72
NFPA 101, NFPA 1 AND NFPA 7D.
8 CONDUITS SHALL BE 1/20 MINIMUM WITH A MAXIMUM FILL OF 40%,
COMPLY WITH NEC.
9. SYSTEM SHALL BE GROUNDED PER MANUFACTURERS SPECIFICATIONS.
111 MINIMUM WIRE SIZE SHALL BE X16 AWG COPPER UNLESS NOTED
OTHERWISE
tt CONDUCTORS SHALL HAVE MINIMUM RATING OF 300V AND SHALL BE
OF SOLID COPPER OR BUNCH - TINNED STRANDED COPPER CONDUCTORS.
12 ALL DEVICES OR UNITS SHALL BE INSTALLED USING APPROVED
MATERIALS AND WIRING PRACTICES IN ACCORDANCE WITH THE NATIONAL
ELECTRIC CODE NFPA 70 ARTICLE #760 POWER LIMITED SECTION AND ALL
APPLICABLE LOCAL WIRING ORDINANCES.
13, ALL OUTDOOR FIRE ALARM DEVICES SHALL BE WEATHERPROOF TYPE.
14 OFF -SITE MONITORING SHALL BE PROVIDED,
16 ALL SMOKE DETECTORS SHALL BE MOUNTED MORE THAN 3' AWAY
FROM A/C DIFFUSERS
111 INTERCONNECTED FIRE ALARM CONTROL PANEL, REMOTE POWER SUPPLIES,
AMPLIFIERS AND DEVICES SHALL BE ARRANGED TO FUNCTION AS A SINGLE
SYSTEM AND MONITORED FOR INTEGRITY PER NFPA 72
17. VISUAL NOTIFICATION DEVICES SHALL COMPLY WITH THE LATEST
EDITION OF ADA GUIDELINES, BE SYNCHRONIZED WHEN REQUIRED, CLEAR
XENON TYPE, AND WITH MIN. INTENSITY OF 75 CANDELAS UNLESS NOTED
OTHERWISE ON PLANS.
16. AUDIBILITY SHALL BE AT LEAST 15 dB ABOVE THE AVERAGE AMBIENT
SOUND OR 5 dB ABOVE THE MAX SOUND LEVEL WHICHEVER IS GREATER
IN THE OCCUPABLE AREA
19, AUDIBLE/VISIBLE AND VISIBLE DEVICES SHALL BE PLACED SUCH THAT
THE ENTIRE LENS IS NOT LESS THAN 800 ABOVE THE HIGHEST FLOOR
LEVEL WITHIN THE SPACE OR 60 BELOW THE CEILING WHICHEVER IS
LOWER AS PER LATEST EDITION OF ADA GUIDELINES AND NFPA 72
2Q WALL - MOUNTED AUDIBLE NOTIFICATION APPLIANCES SHALL HAVE THEIR
TOPS ABOVE THE FINISHED FLOOR AT HEIGHTS OF NOT LESS THAN 90"
AND BELOW THE FINISHED CEILINGS AT HEIGHTS OF NOT LESS THAN 9'
AS PER LATEST EDITION OF NFPA 72
2t THE OPERABLE PART OF EACH MANUAL FIRE ALARM BOX SHALL BE
AT 480 AFF AND COMPLY WITH ADA 42 AND NFPA 72 2i.
22 REFER TO FLOOR PLANS AND SPECIFICATIONS FOR EQUIPMENT
LOCATION, QUANTITY, USE ETC. THE RISER DIAGRAM SHOWN IS OF A
GENERAL FORM
23, PROVIDE END OF LINE RESISTORS, INTERFACE MODULES, CONTROL
MODULES, AUXILIARY POWER SUPPLIES, MONITOR MODULES, CONTROL
RELAYS, ETC. AS REQUIRED FOR A COMPLETE INSTALLATION.
24. CONTRACTOR SHALL SUBMIT SHOP DRAWINGS, FIRE ALARM SYSTEM
SPECIFICATION SHEETS AND ALL BATTERY CALCULATIONS TO THE BUILDING
DEPARTMENT AND THE ENGINEER FOR REVIEW PRIOR TO ACQUIRING THE
PERMIT.
25. ELECTRICAL CONTRACTOR SHALL VISIT THE PROJECT SITE AND INCLUDE
IN HIS/HER BID PROPOSAL ALL THE WORK RELATED TO THE INSTALLATION
OF THE ENTIRE FIRE ALARM SYSTE=M
26. COORDINATE THE INSTALLATION OF ALL FLOW AND TAMPER SWITCH
MONITORS WITH THE FIRE PROTECTION CONTRACTOR
27. COORDINATE THE INSTALLATION OF ALL REQUIRED MONITOR AND CONTROL
MODULES FOR THE HVAC EQUIPMENT WITH THE MECHANICAL CONTRACTOR
REFER TO MECHANICAL DRAWING FOR THE SEQUENCE OF OPERATION.
28. ELECTRICAL CONTRACTOR SHALL PROVIDE TRANSIENT VOLTAGE SURGE
SUPPRESSION (7VSS) ON ALL FIRE ALARM CIRCUITS ENTERING AND LEAVING
THE FACILITY, INCLUDING, BUT NOT LIMITED TO CIRCUITS INTERFACING WITH
THE FIRE ALARM RECEIVING STATION (%� COMMUNICATION CIRCUITS).
MAIN ELECTRICAL ROOM
(GARAGE)
NEW 2 SETS 4#3/0
& 1#20 IN 20 C EACH
ELECTRICAL RISER DIAGRAM
NOT TO SCALE
•••• ••• • • •••ii •iU
YYV �' Y
`
Y
y
Y•GV4
Y W
•
•
V
W
Y w
Y Y U
•
Y
•
F Y F Y
V • •
YYU yV•
If
F M,/
EXISTING
ro
I \, I
I MAIN 1 OF 1
EXISTING
EXISTING
EXISTING
EXISTING
I I I I
F -j
F^-
r
F-1
F^ .7
r
EXISTING
I 8 I I METER I
I
I I
I g l
l '/ I
I g l
l M/ I
I 3P/400 11 120/208 V I
I I
13P/200 I
I I
13P/200 I
I I
I J 3 PHASE
I
I
B
I
L_J
LTJ
L_J
LTJ
400 A
L__J L_T._J
I
G G •
• LL
w
_-- _— L----------
F
1-- •------- - - -L --
o
3P/1200
o0
o
U_
EXISTING
GUTTER
L------------------------
E"
- - - - --
W
- - - - -J
ELECTRICAL RISER DIAGRAM
NOT TO SCALE
•••• ••• • • •••ii •iU
YYV �' Y
`
Y
y
Y•GV4
Y W
•
•
V
W
Y w
Y Y U
•
Y
•
F Y F Y
V • •
YYU yV•
W
ro
M
•
W y
Y F
• •
U•
u }
• Y
• i
Y
Y •
• W
• J
Y
•
•
Y W
Y
• �
Y
•
• F
•
V • U_
• •
yvG y•Y
Ywi
•
G G •
• LL
w
YYVY wYYGG •Y• YV1iw.•
V •
Y • G � w w.
rYUy •
Y Y W Y w Y •
Y Y
YyY YYVYYY V Y•U Y YY•• •
Roof Plan - Electrical
maqueira
gineering
consultants
SCALE: ]/,I'= 1'-0'
M.+.QUEIR^ ENGINEERING CONSULTANTS, INC.
7467 SW 50th Terrace 305.669.55+95
Miami, Florida 33155 cadOmaqueiraxem
w
w
0
}
i
0
LL
O
w
U
(n
DJ
wC6
ic �_
dU
FLU
0=
ZU
W�
ON
<M
0
z
WM
w�;
=N
00
w�
�_
za
w>-
O -o
}U
UUj
LL0
U
ao
cn}
hm
a)w
O=
ZQ
tw
0
T
z�
_z y
w
�<
vw
UV r� Kr' W 4
cnz T�
OL
ROLANDO MAQUEIRA, RE
LLp0 FLORIDA PROFESSIONAL ENGINEER ii RE 55432
"7 \I',.—
WU
(nz
o°
0<
0
N
U)
ro
M
E0
v)
a)
r_j
M
C:
1
O
o
0
V
L=
o
L.n
o0
o
U_
E"
W
0
Ir
_0
Qj
O
V
un
z�
_z y
w
�<
vw
UV r� Kr' W 4
cnz T�
OL
ROLANDO MAQUEIRA, RE
LLp0 FLORIDA PROFESSIONAL ENGINEER ii RE 55432