Loading...
13-1358-010P_f.. 0" 111 • • aq @0000MOOM dom e 1 OR 2 HOUR FIRE RATED THROUGH PENETRATION FIRESTOP FOR SINGLE NON - METALLIC PIPE THROUGH GYPSUM WALLS USING 3M FIRESTOrPING. OTHE 1 OR 2 HR. FIRE RATED GYPSUM BOARD /STUD WALL ASSEMBLY SHALL BE CON�RUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL 0300 OR V400 SERIES WALL OR PARTITION DESIGN 4 THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES: A. STUDS - WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM. 2 IN, X 4 IN, LUMBER SPACED AT 16 IN, O,C. MAX. WITH NOM. 2 IN. X4 IN. LUMBER END PLATES AND CROSS BRACES. STEEL CHANNEL STUDS TO BE NOM, 35/8 IN. WIDE BY 13/8 IN, DEEP CHANNELS SPACED AT 24 IN, O.C. MAX. t+ B, GYPSUM BOARD - 5/a IN. THICK!,; 4 FT. WIDE WITH TAPERED EDGES. THE GYPSUM BOARD TYPE, THICKNESS, NUMBER OF LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAK U300 OR V400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM. OF OPENING IS 3)/8 IN. THROUGH PENETRANTS ONE NON- METALLIC PIPE OR CONDUIT TO BE CENTERED IN THE THROUGH OPENING. THE ANNUAAR SPACE BETWEEN PIPE OR CONDUIT AND PERIPHERY OF OPENING SHALL BE A MIN, OF Y4 IN. AND MAX 3/a IN. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE FLOOR- CEILING ASSEMBLY, THE FOLLOWING TYPES AND SIZES OF NON- METALLIC PIPES OR CONDUITS MAY BE USED: A. PVC PIPE -- NOM. 2 IN. DIAM. (QR SMALLER) SCH. 40 SOLID CORE PVC PIPE USED IN CLOSED (PROCESS OR SUPPLY) ''OR VENTED (DRAIN, WASTE, OR VENT) PIPING SYSTEM. B. RIGID NON - METALLIC CONDUIT - NOM. 2" DIAM, (OR SMALLER) SCH. 40 OR 80 PVC CONDUIT INSTALLED IN ACCORDANCE WITH THE ARTICLE 347 OF THE NEC (NFPA NO. 70). DR1 CPVC PIPE FOR USE IN C. CPVC PIPE NOM. 2 IN. DIAM.,, (OR SMALLER) S 3.5 P C U CLOSED (PROCESS OR SUPPLY) ;;PIPING SYSTEM. D. ccPVC PIPE - NOM. 2 IN. DIAM; (OR SMALLER) SCH 40 CELLULAR CORE PVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE, OR VENT) PIPING SYSTEM. E. ABS PIPE - NOM, 2 IN. DIAM. (OR SMALLER) SCH 40 SOLID CORE ABS PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE, OR VENT) PIPING SYSTEM. F. ccABS PIPE - NOM. 2 in, DIAM. (OR SMALLER) SCH 40 CELLULAR CORE ABS PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE, OR VENT) PIPING SYSTEM. FIRESTOP SYSTEM INSTALLED SYMETRICALLY ON BOTH SIDES OF WALL ASSMEBLY. THE HOURLY F AND T RATINGS FOR FIRESTOP SYSTEM ARE EQUAL TO THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED. THE DETAILS OF THE FIRESTOP SYSTEM SHALL BE AS FOLLOWS. i'' A. FILL, VOID OR CAVITY MATERIALS;,':- WRAP STRIP - NOM. Y4 IN. THICK INTUMESCENT ELASTOMERIC MATERIAL FACED ON ONE SIDE WITH ALUMINUM FOIL, SUPPLIED IN 2 IN, WIDE STRIPS. NOM, 2 IN, WIDE STRIP TIGHTLY WRAPPED AROUND NON- METALLIC PIPE (FOIL SIDE OUT) WITH SEAM BUTTED. WRAP STRIP LAYER SECURELY BOUND WITH STEEL WIRE OR ALUMINUM FOIL TAPE AND SLID INTO ANNULAR SPACE APPROX. 1Y4 IN. SUCH THAT APPROX. 3/4 IN. OF WRAP STRIP PROTRUDES FROM THE WALL SURFACE. B. FILL, VOID OR CAVITY MATERIALS'` CAULK, SEALANT, OR PUTTY --- MIN. 5 /a. IN. THICKNESS OF CAULK OR PUTTY':. APPLIED INTO ANNULAR SPACE BETWEEN WRAP STRIP AND PERIPHERY OF OPENING, A PUTTY,, Y4 IN. DIAM. BEAD OF CAULK OR PUTTY TO BE APPLIED TO THE WRAP STRIP /WALL INTERFACE AND TO THE EXPOSED EDGE OF THE WRAP STRIP LAYERS APPROX. 3/4 IN. FROM THE WALL SURFACE. 3M COMPANY - CP 25WB4 -; IC 15WB +, FIREDAM 150+ CAULK, EB -3000 WT SEALANT, OR MP+ STIX PUTTY, (NOTE: L RATINGS APPLY ONLY WHEN CP 25WB+ CAULK IS USED. CP 25WB+ NOT SUITABLE FOR USE WITH CPVC PIPES.) C. FOIL TAPE (NOT SHOWN) - NOV. 4 IN, WIDE, 3 MIL. THICK ALUMINUM TAPE WRAPPED AROUND PIPE PRIOR TO THE INSTALLATION OF THE WRAP STRIP (ITEM 3A). MIN, OF ONE WRAP, FLUSH WITH BOTH SIDES OF WALL AND PROCEEDING OUTWARD. TAPE IS NOT REQUIRED FOR PIPES SHOWN IN ITEMS 2A, 2B, AND 2C. WL -2003 ss.f 3M Center F- Rating = 1 and 2 Hr * St. Paul, MN 55144 T- Rating = 1 and 2 Hr 1- 800 - 328 -1687 Drawing not to scale * (See Item 3 Above) 1 OR 2 HOUR FIRE RATED THROUGH PENETRATION FIRESTOP FOR SINGLE METALLIC PIPE THROUGH GYrSUM WALLS USING TREMSTOP 1A. ry D PRE -RATED GYPSUM WALLBOARD /STUD` WALL ASSEMBLY (F.B.C. SECTION 712.6) - 0 1. E EACH NEW /EXISTING EIRE WALL, FIRE BARRIER, FIRE PARTITION, SMOKE BARRIER, SMOKE o O METALLIC PIPE-- EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING ABOVE ANY ' A) STEEL PIPE - 12" DIAM. (OR SMALLER) SCH. 10 (OR HEAVIER) DECORATIVE CEILING AND IN ALL CONCEALED SPACES WITH THE WORDING "FIRE AND SMOKE = = B) IRON PIPE - 12" DIAM. (OR.'SMALLER) CAST OR DUCTILE IRON PIPE. C) COPPER TUBING 4" DIAM.,; (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING, r D) COPPER PIPE - 4" DIAM. (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE. LETTERING AND PROVIDED ON BOTH SIDES OF SAID ASSEMBLIES. , THE ANNULAR SPACE SHALL BE MIN, 0" TO MAX. 1" WITHIN THE FIRESTOP SYSTEM. K y O3 TREMSTOP IA MIN, 1/2" THICKNESS OF SEALANT APPLIED WITHIN OPENING. - MIN. 1/4" CANT BEAD OF SEALANT TO BE APPLIED AT POINT CONTACT. i W WL -1158 DY20HOUX) (F. F. P. C.) FLORIDA FIRE PREVENTION CODE 2010 - 'WITH LATEST SUPPLEMENTS c'' (N.F,P.A.) LIFE SAFETY CODE HANDBOOK - LATEST EDITION F- Raking = 1 and 2 Hour (F.A.C.) FLORIDA ACCESSIBILITY CODE FOR BLDG, CONSTRUCTION . $ 3735 Green Rd. T- Rating = 1/4 Hour 2, C CLASSIFICATION OF WORK / ALTERATION LEVEL ANALYSIS Beachwood, OH, 44122 ALTERATION LEVEL 2 : (F.B.C.E. SECTION 404.1) Q Drawing not to scale SCOPE - LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE, THE ADDITION sy s t e m OR ELIMINATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION OF L w - .h i GENERAL NOTE: (F.F.P.C. SECTION 8.3.24) (F.B.C. SECTION 712.6) - - 1. E EACH NEW /EXISTING EIRE WALL, FIRE BARRIER, FIRE PARTITION, SMOKE BARRIER, SMOKE PARTITION, OR ANY NEW /EXISTING WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALI_ BE EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING ABOVE ANY ' ' DECORATIVE CEILING AND IN ALL CONCEALED SPACES WITH THE WORDING "FIRE AND SMOKE = = BARRIER - - PROTECT ALL OPENINGS" OR SIMILAR LANGUAGE. SUCH SIGNS OR STENCILING SHALL BE PROVIDED WITH 4" IN, HIGH LETTERS, AND 1/2" IN. STROKE, AND NOT MORE THAN 15' FEET ON- CENTER. SUCH SIGNS OR STENCILING SHALL BE PROVIDED WITH RFD ' ' LETTERING AND PROVIDED ON BOTH SIDES OF SAID ASSEMBLIES. , , �QGU NO- anUu - 1. APPLICABLE CODES - (F.B.C.) FLORIDA BUILDING CODE 2010 - WITH LATEST SUPPLEMENTS (F. B. C. E.) FLORIDA BUILDING CODE 2010 EXISTING - WITH LATEST SUPPLEMENTS (F. F. P. C.) FLORIDA FIRE PREVENTION CODE 2010 - 'WITH LATEST SUPPLEMENTS (N.F,P.A.) LIFE SAFETY CODE HANDBOOK - LATEST EDITION (F.A.C.) FLORIDA ACCESSIBILITY CODE FOR BLDG, CONSTRUCTION . (N.F.P.A. --10) STANDARD FOR PORTABLE FIRE EXTINGUISHERS 2, C CLASSIFICATION OF WORK / ALTERATION LEVEL ANALYSIS ALTERATION LEVEL 2 : (F.B.C.E. SECTION 404.1) SCOPE - LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF SPACE, THE ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL EQUIPMENT.' MODIFICATION : (F,F,P.0 43.1 , 43.2.2.1.3) THE RECONFIGURATION OF ANY. SPACE THE ADDITION, `REL'OCATION, OR' ELIMINATION OF ANY DO OR OR WINDOW. T HE AD DIT ION OE LOAD B EA RING EL EM ENT S THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM OR THE INSTALLATION OF ADDITIONAL EQUIPMENT. 1 17-11 3. O OCCUPANCY CLASSIFICATION (F.B.C. SECTION 303, F.F.P.C. CH. 12 - NEW ASSEMBLY) GROUP A2 - ASSEMBLY E ELEtTRic 4. R REQUIRED SE PA RATION OF OCCU P ANC I ES ( E B. C. T A BLE 50 8.3. 3, F.F.P.0 TABLE 6.1 .14. 4.1 (b) GROUP A -2 -- ASSEMBLY �- WITH GROUP A (ASSEMBLY) 1 HOUR (8PRINKLFRFD) � WITH GROUP B (BUSINESS) -` 1, HOUR (SPRINKLERED) WITH GROUP M (MERCANTILE) 1 HOUR (SPRINKLERED) 5. A APPROVED AUTOMATIC SPRINKLER SYSTEM (F.F.P.C. SECTION 9.7.1) ` ` R ASC E S M PROVIDED - EXISTING TO BE ADAPTED TO NEW LAYOUT ) ) 6. F FIRE ALARM SYSTEM : (F.F.P.C. SECTION 12.3.4) z z NOT REQUIRED FOR ASSEMBLY OCCUPANCY WITH LESS THAN 300 OCCUPANTS - - -- r - -_ 7. O OCCUPANT LOAD (F.B.C. TABLE 1004.1.1, F.F.P.C. TABLE 7.3.1 .2 do CH. 121 .7.1.1) GROUP A -2 - ASSEMBLY 7 7 - -- - W: CS NON FIXED SES TABLE/ CHAIRS OCCUPANTS �. C ULEMM I _ _ GROUP A -2 - WITH APPROVED AUTOMATIC SPRINKLER 'SYSTEM 8 WALLS do CEILINGS FINISH VERTICAL EXITS AND EXIT PASSAGEWAYS - CLASS B F.B.C. PLUMBING, CHAPTER 4. TABLE 403.1. : CLASSIFICATION A -2 NIGHTCLUBS, BARS, TAVERNS, DANCE HALLS AND BUILDINGS FOR EXIT ACCESS CORRIDORS AND OTHER EXIT WAYS - CLASS "B" SIMILAR PURPOSES (INCLUDES OUTDOOR SEATING .00CUPANTS) ROOMS AND ENCLOSED SPACES = CLASS "C" FLOORS FINISH TOTAL NUMBER OF °OCCUPANTS = 110 OCC. (55 MALE / 55 FEMALE) EXIT ENCLOSURES - CLASS "II" EXIT PASSAGEWAYS CLASS "II" WATER CLOSET LAVATORILS DRINKING FOUNTAIN CORRIDORS = CLASS "I I" MALE (1 /75) FEMALE (1/75), MALE (1 /200) .FEMALE (1/200)" (1 /500) SERVICE SINK 14. CLASSIFICATION OF HAZARD (N.F.P.A. 10 SECTION 1-5) ORDINARY (MODERATE) HAZARD REQUIRED 55/75 - - 0.73 55/75 = 0:73 55/200'= 0.3 , 55/200 = 0.3 110/500 -' 0.22 1 (N.F.P.A. 10 SECTION 1-5.2) PROVIDED 1 1 1 1 WATER SERVED AT TABLE (a) 1 MINIMUM RATED SINGLE FXTINCUISHER = 2A MAXIMUM FLOOR AREA PER UNIT OF A = 1500 SF MAXIMUM FLOOR AREA FOR EXTINGUISHER = 11,250 SF a. F.B.C. PLUMBING SECTION 410.1 : WHERE WATER IS SERVED 'IN RESTAURANTS, DRINKING FOUNTAINS SHALL NOT BE REQUIRED. MAXIMUM TRAVEL DISTANCE TO EXTINGUISHER = 75 FEET b. F.B.C. PLUMBING SECTION- 419.2 URINALS :-'SUBSTITUTION FOR WATER CLOSETS. IN EACH BATHROOM OR TOILET ROOM, URINALS 15. EIRE EXTINGUISHER SPECIFICATION SHALL NOT BE SUBSTITUTED FOR MORE THAN 67 PERCENT OF THE REQUIRED WATER CLOSETS IN ASSEMBLY AND EDUCATIONAL OCCUPANCIES. URINALS SHALL NOT BE SUBSTITUTED FOR MORE THAN 50 PERCENT OF THE REQUIRED WATER CLOSETS IN ALL MANUFACTURER LARSENS OTHER OCCUPANCIES, SERIES MP-SERIES/MULTI PURPOSE DRY CHEMICAL - / C. F.B.C. PLUMBING SECTION 403.1.1 POTTY PARITY : IN ASSEMBLY OCCUPANCIES, RESTRQOMS WHICH ARE OPEN TO THE PUBLIC MODEL NO MP5 (UL RATING _2_A 10B.C) BRACKET PROVIDE STANDARD BRACKET MUST HAVE A RATIO OF 3:2 WATER CLOSETS PROVIDED FOR WOMEN AS THE COMBINED TOTAL' OF WATER CLOSETS AND URINALS OPTION (1521) PROVIDED FOR MEN, UNLFSS THESE ARE TWO OR FEWER SUCH FIXTURES FOR MEN, IN ACCORDANCE WITH §553,86, FLORIDA STATUTES: "K" CLASS EXTINGUISHER WITH SIGNS SHALL BE MOUNTED NEXT TO THE HOOD PULL STATION. c.1. EXCEPTION: THIS SECTION DOES NOT APPLY TO ESTABLISHMENTS LICENSED UNDER CHAPTER 509, FLORIDA STATUTES, IF THE ESTABLISHMENT DOES NOT PROVIDE MEETING OR BANQUET ROOMS WHICH ACCOMMODATE MORE THAN 150 PEOPLE, AND THE ESTABLISHMENT HAS AT LEAST THE SAME NUMBER OF WATER CLOSETS FOR WOMEN AS THE COMBINED TOTAL OF WATER CLOSETS AND URINALS FOR MEN. �J • bYrY• r� -` 21 • • • YI.1/ w Y • • > • •aVY • • w J Y OU1 �, / v • Y `� UU_ Y Y U Y • w Y • u Y Y V 1 Y < • a ♦aY • i U I� u1 • O � V YIY • YI•• i` pl> rri Sri v w 0 J d d z 0 0 d 0 d w O C) z I I Ln N I co N U EL DISTANCE SECT- 14.2.5.2, EQ. IS X150' -0" r� F ,1 N j 0 w �J LL] u� OV w O= z� (0< C) zo z� LU CI) LU M =N d V 1 M rH M 00 E 0 t--I M rU �! W E W 0 o �. � � W p L U Ln � r-q o= E C6 W i