13-1358-009,E I _E__ I.- - IN typical fire penetration detail 1 OR 2 HOUR FIRE RATED THROUGH PENETRATION FIRESTOP FOR SINGLE NON - METALLIC PIPE THROUGH GYPSUM WALLS USING 3M FIRESTOPPING. n OTHE 1 OR 2 HR, FIRE RATED GYPSUM BOARD /STUD WALL ASSEMBLY SHALL BE CONSTRUCTED OF THE MATERIALS AND IN THE MANNER DESCRIBED IN THE INDIVIDUAL U300 OR V400 SERIES WALL OR PARTITION DESIGN IN THE UL FIRE RESISTANCE DIRECTORY AND SHALL INCLUDE THE FOLLOWING CONSTRUCTION FEATURES: A. STUDS WALL FRAMING MAY CONSIST OF EITHER WOOD STUDS OR STEEL CHANNEL STUDS. WOOD STUDS TO CONSIST OF NOM, 2 IN. X 4 IN, LUMBER SPACED AT 16 IN. O.C. MAX. WITH NOM. 2 IN. X4 IN. LUMBER END PLATES AND CROSS BRACES. STEEL CHANNEL STUDS TO BE NOM. 35 /i IN. WIDE BY 13/8 IN. DEEP CHANNELS SPACED AT 24 IN. O.C. MAX. B. GYPSUM BOARD - 5/a IN, THICK, 4 FT. WIDE WITH TAPERED EDGES, THE GYPSUM BOARD TYPE, THICKNESS, NUMBER OF' LAYERS, FASTENER TYPE AND SHEET ORIENTATION SHALL BE AS SPECIFIED IN THE INDIVIDUAK U300 OR V400 SERIES DESIGN IN THE UL FIRE RESISTANCE DIRECTORY. MAX DIAM. OF OPENING IS 3Y8 IN, THROUGH PENETRANTS ONE NON- METALLIC PIPE OR CONDUIT TO BE CENTERED IN THE THROUGH OPENING. �J THE ANNUALR SPACE BETWEEN PIPE OR CONDUIT AND PERIPHERY OF OPENING SHALL BE A MIN; OF Y4 IN. AND MAX 3/8 IN. PIPE OR CONDUIT TO BE RIGIDLY SUPPORTED ON BOTH SIDES OF THE FLOOR- CEILING ASSEMBLY, THE FOLLOWING TYPES AND SIZES OF NON- METALLIC PIPES OR CONDUITS MAY BE USED: A. PVC PIPE - NOM. 2 IN. DIAM: (OR SMALLER) SCH. 40 SOLID CORE PVC PIPE USED IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE, OR VENT) PIPING SYSTEM. B. RIGID NON METALLIC CONDUIT - NOM. 2" DIAM. (OR SMALLER) SCH. 40 OR 80 PVC CONDUIT INSTALLED IN ACCORDANCE WITH THE ARTICLE 347 OF THE NEC (NFPA N0. 70). C. CPVC PIPE - NOM. 2 IN. DIAM. (OR SMALLER) SDR13.5 CPVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) PIPING SYSTEM. D. ccPVC PIPE - NOM. 2 IN. DIAM. (OR SMALLER) SCH 40 CELLULAR CORE PVC PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE, OR VENT) PIPING SYSTEM. E. ADS PIPE - NOM. 2 IN. DIAM. (OR SMALLER) SCH 40 SOLID CORE ADS PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE, OR VENT) PIPING SYSTEM. F. ccABS PIPE NOM. 2 in. DIAM. (OR SMALLER) SCH 40 CELLULAR CORE ADS PIPE FOR USE IN CLOSED (PROCESS OR SUPPLY) OR VENTED (DRAIN, WASTE, OR VENT) PIPING SYSTEM. FIRESTOP SYSTEM O.INSTALLED SYMETRICALLY ON BOTH SIDES OF WALL ASSMEBI_Y. THE HOURLY E AND T RATINGS FOR FIRESTOP SYSTEM ARE EQUAL TO THE HOURLY FIRE RATING OF THE WALL ASSEMBLY IN WHICH IT IS INSTALLED. THE DETAILS OF THE FIRESTOP SYSTEM SHALL BE AS FOLLOWS. A. FILL, VOID OR CAVITY MATERIALS - WRAP STRIP - NOM. Y4 IN. THICK INTUMESCENT ELASTOMERIC MATERIAL FACED ON ONE SIDE WITH ALUMINUM FOIL, SUPPLIED IN 2 IN. WIDE STRIPS. NOM. 2 IN. WIDE STRIP TIGHTLY WRAPPED AROUND NON - METALLIC PIPE (FOIL SIDE OUT) WITH SEAM BUTTED, WRAP STRIP LAYER SECURELY BOUND WITH STEEL WIRE OR ALUMINUM FOIL TAPE AND SLID INTO ANNULAR SPACE APPROX. 1Y4 IN. SUCH THAT APPROX. 3/4 IN. OF WRAP STRIP PROTRUDES FROM THE WALL SURFACE. B. FILL, VOID OR CAVITY MATERIALS - CAULK, SEALANT, OR PUTTY - MIN. 5/a IN. THICKNESS OF CAULK OR PUTTY APPLIED INTO ANNULAR SPACE BETWEEN WRAP STRIP AND PERIPHERY OF OPENING. A NOM Y4 IN. DIAM. BEAD OF CAULK OR PUTTY TO BE APPLIED TO THE WRAP STRIP /WALL INTERFACE AND TO THE EXPOSED EDGE OF THE WRAP STRIP LAYERS APPROX. 3/4 IN, FROM THE WALL SURFACE. 3M COMPANY -- CP 25WB +, IC 15WB +, FIREDAM 150+ CAULK, FB -3000 WT SEALANT, OR MP+ STIX PUTTY. (NOTE: L RATINGS APPLY ONLY WHEN CP 25WB+ CAULK IS USED. CP 25WB+ NOT SUITABLE FOR USE WITH CPVC PIPES.) C. FOIL TAPE (NOT SHOWN) NOM, 4 IN. WIDE, 3 MIL. THICK ALUMINUM TAPE WRAPPED AROUND PIPE PRIOR TO THE INSTALLATION OF THE WRAP STRIP (ITEM 3A). MIN. OF ONE WRAP, FLUSH WITH BOTH SIDES OF WALL AND PROCEEDING OUTWARD. TAPE IS NOT REQUIRED FOR PIPES SHOWN IN ITEMS 2A, 2B, AND 2C. WL -2003 9WTs s i f 3M Center F- Rating = 1 and 2 Hr St. Paul, MN 55144 T- Rating = 1 and 2 Hr 1- 800 -328 -1687 Drawing not to scale "` (See Item 3 Above) `ri's t co t`ypIl Fire penetration detail 1 OR 2 HOUR FIRE RATED ' THROUGH PENETRATION FIRESTOP FOR SINGLE METALLIC PIPE THROUGH GYPSUM WALLS USING TREMSTOP 1A. 8 w e U y 0 a N O C z J U 0 w `T • U O PRE -RATED GYPSUM WALLBOARD ZSTUD WALL ASSEMBLY METALLIC PIPE - A) STEEL PIPE - 12" DIAM. (OR SMALLER) SCH. 10 (OR HEAVIER) B) IRON PIPE - 12" DIAM. (OR SMALLER) CAST OR DUCTILE IRON PIPE. C) COPPER TUBING - 4" DIAM. (OR SMALLER) TYPE L (OR HEAVIER) COPPER TUBING. D) COPPER PIPE - 4" DIAM. (OR SMALLER) REGULAR (OR HEAVIER) COPPER PIPE. THE ANNULAR SPACE SHALL. BE MIN, 0" TO MAX. 1" WITHIN THE FIRESTOP SYSTEM. O TREMSTOP IA - MIN. 1/2" THICKNESS OF SEALANT APPLIED WITHIN OPENING. MIN. 1/4" CANT BEAD OF SEALANT TO BE APPLIED AT POINT CONTACT. WL -l158 IffMoHQD G�•S S � �cv � F- Rating = 1 and 2 Hour n n 3735 Green Rd. T- Rating = 1/4 Hour m 1 Beachwood, OH, 44122 \ Drawing not to scale 'Pis t e 0 typical fire penetration signage FIRE AND SMOKE I':>_ BARRIER, PROTECT & ' OPENINGS GENERAL NOTE: (r.r.N.c. SEUIIUN b- 6.2.4) (F.B.C. SECTION 712.6) 1. EACH NEW /EXISTING FIRE WALL, FIRE BARRIER, FIRE PARTITION, SMOKE BARRIER, SMOKE PARTITION, OR ANY NEW /EXISTING WALL REQUIRED TO HAVE PROTECTED OPENINGS SHALL BE EFFECTIVELY AND PERMANENTLY IDENTIFIED WITH SIGNS OR STENCILING ABOVE ANY DECORATIVE CEILING AND IN ALL CONCEALED SPACES WITH THE- WORDING "FIRE AN "D SMOKE BARRIER - PROTECT ALL OPENINGS" OR SIMILAR LANGUAGE. SUCH SIGNS OR STENCILING SHALL BE PROVIDED WITH 4" IN. 11IGH LETTERS, AND 1/2" IN. STROKE, AND NOT MORE THAN 15' FEET ON- CENTER. SUCH SIGNS OR STENCILING SHALL BE PROVIDED WITH RED LETTERING AND PROVIDED ON BOTH SIDES OF SAID ASSFMBLIES. Gab 1. APPLICABLE CODES (F.B.C.) FLORIDA BUILDING CODE 2010 - WITH LATEST SUPPLEMENTS (F. 5. C. E.) FLORIDA BUILDING CODE 2010 EXISTING -- WITH LATEST SUPPLEMENTS (F.F.P.C.) FLORIDA FIRE PREVENTION CODE 2010 - WITH LATEST SUPPLEMENTS (N.F.P.A.) LIFE SAFETY CODE HANDBOOK - LATEST EDITION (F.A.C.) FLORIDA ACCESSIBILITY CODE FOR BLDG. CONSTRUCTION (N.F.P.A. -10) STANDARD FOR PORTABLE FIRE EXTINGUISHERS 2. CLASSIFICATION OF WORK ALTERATION LEVEL ALTERATION LEVEL 2 (F.B.C.E. SECTION 404.1) SCOPE - LEVEL 2 ALTERATIONS INCLUDE THE RECONFIGURATION OF SPAEF, THE ADDITION OR ELIMINATION OF ANY DOOR OR WINDOW, THE RECONFIGURATION OR EXTENSION OF ANY SYSTEM, OR THE INSTALLATION OF ANY ADDITIONAL_ EQUIPMENT. MODIFICATION : (F.F.P.0 43.1 , 43.2.2.1.3') THE RECONFIGURATION OF ANY SPACE ,THE ADDITION, RELOCATION, OR ELIMINATION OF ANY DOOR OR WINDOW THE ADDITION OF LOAD GEARING ELEMENTS ,THE RECONFICURATIO OR EXTENSION OF ANY SYSTEM OR THE INSTALLATION OF ADDITIONAL. EQUIPMENT. 1 3, CATEGORY OF REHABILITATION : (F.F.P.0 NFPA 101, 43.2.2.1.4) RECONSTRUCTION : THE RECONFICURATION OF A SPACE THAT AFFECTS AN EXIT OR A CORRIDOR SHARED BY MORE THAN ONE OCCUPANT SPACE; OR THE RECONFIGURATION OF A SPACE SUCH THAT THE REHABILITATION WORK AREA IS NOT PERMITTED TO BE OCCUPIED 13ECAUSF EXISTING MEANS OF EGRESS AND FIRE PROTECTION SYSTEMS, OR THEIR EQUIVALENT, ARE NOT IN PLACE OR CONTINUOUSLY MAINTAINED. 4. OCCUPANCY CLASSIFICATION (F.B.C. SECTION 303, F.( P.C. CH. 12 - NEW ASSEMBLY) GROUP A2 - ASSEMBLY 5. REQUIRED SEPARATION OF OCCUPANCIES _- (F.B.C. TABLE 508.3.3, F.F.P.0 TABLE 6.1 .14.4.1 (b) GROUP A -2 - ASSEMBLY WITH GROUP A (ASSEMBLY) = 1 HOUR (SPRINKLERED) WITH GROUP B (BUSINESS) = 1 HOUR (SPRINKLERED) WITH GROUP M (MERCANTILE) = 1 HOUR (SPRINKLERED) 6. APPROVED AUTOMATIC SPRINKLER SYSTEM : (F.F.P.C. SECTION 9.7.1 ) PROVIDED - EXISTING TO BE ADAPTED TO NEW LAYOUT 7. EIRE ALARM SYSTEM : (F.F.P.C. SECTION 12.3.4) NOT REQUIRED FOR ASSEMBLY OCCUPANCY WITH LESS THAN 300 OCCUPANTS 8. OCCUPANT LOAD (F.B.C. TABLE 1004.1.1, F.F.P.C, TABLE 7.3.1.2 & CH. 12.1.7.1.1) GROUP A -2 - ASSEMBLY NON FIXED SEATS TABLE CHAIRS INDOOR 845 SE /15 SF, NET PER OCC: = 57 OCC. OUTDOOR 189 SF /15 SF. NET PER OCC 18 OCC, FIXED SEATS: BANQUETTES 268" L.I. /18" GROSS PER OCC. 15 OCC. BOOTH (N /A) STORAGE (COOLER) 102 SF / 300 GROSS PER OCC. = 1 OCC. STORAGE 80 SF / 300 GROSS PER OCC. = 1 OCC. KITCHEN /ORDER COUNTER 738 SF / 100 GROSS PER OCC. - 4 OCC. OFFICE 42 SF-/ 1 00 GROSS PER OCC. = 1 OCC, TOTAL NUMBER OF OCCUPANTS - 97 OCC. 9. EXIT AND EXIT ACCESS DOORWAYS : (F.B.C. SECTION 1015, F.F.P.C. SECTION 7.4 do 12.2.4) GROUP A -2 TENANT SPACE EXITS REQUIRED = 2 EXIT TENANT SPACE EXITS PROVIDED = 2 EXIT 10. EGRESS WIDTH PER OCCUPANT REQUIRED : (F.B.C. TABLE 1005.1 , F.E P.C. SECTION 7.2.1.2) GROUP A -2 = 0.2 /00C. TENANT SPACE = 97 TOTAL OCC. (X) 0.2 /OCC. = 20 INCHES REQUIRED 2 DOOR PROVIDED = 10 INCHES EACH 2 DOORS AT 34 INCHES EACH = 68 INCHES PROVIDED = 68 TOTAL INCHES PROVIDED 11. COMMON PATH OF EGRESS TRAVEL ALLOWED : (F,B.C. SECTION 1014.3, EXCEPTION 5) (F.F.P.C. SECTION 12.2.5.1.2) GROUP A -2 = 20 FEET ALLOWED 12, MINIMUM AISLE EGRESS WIDTH ALLOWED : (F.B.C. SECTION 1014.4, F.F.P.C. SECTION 12.2.3.8) GROUP A - 44' INCHES 13, EGRESS ACCESS TRAVEL DISTANCE ALLOWED : (F.B.C. TABLE 101 6.1 , F.F.P.C. SECT. 1 2.2.6) GROUP A -2 WITH APPROVED AUTOMATIC SPRINKLER SYSTEM - 250 FEET ALLOWED 14. MINIMUM INTERIOR FINISH FLAME SPREAD do SMOKE DEVELOPMENT CLASSIFICATION REQUIREMENT: (F.B.C. TABLE 803.5, 804.4.1, F.F.P.C. SECTION 12.3.3) GROUP A -2 - WITH APPROVED AUTOMATIC SPRINKLER SYSTEM WALLS do CEILINGS FINISH : VERTICAL EXITS AND EXIT PASSACEWAYS = CLASS "B" EXIT ACCESS CORRIDORS AND OTHER EXIT WAYS - CLASS "B" ROOMS AND ENCLOSED SPACES - CLASS "C" FLOORS FINISH : EXIT ENCLOSURES - CLASS "II" EXIT PASSAGEWAYS = CLASS "II" CORRIDORS = CLASS "II" 15. CLASSIFICATION OE HAZARD : (N.F.P.A. 10 SECTION 1-5) ORDINARY (MODERATE) HAZARD (N.F.P.A. 10 SECTION 1-5.2) MINIMUM RATED SINGLE EXTINGUISHER = 22A MAXIMUM FLOOR AREA PER UNIT OF A = 1500 SF MAXIMUM FLOOR AREA FOR EXTINGUISHER = 11,250 SF MAXIMUM TRAVEL DISTANCE TO EXTINGUISHER = 75 FEET 16, FIRE EXTINGUISHER SPECIFICATION MANUFACTURER LARSENS SERIES : MP- SERIES /MULTI PURPOSE DRY CHEMICAL MODEL NO MP5 (UL RATING 2A- 10B:C) BRACKET PROVIDE STANDARD BRACKET OPTION (� 1 521) "K" CLASS EXTINGUISHER WITH SIGNS SHALL BE MOON ED NEXT TO THE HOOD PULL STATION. / i F.B.C. PLUMBING CHAPTER 4 TABLE 403.1. : CLASSIFICATION A -2 NIGHTCLUBS, BARS, TAVERNS, DANCE HALLS AND BUILDINGS FOR SIMILAR PURPOSES (INCLUDES OUTDOOR SEATING OCCUPANTS) TOTAL NUMBER OF OCCUPANTS = 97 OCC. (49 MALE / 49 FEMALE) REQUIRED 4U/ /�D = U.bb 4y/ 13 = U.00 'r�1/ zvu PROVIDED 1 1 1 1 WATER SERVED AT TABLE (a) 1 a. E.B.G""__ PLUMBING SECTION 410.1 : WHERE WATER IS SERVED IN RESTAURANTS, DRINKING FOUNTAINS SHALL NOT BE REQUIRED. In F.B.C. PLUMBING SECTION 419.2 URINALS : SUBSTITUTION FOR WATER CLOSETS. IN EACH BATHROOM OR TOILET ROOM, URINALS r w r U) t U w of IL W 0 LL n w �J �J to Z2 in w° N w�n Z of O0 z Lj jo a mt cD Z N Ln 00; T-4 00 Ln ` 00 r_1 e • • N 0/0� rt.,D.0- W �0 - � h ` ` a e a 0 � LU O> EQ 0.L oo C* 0 V CULn° LL E �: LLJ E 0 Ln M O� -0oU� Q 0 V I- nw)�'Fa+►a'� EZSe _� M � •• 4 - IJ x � � t i" •, h ,� ,C • a ?1 • �. �_ ��1 r.'� 2LL ROBERT K. MORISETTE, AIA, NCARB, LEED AP BD+C, CDP LL FLORIDA REGISTERED ARCHITECT # AR +53259 zw wU zz o° Ut Zo WZ t RZ 3:° LU fy w o= a-Z =o rx °cn wC)Z J ° °W ?n a O U w n 0 r 0 Z L0 x a W IL ." • Y y Y • y y age, • • Y • • • Y • W w J y *Do O o • uy • J � y Vy Y • • V LL � y y • V y IG+ • y V VY •' ` U J J • Y v • L • • T_ • y . v) • • • ° ° s y v w Y V••• F r w r U) t U w of IL W 0 LL n w �J �J to Z2 in w° N w�n Z of O0 z Lj jo a mt cD Z N Ln 00; T-4 00 Ln ` 00 r_1 e • • N 0/0� rt.,D.0- W �0 - � h ` ` a e a 0 � LU O> EQ 0.L oo C* 0 V CULn° LL E �: LLJ E 0 Ln M O� -0oU� Q 0 V I- nw)�'Fa+►a'� EZSe _� M � •• 4 - IJ x � � t i" •, h ,� ,C • a ?1 • �. �_ ��1 r.'� 2LL ROBERT K. MORISETTE, AIA, NCARB, LEED AP BD+C, CDP LL FLORIDA REGISTERED ARCHITECT # AR +53259 zw wU zz o° Ut Zo WZ t RZ 3:° LU fy w o= a-Z =o rx °cn wC)Z J ° °W ?n a O U w n 0 r 0 Z L0 x a W IL LIFE SAFETY PLAN & CODE ANALYSIS #13005 As Shown Icz 301 September 23, 2013 • PERMIT SETS v f,yA4 � cn r r c ." / d\ 4 n m e Mn9 7 LIFE SAFETY PLAN & CODE ANALYSIS #13005 As Shown Icz 301 September 23, 2013 • PERMIT SETS v f,yA4 � cn r r c