12-528-004AIR CONDITIONING SYSTEM - GENERAL NOTES 1. DUCTWORK SHALL BE 1.5" THICK. 3 POUNDS PER CUBIC FOOT DENSITY FIBERGLASS WITH VAPOR BARRIERS. UNLESS OTHERWISE SPECIFIED .DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH WITH MANUFACTURER'S SPECIFICATIONS AND ACCORDING TO "ASHRAE" & "SMACNA" STANDARDS. DUCT DIMENSIONS ARE IN INCHES AND CORRESPOND TO INSIDE DIMENSIONS WIDTH X HEIGHT. DUCT SYSTEM SHALL COMPLY W/ "NFPA" STD. N0.90A AND /OR 908. DUCTWORK AND COMPONENTS SHALL BE CLASS 1 MATERIALS IN ACCORDANCE WITH U.L. 181 TESTS. 2. COORDINATE LOCATIONS,SIZES & OPENINGS W /OTHER TRADES ON THE JOB. A/C CONTRACTOR SHALL PROVIDE THE COMPLETE DUCT SYSTEM W/TURNING VANES AT ALL ELBOWS,SPUTTERS & DAMPERS, AS REQUIRED. 3. DIFFUSERS SHALL BE SELECTED,LOCATED AND BALANCED IN ORDER THATTHEY DELIVER THE REQUIRED CFM TO THE ENTIRE ROOM EVENLY & DRAFT FREE TO MANTAIN THE FOLLOWING DESIGN CONDITIONS: INSIDE OUTSIDE RELATIVE HUMIDITY COOLING -78 DB 91 DB - 78 DB 50% TO 60% HEATING - 72 DB 45 DB 4. ALL FAN UNIIS,MOTORS,COMPRESSORS, ETC. SHALL BE ISOLATED, AS REQUIRED TO OPERATE QUIETLY SO THAT NO OBJECTIONABLE SOUND WILL BE HEARD IN THE HABITABLE SPACES DUE TO AIR VELOCITY,MOTOR HUMNIBRATION,OR MECHANICAL MOVEMENT. 5. A/C SYSTEM SHALL HAVE DISPOSABLE AIR FILTERS LOCATED AS REQUIRED FOR EASY ACCESIBILITY. 6. A/C SYSTEM SHALL BE CONTROLED BY A THERMOSTAT,MOUNT THERMOSTAT 5' -0" ABOVE FINISHED FLOOR.U.O.N. 7. ALL GRILLES & DIFFUSERS TO BE ALUMINUM OR PLASTIC CONSTRUCTION.DIFFUSERS SHALL HAVE HIDDEN OPOSSED BLADE DAMPERSYROVIDE GASKETS ON ALL GRILLES & DIFFUSERS. TITUS OR AIREGUIDE FINISHED COLOR BY ARCHITECT. 8. UNDERCUTS DOORS , 1" A.F.F. AS INDICATED.ZP 9. PROVIDE FLOAT SWITCH ON EACH AUXILIARY DRAIN PAN. SWITCH TO TURN SYSTEM OFF WHENEVER THERE IS WATER IN AUXILIARY DRAIN PAN. 10. UNDERGROUND CONDENSATE DRAIN LINE SHALL BE 2 INCHES DIA. MINIMUM 11. ALL EXHAUST DUCTS SHALL BE CONSTRUCTED OF SHEET METAL, TERMINATE OUTSIDE THE BUILDING, AND BE EQUIPPED WIHT A BACKDRAFT DAMPER 12. DUCTS FROM "TOILET ROOMS" SHALL DISCHARGE TO THE OUTSIDE OF BUILDING, SHALL BE TERMINATED NOT LESS THAN 6 INCHES ABOVE THE FINISHED ROOF SURFACE, AND SHALL BE SCREENED WITH A CORROSION RESISTANT CORROSION RESISTANT MATERIAL HAVING A MESH SIZE NOT LARGER THAN 1/2 INCHES 13. CLOTHES DRYERS EXHAUST DUCTS (OR VENTS ) SHALL COMPLY WITH MANUFACTURER'S INSTALLATION INSTRUCTION, BE CONSTRUCTED OF A MINIMUM 26 GAUGE METAL PIPE,HAVING A SMOOTH INTERIOR SURFACE WITH JOINTS RUNNING IN THE DIRECTION OF THE AIR FLOW. DUCT JOINTS SHALL NOT BE ASSEMBLED WITH SHEET METAL SCREWS OR OTHER WHICH WOULD EXTEND INTO THE DUCT 14. CLOTHES DRYER EXHAUST DUCT SHALL " NOT " BE SCREENED EXHAUST FAN BRACKET (ADJUSTABHANGING E) UNDERCUTS DOORS 1" A.F.F AC FLOOR PLAN 1/4 " ROOF STRUCTURE SEE ARCHITECTURAL 4 -16d NAILS THRU PLYWOOD DUCT FROM UNIT 4" DIAM. GALVANIZED STEEL GAGE No 30 4" DIAM. EXHAUST DUCT STEEL HANGER WIRE TYPICAL CEILING CABINET EXHAUST FAN W/ BACKDRAFT DAMPER LOW NOISE LEVEL AND NO VIBRATION FRONT FACE GRILLE W/ FASTENING SCREENS PROVIDE W /P. CAP LOW PROFILE B.D.D. AT TOP FOR DRYER NO SCREEN. FOR BATHROOM PROVIDE INSECT SCREEN • co WALL TYPICAL ROOF CA' DETAIL A DRYER AND/OR TOILET EXH. ND.DRAIN VE GRADE CU SPLIT SYSTEM SCHEDULE UNIT NO. DUCT SMOKE DETECTOR 1 TOTAL CAPACITY BTU /HR 475000 SENS CAPACITY BTU /HR 36250 CFM SUPPLY FIRE RATED ENCLOSURE 1600 CFM 0 /AIR FIRE RATED ROOF CEILING ASSEMBLY - HEATER KW FIRE STOPPING 7.5 ESP -IN WG. SMOKE CONTROL 0.30 TEMP. AIR ENT. COIL DB /WB 80/76 C.U. FLA z 19.3 VOLTAGE 1 -60 -240 MANUFACTURER RHEEM AHU MODEL RBHM25J1ISMS C.U. MODEL RARL048JAZ SEER /EER 16.0 LIQUID /SUCTION SIZE -IN 3/8 "- 7/8" ELBOW & ASSEMBLY 4" 4" 4" 4" MI MIN METAL SEAT (SEE ELEV.) —7 A/C DISC. TYPICAL A/C PLAN CLASS 1. R -6 CONDENSING UNI MAINTAIN 1' -0 "_ CLEAR FOR WALL FASTEN CU T0------ CON. PAD AS PER M.F.R SPEC'S TO WITHSTAND 146 M.P.H WINDS (1/2- BOLTS 3" LG EMBED IN THE CONC. EA. SIDE) CELING 26 MSG,1 1/2' W GALV. STRAPS R -6 FLEXIBLE DUCTS 48" C/C & 0 ON ONE INCH THK EV RY ELBOW 6" WIDE W f HIT) REDHEADS FIBERGLASS SADDLES 0 1 4 SCREWS ATTACHED TO T USSES /SLAB DUCT SUPPORT DETAIL NOTE: FLEXIBLE DUCTS SHALL BE INSTALED WITHOUT KINKS OR SAGGING HVAC DESIGN REQUIRES: YES NO DUCT SMOKE DETECTOR HP CFM ®" S,p, FIRE DAMPER(S) DIMENSIONS WxLxH (IN.) WEIGHT LBS. SMOKE DAMPER(S) EX. TOILET FAN ✓ FIRE RATED ENCLOSURE 1/90 ✓ FIRE RATED ROOF CEILING ASSEMBLY 10 x 10 x 6 6 FIRE STOPPING �.t SMOKE CONTROL LLJ N In i r_nr_Kin a E.F. EXHAUST FAN ® CEILNG DIFFUSER FLEXIBLE DUCT RIGID DUCT Q PROG. THERMOSTAT FAN SCHEDULE FAN # MANUFACTURER AND MODEL N0. RPM HP CFM ®" S,p, ELECT. SERVICE VOLTS /PH/Hz DIMENSIONS WxLxH (IN.) WEIGHT LBS. REMARKS EX. TOILET FAN NUTONE QT -80 1500 1/90 70 0 1/8" 115/l/60 10 x 10 x 6 6 DAMPER GRILLE, & ROOF CAP �.t o LLJ N In Of Ld U) z 3/4 "0 PV DRAIN W/ USE 1/4" CABLES CROSSED OVER THE UNIT FASTENED TO THE PAD SUPPORT dOWER AND CONTROL CONNECTIONS 6" MIN. ZS� 00 6" MIN. 6" MIN LIQUID LINE W/O INSULATION CONCRETE BASE W/ 6X6 - 10/10 WWF SEAL ENTRANCE OF REFRIGERANT LINES INTO P.V.C. PIPE W/ UNIT MUST BE INSTALED TO IMPERMEABLE, RESILIENT MATERIAL WITHSTAND 150 MPH HURRICANE FORCE WINDS CONDENSING UNIT MOUNTING INSTALLATION OF ALL EXTERIOR C/U AT GROUND LEVEL IN SINGLE FAMILY, DUPLEX AND FEE SIMPLE TOWNHOUSES IN UNINCORPORATED MIAMI -DADE COUNTY SHALL BE ANCHORED TO THE CONCRETE SLAB ON THE INSIDE OF THE UNIT, WITH AN ANCHOR BOLT OF 500 LBS MINIMUM PULL CAPACITY GFM CLOSURE 2 1/2" SQUARE WASHERS 12" MAX. O.0 2 PER SIDE #10X1 1/4" SHEET METAL SCREWS FIROUS GLASS DUCT FLANGE 22 GA SHEET METAL � SCREW POP RIVET 1'X3" OR SPOT WELD TO EQUIPMENT FLANGE AHU CONNECTION TO S/A PLENUM MECHANICALLY ATTACHED ALSO 4" AROUND CLOSET TO OUTSIDE AHU ELEVATION SCHEME N TS 6" SCHAEDULE 40 P.V.0 PIPE INCREASE SIZE AS REQUIRED BY LENGHT AND ROUTING SUCTION LINE W/ 1 -1/ ARMAFLEX INSULATION DETAIL INES TO COND. UNIT HUNG FROM ASG, 1 1/2" STRAPS )MODE PIPE SHIELDS MIN. 48" C/C INSULATION L LOUVERED DOOR )OD AHU SUPPORT (SELF— STANDING) T_I__N otr)rnu7 Z10,0 J O Il-1 of OZ 0) V) O a 0 tn E I � a = IZ N W O 1 REVISIONI: REVISION2 REVISION3 REVISION4 SHEET mi LL_ ° LLJ Q W z Z W U Ld 0 W Cy- � ::E < Ld Ld W � �.t o LLJ N In Of Ld U) z o U7 (.0 REVISIONI: REVISION2 REVISION3 REVISION4 SHEET mi LL_ ° LLJ Q 0U� z Z W U Ld 0 W Cy- � ::E Ld Ld W � V J o LLJ N In Of Ld U) z o U7 (.0 REVISIONI: REVISION2 REVISION3 REVISION4 SHEET mi