15-334-005I m
1- ALL WORK SHALL BE PERFORMED TO MEET THE REQUIREMENTS OF THE GOVERNING
EDITION OF THE NATIONAL ELECTRICAL CODE (N.E.C), LOCAL AND STATE CODES
AND ANY OTHER APPLICABLE CODES AND STANDARDS.
2- ALL WIRING SHALL BE COPPER (CU) THWN INSULATION.
IF ALUMINUM WIRES ARE USED:
A) TO PREVENT OVERHEATING AT CONNECTION POINTS USE OXIDE INHIBITING COMPOUND
FOR STRIPPED PORTION OF CONDUCTORS INSIDE CONNECTORS.
B) A PREVENTIVE MAINTENANCE PLAN IS NECESSARY TO ENSURE A RELIABLE SERVICE
INCLUDING VISUAL INSPECTIONS AND TESTS FOR SPLICES AND CONNECTION POINTS
(CORROSION AND TIGHTNESS PRINCIPALLY).
INSPECTION INTERVALS OF 2 YEARS MAXIMUM ARE STRONGLY RECOMMENDED.
3 ALL CIRCUIT BREAKERS AND DISCONNECTS SHALL BE RATED AT MINIMUM OF 10,000 AIC.
4- PRIOR TO INSTALLATION OF ROUGH ELECTRICAL WIRING, CHECK NAMEPLATE
DATA OF ALL EQUIPMENT FOR REQUIRED VOLTAGES, MINIMUM CIRCUIT AMPACITY,
AND OVERCURRENT PROTECTION.
5- ELECTRICAL CALCULATIONS WERE BASED ON INFORMATION PROVIDED BY
ELECTRICAL CONTRACTOR AND /OR OWNER AGENT. ELECTRICAL CONTRACTOR
TO VERIFY LOAD FOR EACH CIRCUIT AND ADJUST ACCORDINGLY, CHANGES
TO BE REFLECTED IN THE DRAWINGS.
6- ALL BRANCH CIRCUITS SHALL BE PROPERLY PHASE BALANCED.
7- ALL NEW CONDUCTORS SHALL BE RUN IN CONDUIT (METALLIC TYPE) UNLESS
OTHER TYPES CAN BE USED AS PER NEC:
-PVC SCH. 40 WHEN INSTALLED 12" UNDER SLABS ON GRADE OR WHEN EMBEDDED
IN CONCRETE WALLS OR SLABS.
-NM, NMC, NMS (NONMETALLIC SHEATHED CABLE) CAN BE INSTALLED ACCORDING TO NEC
334 -10 AND 334 -12.
8- IF PVC CONDUITS ARE USED FOR FEEDERS, A GROUNDING
CONDUCTOR SIZED IN ACCORDANCE WITH N.E.C. 250 - 122 MUST
BE INSTALLED AND CONDUIT SIZE INCREASED AS REQUIRED.
9- TYPEWRITTEN PANEL TALLY SHALL BE FURNISHED AFTER JOB IS
COMPLETED REFLECTING ALL CHANGES AND ADDITIONS.
10- THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL
CONTRACTOR FOR INSTALLATION OF NEW MECHANICAL EQUIPMENT.
11-- THIS DRAWING IS A GUIDE FOR THE INSTALLATION OF ELECTRICAL
SERVICE. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE A
FUNCTIONING SYSTEM.
12- THE ELECTRICAL DESIGN IS BASED UPON THE AVAILABLE INFORMATION AT DESIGN TIME
AND THE CONTRACTOR SHALL REVIEW NAMEPLATE DATA AND MANUFACTURER SUPPLIED
LITERATURE FOR ALL PIECES OF EQUIPMENT PRIOR TO ROUGH ELECTRICAL WIRING.
THE CONTRACTOR SHALL CHECK ALL EQUIPMENT FOR PROPER VOLTAGE, PHASE AND
AMP RATING PRIOR TO INSTALLATION. THE CONTRACTOR SHALL CONTACT ENGINEER
PRIOR TO ANY FIELD ADJUSTMENT.
13- NEW OUTLETS IN OPPOSITE SIDES ON FIRE RATED WALLS TO BE 24" HORZ. APART (MIN).
AND FIRE PROTECTED.
14- CONTRACTOR TO VERIFY ADJUSTMENT FACTORS FOR MORE THAN THREE
CURRENT- CARRYING CONDUCTORS IN A CONDUIT ACCORDING TO
TABLE 310- 15(b)(2)(a) NEC.
15- ALL SMOKE OR CARBON MONOXIDE DETECTORS TO BE LOCATED 3' APART MIN. FROM
A/C OUTLETS AND INTERCONNECTED FOR SIGNALING PURPOSE. CARBON MONOXIDE
DETECTORS TO BE LOCATED 10' MAXIMUM FROM ANY SLEEPING AREA.
16- ELECTRICAL CONTRACTOR TO VERIFY EXISTING CONDITIONS AND CODE VIOLATIONS TO FIX.
17- ALL NEW RECEPTACLES SPECIFIED IN NEC 210.8, 120 V, 15 OR 20 AMPS, SHALL HAVE GROUND
FAULT CIRCUIT INTERRUPTER PROTECTION (GFCI PROTECTION).
18- ALL NEW 120 V, SINGLE PHASE 15 OR 20 AMPS BRANCH CIRCUITS SPECIFIED IN NEC 210.12 (B)
SHALL RE PROTECTED BY AFCI BREAKERS... ELECTRICAL PLAN
19- ALL NEW RECEPTACLES SPECIFIED IN NEC .210.52, 120 V, 15 OR 20 AMPS, SHALL BE LISTED
TAMPER- RESISTANT RECEPTACLES (NEC 406.11).
20- NOT USED
21- ELECTRICAL CONTRACTOR TO FIELD VERIFY BRANCH CIRCUIT, POSITION AN CONNECTION.
ALL PANELS SHALL HAVE UPDATED BRANCH CIRCUITS LABELS.
CONTRACTOR SHALL VERIFY ACCEPTABILITY AND GOOD CONDITIONS OF EXISTING FEEDER CABLE,
OCP, EXISTING ELECTRICAL PANELS AND BUS BAR CLEANING. ELECTRICAL ENGINEER AND
ARCHITECT SHALL BE NOTIFIED ANY CHANGE
22- ALL CIRCUIT BREAKERS AND FUSES SHALL BE ON THE TIME RELEASED TYPE
UNLESS OTHERWISE NOTED.
23- NON - LOCKING RECEPTACLES IN DAMP AND WET LOCATIONS SHALL BE
LISTED WEATHER RESISTANT TYPE WITH A WEATHER PROOF ENCLOSURE OXIDE INSIDE HOUSE
AS PER NEC 406.8 (A) k (B).
24- THE ELECTRICAL SYSTEM SHALL BE COMPLETELY AND EFFECTIVELY
GROUNDED PER NEC REQUIREMENTS AND STATE AND LOCAL CODE REQUIREMENTS.
WEATHER HEAD
25- CONTRACTOR TO VERIFY OUTLET BOXES FOR LIGHTING FIXTURES (PENDANT LIGHTS) OR ELECTRICAL SERVICE
CEILING FANS ACCORDING TO FIXTURE WEIGHT TO COMPLY WITH NEC 314.27. CONDUCTORS
26- NOT USED FROM FPL TXR
(EXISTING) .
27- ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ARCHITEC /OWNER TO FIELD VERIFY
INSTALLATION FOR OUTLETS, LIGHTING FIXTURES AND ELECTRICAL EQUIPMENT.
(1)
ELECTRICAL PNL "A" S1
SCOPE OF WORK Mca 10 zFo1 A
PROVIDE POWER AND LIGHTING FOR REMODELED EXISTING 240/120 V
AREA IN EXISTING DWELLING UNIT. METER 1 PH, 3 W
— PROVIDE POWER FOR NEW A/C UNIT (SEE MECH. EXISTING
PLAN).
EXISTING ELECTRICAL SERVICE TO REMAIN.
EXISTING ELECTRICAL PNL "A" TO. REMAIN.
� �. • • � tea h'
. •.qua WY• �[ •t1 uir •];,;. •�J s FY
REVISIONS:t"',
• •
• +
+ V RE.V.1. • U • k'
�,� ..•�; �`r
'ElNTS
REV.2
• i 6 �
� x_wJt t
t
r
• Y
set
� $
`
h�l
. �
J�
fix;'
wx.
. W oW ,
t,
,..
Z t
N— IN
W' coI�
JoIX
Z
�Wm`�
N_ `°
J ��`
< Z
Z
h � �
uj
k.
y$ i
t
�o
Z
0'
0
O,`,.`
�ea
vi'Y'k
( *)— PROVIDE #10 EG CONDUCTOR
ELECTRICAL LEGENDy ry
i KEY PLAN � � A �f 0
0 "L C
ELECTRICAL RISER DIAGRAM
�,� ..•�; �`r
'ElNTS
�'��i AL ESC' `%
fill
N
�
r
`
h�l
J�
Z
0'
0
O,`,.`
�ea
i KEY PLAN � � A �f 0
0 "L C
ELECTRICAL RISER DIAGRAM
�,� ..•�; �`r
'ElNTS
�'��i AL ESC' `%
fill
N
�
r
N
�
p