13-319-005ELECTRICAL NOTES 1- ALL WORK SHALL BE PERFORMED TO MEET THE REQUIREMENTS OF THE GOVERNING EDITION OF THE NATIONAL ELECTRICAL CODE (N.E.C), LOCAL AND STATE CODES AND ANY OTHER APPLICABLE CODES AND STANDARDS. 2- ALL WIRING SHALL BE COPPER (CU) THWN INSULATION. IF ALUMINUM WIRES ARE USED: A) TO PREVENT OVERHEATING AT CONNECTION POINTS USE OXIDE INHIBITING COMPOUND FOR STRIPPED PORTION OF CONDUCTORS INSIDE CONNECTORS. B) A PREVENTIVE MAINTENANCE PLAN IS NECESSARY TO ENSURE A RELIABLE SERVICE INCLUDING VISUAL INSPECTIONS AND TESTS FOR SPLICES AND CONNECTION POINTS (CORROSION AND TIGHTNESS PRINCIPALLY). INSPECTION INTERVALS OF 2 YEARS MAXIMUM ARE STRONGLY RECOMMENDED. 3- ALL CIRCUIT BREAKERS AND DISCONNECTS SHALL BE RATED AT MINIMUM OF 10,000 AIC. 4- PRIOR TO INSTALLATION OF ROUGH ELECTRICAL WIRING, CHECK NAMEPLATE DATA OF ALL EQUIPMENT FOR REQUIRED VOLTAGES, MINIMUM CIRCUIT AMPACITY, AND OVERCURRENT PROTECTION. 5- ELECTRICAL CALCULATIONS WERE BASED ON INFORMATION PROVIDED BY ELECTRICAL CONTRACTOR AND /OR OWNER AGENT. ELECTRICAL CONTRACTOR TO VERIFY LOAD FOR EACH CIRCUIT AND ADJUST ACCORDINGLY, CHANGES TO BE REFLECTED IN THE DRAWINGS. 6- ALL BRANCH CIRCUITS SHALL BE PROPERLY PHASE BALANCED. 7- ALL NEW CONDUCTORS SHALL BE RUN IN CONDUIT (METALLIC TYPE) UNLESS OTHER TYPES CAN BE USED AS PER NEC: -PVC SCH. 40 WHEN INSTALLED 12" UNDER SLABS ON GRADE OR WHEN EMBEDDED IN CONCRETE WALLS OR SLABS. -NM, NMC, NMS (NONMETALLIC SHEATHED CABLE) CAN BE INSTALLED ACCORDING TO NEC 334 -10 AND 334 -12. 8- IF PVC CONDUITS ARE USED FOR FEEDERS, A GROUNDING CONDUCTOR SIZED IN ACCORDANCE WITH N.E.C. 250 - 122 MUST BE INSTALLED AND CONDUIT SIZE INCREASED AS REQUIRED. 9- TYPEWRITTEN PANEL TALLY SHALL BE FURNISHED AFTER JOB IS COMPLETED REFLECTING ALL CHANGES AND ADDITIONS. 10- THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH THE MECHANICAL CONTRACTOR FOR INSTALLATION OF NEW MECHANICAL EQUIPMENT. 11- THIS DRAWING IS A GUIDE FOR THE INSTALLATION OF ELECTRICAL SERVICE. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE A FUNCTIONING SYSTEM. 12- THE ELECTRICAL DESIGN IS BASED UPON THE AVAILABLE INFORMATION AT DESIGN TIME AND THE CONTRACTOR SHALL REVIEW NAMEPLATE DATA AND MANUFACTURER SUPPLIED LITERATURE FOR ALL PIECES OF EQUIPMENT PRIOR TO ROUGH ELECTRICAL WIRING. THE CONTRACTOR SHALL CHECK ALL EQUIPMENT FOR PROPER VOLTAGE, PHASE AND AMP RATING PRIOR TO INSTALLATION. THE CONTRACTOR SHALL CONTACT ENGINEER PRIOR TO ANY FIELD ADJUSTMENT. 13- NEW OUTLETS IN OPPOSITE SIDES ON FIRE RATED WALLS TO BE 24" HORZ. APART (MIN). AND FIRE PROTECTED. 14- CONTRACTOR TO VERIFY ADJUSTMENT FACTORS FOR MORE THAN THREE CURRENT - CARRYING CONDUCTORS IN A CONDUIT ACCORDING TO TABLE 310- 15(b)(2)(a) NEC. 15- ALL SMOKE OR CARBON MONOXIDE DETECTORS TO BE LOCATED 3' APART MIN. FROM A/C OUTLETS AND INTERCONNECTED FOR SIGNALING PURPOSE. CARBON MONOXIDE DETECTORS TO BE LOCATED 10' MAXIMUM FROM ANY SLEEPING AREA. 16- ELECTRICAL CONTRACTOR TO VERIFY EXISTING CONDITIONS AND CODE VIOLATIONS TO FIX. 17- ALL NEW RECEPTACLES SPECIFIED IN NEC 210.8, 120 V. 15 OR 20 AMPS, SHALL HAVE GROUND FAULT CIRCUIT INTERRUPTER PROTECTION (GFCI PROTECTION). 18- ALL NEW 120 V, SINGLE PHASE 15 OR 20 AMPS BRANCH CIRCUITS SPECIFIED IN NEC 210.12 (B) SHALL BE PROTECTED BY AFCI BREAKERS. 19- ALL NEW RECEPTACLES SPECIFIED IN NEC 210.52, 120 V, 15 OR 20 AMPS, SHALL BE LISTED TAMPER - RESISTANT RECEPTACLES (NEC 406.11). 20- NOT USED 21- ELECTRICAL CONTRACTOR TO FIELD VERIFY BRANCH CIRCUIT, POSITION AN CONNECTION. ALL PANELS SHALL HAVE UPDATED BRANCH CIRCUITS LABELS. CONTRACTOR SHALL VERIFY ACCEPTABILITY AND GOOD CONDITIONS OF EXISTING FEEDER CABLE, OCP, EXISTING ELECTRICAL PANELS AND BUS BAR CLEANING. ELECTRICAL ENGINEER AND ARCHITECT SHALL BE NOTIFIED ANY CHANGE 22- ALL CIRCUIT BREAKERS AND FUSES SHALL BE ON THE TIME RELEASED TYPE UNLESS OTHERWISE NOTED. 23- NON- LOCKING RECEPTACLES IN DAMP AND WET LOCATIONS SHALL BE LISTED WEATHER RESISTANT TYPE WITH A WEATHER PROOF ENCLOSURE AS PER NEC 406.8 (A) do (B). 24- THE ELECTRICAL SYSTEM SHALL BE COMPLETELY AND EFFECTIVELY GROUNDED PER NEC REQUIREMENTS AND STATE AND LOCAL CODE REQUIREMENTS. 25- CONTRACTOR TO VERIFY OUTLET BOXES FOR LIGHTING FIXTURES (PENDANT LIGHTS) OR CEILING FANS ACCORDING TO FIXTURE WEIGHT TO COMPLY WITH NEC 314.27. 26- NOT USED 27- ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ARCHITEC /OWNER TO FIELD VERIFY INSTALLATION FOR OUTLETS, LIGHTING FIXTURES AND ELECTRICAL EQUIPMENT. ELECTRICAL SCOPE OF WORK PROVIDE POWER AND LIGHTING FOR REMODELED AREA IN EXISTING DWELLING UNIT. - PROVIDE POWER FOR NEW A/C UNIT (SEE MECH. PLAN). - RELOCATE WASHER /DRYER TO EXISTING ROOM AS A NEW UTILITY ROOM. - REPLACE EXISTING TANK WATER HEATER BY A NEW INSTANT WATER HEATER. - INSTALL SMOKE AND CARBON MONOXIDE DETECTORS ACCORDING TO NATIONAL AND LOCAL CODES. EXISTING ELECTRICAL SERVICE TO REMAIN. EXISTING ELECTRICAL PNL "A" TO REMAIN. ELECTRICAL- FLAN OUTSIDE INSIDE HOUSE WEATHER HEAD - ELECTRICAL SERVICE CONDUCTORS FROM FPL TXR (EXISTING) (1) PNL "A" S1 0 200 A MCB 200 A 1 OF 1 EXISTING 240/120 V METER 7, 1 PH, 3 W EXISTING (1) / °fl(ISTING GROUNDING SYSTEM, FIELD r VERIFY MINIMUM OF 1 - #4 (G) THWN IN 1/2 " C CONNECTED TO 2 GROUNDING RODS 10' L, 3/4" D, 6' MIN APART AND CONNECTED TO THE CWL (1)- EXISTING FEEDER FIEL VERIFY MIN. OF 3 -2/0 THWN Cu, IN 1 -1/2" C. ELECTRICAL RISER DIAGRAM NTS Panel Schedule - DUPLEX RECEPTACLE 20 A /120 V - QUADRUPLE RECEPTACLE 20 A/120 V -DUPLEX RECEPTACLE AT 48" AFF 20 A/120 V IF Panel: A (EXISTING LOAD CENTER) • - SINGLE RECEPTACLE ° 240 V p - ELECTRICAL PANEL Amps 200 (MCB 200 A) INTERCONNECTED W ALL S. D. IN THE HOUSE FO SIGNALING - SINGLE STATION SMOKE /CARBON MONOXIDE DETECTOR. ............. Volts 1201240 - SAFETY SWITCH - SAFETY SWITCH (NEMA 3R) FIXTURE 4' 2' (TWO LAMPS 96NW 120 V Q -J. BOX FOR RECESSED LIGHTING FIXTURE Phases 1 �J w O Q' Z O O Wires 3 f I�+■i U Q O Q o w z O Type SURFACE I ' x a Job No.: SITE PLAN Drawn By: AC Scale: 1/4 f 5 E1 Description Wire Cond VA Trip CKT I Al B CKT Trip VA Cond Wire Description 1a x 2a EXISTING LOAD (RANGE) -- -- 10,000 50(2P) lb x 2b 60(2P) 11,800 1" #6 NEW INSTANTWH 3a x 4a 3b xl 4b SPACE 20(1P) 1,500 --- --- EXISTING LOAD (LIGHTING) 5b x 6b SPACE 20(1P) 1,500 -- -- EXISTING LOAD (LIGHTING) 7b x 8b NEWFAMILYROOM #12 112" 900 201P 9a x 10a 20113 900 -- -- EXISTING LOAD (LIGHTING) NEW HEAT PUIVP #12 1/2" 1,000 20(2P) 9b x 10b SPACE 11a IxI 12a EXISTING LOAD (CU -NON COINC) -- -- 4,500 30(1P) 11b xj 12b 20(lPT 1,000 -- -- EXISTING LOAD REFRIG. 13a x 14a 20(1P) 800 — --- EXISTING LOAD (LIGHTING) EXISTING LOAD (WASH/DRYER) #10 1/2" 5,500 30(1P) 13b x 14b 20(1P) 1,500 1!2" #12 LAUNDRYRECEPT. 15a x 16a 20(1P) 1,000 -- -- EXISTING LOAD (MCRW) EXISTING LOAD (LIGHTING) -- -- 900 20(1P) 15b x 16b 20(1P) 900 112" #12 EXISTING LOAD (LIGHTING) 17a x 18a 20(IP) 900 -- --- EXISTING LOAD (LIGHTING) EXISTING LOAD (AHU) -- -- 10,500 60(2P) 1713 x 18b 20(1P) 900 -- -- EXISTING LOAD (LIGHTING) 19a x 20a 20(1P) 900 — --- EXISTING LOAD (LIGHTING) 19b x 20b 20(1l' ) 1,200 12" #12 NEWBATHROOM CONNEC I ED LOAD-- 57,200 VA ADJ, AREA= 1,500 SQ -F UGHIINGLOAD= 4,500 VA 2 S. APP. CiRC +L. CIRC= 4,500 VA - i OTHER EQ. LOAD- 31=600 f VA :... 4 ........... . 1 ST 10,000 VA 100 % = 10,0001 VA I REMINDER 40 ° >a = 12,240 = VA AIC LOAD­-' OAD= .......... 11,500 11,5- VA f. £ TOTAL DEMAND-- 33,740 VA 5 I AMPS= 141 ELECTRICAL LEGEND -J. BOX FOR SURFACE MTD LIGHTING FIXTURE .(�. J. BOX FOR LIGHTING FIXTURE I (WALL MOUNTED) - ELECTRICAL SWITCH 20 A/120 V - ELECTRICAL SWITCH 20 A /120 V (THREE WAY) 14 - ELECTRICAL SWITCH 20 A /120 V (FOUR WAY) -FLOOD LIGHT J. BOX FOR LIGHTING FIXTURE AND FAN CEILING MOUNTED (FAN OPTIONAL) 4P - EXHAUST FAN -)- BRANCH CIRCUIT WITH (/) LINE, (/) NEUTRAL AND (1) GROUNDING CONDUCTORS. E- EXISTING ( *)- PROVIDE #10 EG CONDUCTOR ( *) EXISTING ELECTRICAL METER BEM ........... __.__....___..__.___ ........ _................................. Ph "A "� EXISTING �� I BEDROOM • 3 _ EXISTING EXISTING ROOM KITCHEN DINING ROOM / __ ............................... _._ ..... __ ......... _.. I ;A O� 8 SD i t Li ............. _ . ............................... Li SD EXISTING EXISTING BEDROOM • 2 BEDROOM • EXISTING LIVING ROOM � I E ONE STORY RESIDENCE 6510 MANOR LN ................ KEY FL_ AN 8 ■I' -0" •••• p e F P j • •••• rc; S E • XA T W ��y Wi J Z • Q ` • ••.ZESS ION �•• e••if s•• PREPARED BY CONSULTANT ino Curtis, PE Corp. (C.A. #: 27293) Engineering Services A/e'ondro F. Pino (PE Lic 59459) 1484 S 34th Ln Miomi FL33185 ph: 305 562 8676 Dinocurtispe®bellsouth. net rwv,IS-IONS: - DUPLEX RECEPTACLE 20 A /120 V - QUADRUPLE RECEPTACLE 20 A/120 V -DUPLEX RECEPTACLE AT 48" AFF 20 A/120 V IF -PHONE /DATA OUTLET --0 -TV OUTLET • - SINGLE RECEPTACLE ° 240 V p - ELECTRICAL PANEL - ELECTRICAL METER SD - SINGLE STATION SM KE DETECTOR INTERCONNECTED W ALL S. D. IN THE HOUSE FO SIGNALING - SINGLE STATION SMOKE /CARBON MONOXIDE DETECTOR. INTERCONNECTED W ALL SO, S/C IN THE HOUSE FOR SIGNALING [:p - SAFETY SWITCH - SAFETY SWITCH (NEMA 3R) FIXTURE 4' 2' (TWO LAMPS 96NW 120 V Q -J. BOX FOR RECESSED LIGHTING FIXTURE -J. BOX FOR SURFACE MTD LIGHTING FIXTURE .(�. J. BOX FOR LIGHTING FIXTURE I (WALL MOUNTED) - ELECTRICAL SWITCH 20 A/120 V - ELECTRICAL SWITCH 20 A /120 V (THREE WAY) 14 - ELECTRICAL SWITCH 20 A /120 V (FOUR WAY) -FLOOD LIGHT J. BOX FOR LIGHTING FIXTURE AND FAN CEILING MOUNTED (FAN OPTIONAL) 4P - EXHAUST FAN -)- BRANCH CIRCUIT WITH (/) LINE, (/) NEUTRAL AND (1) GROUNDING CONDUCTORS. E- EXISTING ( *)- PROVIDE #10 EG CONDUCTOR ( *) EXISTING ELECTRICAL METER BEM ........... __.__....___..__.___ ........ _................................. Ph "A "� EXISTING �� I BEDROOM • 3 _ EXISTING EXISTING ROOM KITCHEN DINING ROOM / __ ............................... _._ ..... __ ......... _.. I ;A O� 8 SD i t Li ............. _ . ............................... Li SD EXISTING EXISTING BEDROOM • 2 BEDROOM • EXISTING LIVING ROOM � I E ONE STORY RESIDENCE 6510 MANOR LN ................ KEY FL_ AN 8 ■I' -0" •••• p e F P j • •••• rc; S E • XA T W ��y Wi J Z • Q ` • ••.ZESS ION �•• e••if s•• PREPARED BY CONSULTANT ino Curtis, PE Corp. (C.A. #: 27293) Engineering Services A/e'ondro F. Pino (PE Lic 59459) 1484 S 34th Ln Miomi FL33185 ph: 305 562 8676 Dinocurtispe®bellsouth. net rwv,IS-IONS: _ 'D-�V.1 REV.2 - - - REV.3 0 U M � � r- 00 M N .-, �w Z W a U ° z O v 1 W z O U W w �J w O Q' Z O O `O I�+■i U Q O Q o w z O M C\ °` M p A � A O z ¢ x a Job No.: SITE PLAN Drawn By: AC Scale: 1/4 Date : 03/13 E1