Loading...
13-240-036GENERAL HS.A.C. NOTES 1. The contractor shall furnish all labor, material and equipment for a complete H.V.A.C. system in accordance with these drawings. The Florida Building Code 2001 and the latest edition of the following publications: (o )ANS 89.1 Mechanical Refrigeration (b) NFPA Pamphlets 90A k 91 c) SMACNA (d) ASHRAE. 2. All air conditioning ductwork shall be 1 -112 " standard duty foil reinforced fiberglass (R -6) ` manufactured logo riveted on the vapor barrier when in unconditioned s ace, and 3%4 standard duty foil reinforced fiberglass (R -4) manufactured logo printed on the vapor barrier in conditioned space or return plenum space. J. All exhaust ductwork shall be code gage galvanized sheet metal. 4. Duct size shown are net free area inside. 5. All air devices (diffusers, registers and grilles) shall be all aluminum construction, with exposed surface chemically treated to receive paint to match color or AIR GUIDE or approved equal. 6. Provide opposed blade dampers at all diffusers and registers. 7. Thermostats shall be combination cooling heating with system Cool / Auto / Heat / Off and Fan On /Auto selector switches. 8. Refrigerant piping shall be copper type "L" with 112" armaflex. Insulation shhall be provided far suction lines. 9. Provide new filters for fan coil before starting. These filters must also be replaced prior to final acceptance by owner. 10. General contractor is to hire an independent Test and Balance company which shall provide 3 set of the report sign and sealed by the Professional Engineer from the company prior of acceptance of work if required. 11. Mechanical contractor its to provide turning vent at all change of directions or to provide turning radio, all outlets sholl have extractors or scuppers. and shall be installed in accordance with the applicable regulations. LEGEND 4 "0 GMD(26GA) UP THRU ROOF W /WP CAP, BIRD SCREEN & B. D. D. AS PER 1502.2 SITE INVESTIGATION NOTE EXAMINATION OF CONTRACT DOCUMENTS AND SITE OF WORK: THE BIDDER IS REQUIRED, BEFORE SUBMITTING HIS PROPOSAL, TO VISIT THE SITE OF THE PROPOSED WORK AND FAMILIARIZE HIM OR HERSELF WITH THE NATURE AND EXTENT OF THE WORK AND ANY LOCAL CONDITIONS THAT MAY IN ANY MANNER AFFECT THE WORK TO BE DONE AND EQUIPMENT, MATERIALS AND LABOR REQUIRED THEREFORE. SINCE THE WORK INVOLVES NEW AND /OR EXISTING BUILDINGS, SYSTEMS AND FACILITIES, SPECIAL CONSIDERATION SHALL BE GIVEN TO EXAMINATION OF WORKING CONDITIONS, NEW FACILITIES AND ALL BUILDING STRUCTURES FAMILIARIZE TO HIMSELF WITH ALL EXISTING CONDITIONS. SLIGHT VARIATION OF ROUTING AND OR CONSTRUCTIONS SHOULD BE ANTICIPATED BY THIS CONTRACTOR TO AVOID CONFLICTS WITH OTHER TRADES. THESE VARIATIONS ARE EXPRESSLY INCLUDED AS PART OF THE WORK WHENEVER REQUIRED AT NO ADDITIONAL COST TO THE OWNER. IGNORANCE ON THE PART OF THE CONTRACTOR WILL IN NO WAY RELIEVE HIM OF THE OBLIGATIONS AND RESPONSIBILITY ASSUMED UNDER THIS CONTRACT. HV ^C DESIGN REQUIRE: 24X24 CD –(SEE SCHEDULE) NO DUCT TO MATCH NECK SIZE TYP. ELECTRIC.. DATA CEILING GRILLE SEE SIZE SCHEDULE FIRE DAMPER(S) DUCT TO MATCH NECK SIZE TYP. Q RAG –( RETURN AIR GRILL)) OAS VOLUME DAMPER ® THERMOSTAT DD DUCT MOUNTED SMOKE DETECTOR PHASES X SEE F.A. RISER FOR SPECS. FUSES AIR FLOW DIRECTION ( ARROWS DENOTE SMOKE CONTROL 1 WAY, 2 WAY, ETC., SEE PLANS X RETURN OR EXHAUST, SEE PLANS. 34.6 / 67 80 p WALL MOUNTED SIDE REGISTER. 7 34 �J D EXHAUST FAN O.A.I. OUTSIDE AIR INTAKE S.R. SIDE REGISTER CD CEILING DIFFUSER CG CEILING GRILLE H.P. HEAT PUMP UNIT F.L.D FULL LOUVERED DOOR CU CONDENSING UNIT AHU AIR HANDLER UNIT UC UNDERCUT DOOR FOR AIR RETURN RTU ROOF TOP UNIT VD MANUAL VOLUME DAMPER 4 "0 GMD(26GA) UP THRU ROOF W /WP CAP, BIRD SCREEN & B. D. D. AS PER 1502.2 SITE INVESTIGATION NOTE EXAMINATION OF CONTRACT DOCUMENTS AND SITE OF WORK: THE BIDDER IS REQUIRED, BEFORE SUBMITTING HIS PROPOSAL, TO VISIT THE SITE OF THE PROPOSED WORK AND FAMILIARIZE HIM OR HERSELF WITH THE NATURE AND EXTENT OF THE WORK AND ANY LOCAL CONDITIONS THAT MAY IN ANY MANNER AFFECT THE WORK TO BE DONE AND EQUIPMENT, MATERIALS AND LABOR REQUIRED THEREFORE. SINCE THE WORK INVOLVES NEW AND /OR EXISTING BUILDINGS, SYSTEMS AND FACILITIES, SPECIAL CONSIDERATION SHALL BE GIVEN TO EXAMINATION OF WORKING CONDITIONS, NEW FACILITIES AND ALL BUILDING STRUCTURES FAMILIARIZE TO HIMSELF WITH ALL EXISTING CONDITIONS. SLIGHT VARIATION OF ROUTING AND OR CONSTRUCTIONS SHOULD BE ANTICIPATED BY THIS CONTRACTOR TO AVOID CONFLICTS WITH OTHER TRADES. THESE VARIATIONS ARE EXPRESSLY INCLUDED AS PART OF THE WORK WHENEVER REQUIRED AT NO ADDITIONAL COST TO THE OWNER. IGNORANCE ON THE PART OF THE CONTRACTOR WILL IN NO WAY RELIEVE HIM OF THE OBLIGATIONS AND RESPONSIBILITY ASSUMED UNDER THIS CONTRACT. HV ^C DESIGN REQUIRE: YES NO DUCT SMOKE DETECTOR ELECTRIC.. DATA X FIRE DAMPER(S) ELECTRICAL DATA X SMOKE DAMPERS OAS X FIRE RATE ENCLOSURE W9 X FIRE RATED ROOF /FLOOR CEILING ASSEMBLY PHASES X FIRE STOPPING FUSES X SMOKE CONTROL COND. X FAN —COIL DESIGNATION CFM MffrUH ELECTRIC.. DATA ENTERING F ELECTRICAL DATA MANUFAC. W UNIT OAS TOTAL SENSIM.E W9 DR VOLTS PHASES HMG KW AN FUSES LIG. SUC. COND. AHU --1(E) 1200 34.6 25.3 67 80 230 1 7 34 40 RHEEM REAB -141 OBQSW 5116 718 1 AHU -2(N) 1 1200 1 35.4 25.8 67 80 230 1 7 34 40 RHEEM RHLAHM3617JA 5116 718 1 1 CONDENSING UNIT DESIGNATION MIRUH TEMP. ENT. CONDEJOM ELECTRIC.. DATA LU MANUFAC. UNIT OBS OR SEER AR£A SERVED VOLTS PHASES MARE AMPS FUSES CU -1(E) 34.6 90 230 1 25 30 TRANE 2TTB3036A1000AA 13.0 SHOWN CU -2(N) 35.4 90 230 1 25 30 RHEEM 13AJA36AO1 14.0 SHOWN 4 "0 GMD(26GA) L ROOF W /WP CAP, W/ BACKDRAFT D, PER FBC 504.4 2"! CD LINE TO DISCHARGE 6" AFG k 12" AWAY FROM FOOTING • MINE 0 IN r_— _VA -SH-R- CG 6X6 75 CFM 1 6"0 BATH CG 8X6 100 CFM CG 10X8 200 CFM 1 7 "0 MASTER BEDROOM C 1G 0x8 �» D. 1 200 CFM 7"0 AS 0 AHU112 1 ex 3 TONS / L WID - 2 "0 CD / CG 6X6 / 75 CFM REF LINES _CF (OH) --� A U N D R REF LINES 4 (SEE DETAIL) cu112 (N) L_ — 12'X12" LOUVER ON EACH LATERAL WALL LOCATED AT 6" BELOW TOP AND ANOTHER 6" ABOVE FLOOR ., x x a r D RAG ,/ 18x118 FLD FOR DRYER MAKE UP AIR !ST / / ELEId �. I. // �w wHI/ / 14Y ,FUN�GMDI(=IJBI_Fel� ) y O I E 7' A 11."o DIST. C01 TERRACE ARBAG O O — — — — — — — 6 "OGMD (22GA) FOR D.W. 1 8 „o f KITCHEN EXHAUST DUCT THRU WALL W WP CAP KITCHEN / CG 12X8 CG 12x8 275 CFM 200 CFM STOVE 8 "0 MICRO REF �n �7 777-- TT AD tA�Z IL-71– 7 A W /"� GY• / / � / / / / / / / / / / / TIC / / / / )6 Y6 '(N�� /R 0 /OM _V' _z AgSET/ 7/ 'z _j_/ *DK/0W NEW PORCH / MECHANICAL PLAN SCALE: 1/4 "= V -0" D F I�I CUj1(E) . W • {i v G V V • Revisions �t7.3. 0 0.13 «1, • i «3 27'201, . . • •y• • ••• n i19 «• 1/\ . • CC w� 0 LJ U LU LL Z LLI LlJ UJ Cf) C/) Z Wo Q CC 0 Q V �O LL C Seal "'" 4 ■ AA -2 001560 s W �Q U 4 0 G d' J Cc C1 a o Lo U � co z L co U) o X *0 O LL 0 � � U N o CL t 4 I L0 p ��� 0 .� Y. A/ Qa >a Ow0 LF Cd —� > 0 LL L N E U U N o 0 Q as N z °' a 0 U Qw a � o WU � �J Q m Job No. w� Date f, W r, z Scale SHOWN W U :w " •w . C Seal "'" 4 ■ AA -2 001560 s W' W N Z M -1 h U Job No. w� Date f, W r, Scale SHOWN W ) 6 :w " •w . C Seal "'" 4 ■ AA -2 001560 W Sheet Noy" W' W N Z M -1 h