14-952-037ELECTRICAL SPECIFICATIONS
1. ALL WORK TO BE IN ACCORDANCE WITH THE RULES AND REGULATION OF THE LOCAL
AUTHORITIES HAVING JURISDICTION AND THE MOST RECENT EDITION OF NATIONAL ELECTRIC
CODE.
2. FURNISH ALL MATERIALS, EQUIPMENT, LABOR, & SERVICES REQUIRED FOR THE INSTALLATION
OF ALL ELECTRICAL WORK & AS REQUIRED TO PROVIDE A COMPLETE & OPERABLE ELECTRICAL
SYSTEM AS INDICATED ON THE DRAWINGS.
3. CONTRACTOR SHALL GUARANTEE WORK INSTALLED UNDER THE CONTRACT TO BE FREE FROM
DEFECTIVE WORKMANSHIP & MATERIALS, USUAL WEAR EXCEPTED, & SHOULD ANY SUCH
DEFECTS DEVELOP WAN A PERIOD OF ONE YEAR ACCEPTANCE OF THE BLDG. BY THE YEAR,
THIS CONTRACTOR SHALL REPAIR AND /OR REPLACE ANY DEFECTIVE ITEMS & DAMAGE
RESULTING FROM FAILURE OF THESE ITEMS, AT NO EXPENSE TO THE OWNER.
4. INCIDENTAL ITEMS NOT INDICATED ON THE DRAWINGS, NOR MENTIONED IN THE SPECIFICATIONS,
THAT CAN BE LEGITIMATELY & REASONABLE BE INFERRED TO BELONG TO THE WORK
DESCRIBED OR BE NECESSARY IN GOOD PRACTICE TO PROVIDE A COMPLETE SYSTEM, SHALL BE
FURNISHED & INSTALLED AS THOUGH ITEMIZED HERE IN EVERY DETAIL.
5. NOTIFY ARCHITECT IMMEDIATELY OF POSSIBLE CONFLICTS WITH STRUCTURE, MECHANICAL, OR
OTHER FEATURES. WHERE JOB CONDITIONS REQUIRE REASONABLE CHANGES IN LOCATIONS &
ARRANGEMENT OF INDICATED EQUIP., CONDUIT, OUTLETS, OR WIRING, CONTRACTOR SHALL MAKE
SUCH CHANGES WITHOUT COST TO OWNER.
6. OWNER SHALL FILE PLANS WITH AND OBTAIN APPROVALS FROM MUNICIPAL AGENCIES. ALL
PERMITS AND CERTIFICATES OF INSPECTION SHALL BE OBTAINED AND PAID FOR BY THE
OWNER.
7. CONTRACTOR SHALL VISIT SITE PRIOR TO BIDDING. BIDS SHAM SERVE AS EVIDENCE OF
KNOWLEDGE OF EXISTING CONDITIONS.
8. THIS CONTRACTOR SHALL DO ALL CUTTING, CHASING, OR CHANNELING AND PATCHING REQUIRED
FOR ANY WORK HEREIN SPECIFIED.
ALL OPENINGS THROUGH STRUCTURALLY SUPPORTED SLABS MUST BE COREBORED, SLEEVED,
GROUTED, SEALED AND MADE WATERPROOF. SLEEVES MUST EXTEND AT LEAST 2" AFF.
ALL SLEEVES, OPENINGS, ETC. THROUGH FIRE RATED WALLS AND FLOORS SHALL BE SEALED
AFTER CONDUIT INSTALLATION TO RETAIN FIRE RATING.
9. ALL ELECTRICAL WORK SHALL BE INSTALLED SO AS TO BE READILY ACCESSIBLE FOR
OPERATING, SERVICING, MAINTAINING AND REPAIR.
HANGERS SHALL INCLUDE ALL MISCELLANEOUS STEEL, SUCH AS CHANNELS, RODS, ETC.,
NECESSARY FOR THE INSTALLATION OF WORK AND SHALL BE SECURED TO THE BUILDING
- STRUCTURE, NOT TO PIPING OR DUCTWORK.
ALL CONDUIT SHALL BE CONCEALED WHERE POSSIBLE. EXPOSED CONDUIT SHALL BE RUN IN
STRAIGHT LINES PARALLEL WITH OR AT RIGHT ANGLES TO COLUMN LINES AND SEPARATED AT
LEAST 3" FROM WATER LINES WHEREVER THEY RUN ALONG SIDE OR ACROSS SUCH LINES.
10. EVERY PART OF THE INSTALLATION SHALL BE TESTED, OPERATED AND LEFT IN PERFECT
a WORKING ORDER.
11. IT SHALL BE THIS CONTRACTOR'S RESPONSIBILITY, PRIOR TO ANY INDIVIDUAL CIRCUITS
INSTALLATION, TO VERIFY WITH ALL OTHER TRADES CONCERNED THAT THE CIRCUIT WITH
DEVICES AS DRAWN IS ADEQUATE IN SIZE AND MAKE -UP FOR THE MECHANICAL AND /OR
KITCHEN EQUIPMENT TO BE INSTALLED. IF ANY CONFLICT IN VOLTAGE, PHASE OR LOAD IS
ENCOUNTERED WHICH WOULD ALTER THE CIRCUIT SIZE, THIS CONTRACTOR SHALL NOTIFY THE
ENGINEER OR OWNER IMMEDIATELY. FAILURE TO DO SO SHALL PLACE THE RESPONSIBILITY FOR
ANY SUBSEQUENT CIRCUIT CHANGE DIRECTLY UPON THE CONTRACTOR.
12. GENERAL SCOPE OF WORK
CONTRACTOR SHALL FURNISH ALL LABOR, MATERIALS, SUPPLIES, EQUIPMENT AND FEES
REQUIRED TO COMPLETELY INSTALL, TEST AND PLACE THE HEREIN SPECIFIED EQUIPMENT,
COMPONENTS, CONTROLS, AND SYSTEMS IN SERVICE.
COMPLETE POWER AND LIGHTING SYSTEMS INCLUDING ALL PANELS AND COMPLETE BRANCH
CIRCUIT WIRING SYSTEM
TEMPORARY ELECTRICAL SERVICE AS REQUIRED FOR CONSTRUCTION
COMPLETE TELEPHONE CONDUIT SYSTEM INCLUDING CONDUIT FROM POINT OF CONNECTION TO
UTILITY COMPANY SERVICE AND ALL TERMINAL DEVICES, BOXES, CONDUIT, PLATES, ETC.
PROVISIONS FOR FIRE ALARM SYSTEM AS REQUIRED BY CODE
p WIRING AND FINAL CONNECTION TO ALL SIGNS AND GRAPHICS
TESTING OF ALL CABLES AND CIRCUIT WIRING AFTER INSTALLATION
TESTING OF ALL ELECTRICAL EQUIPMENT
WARRANTY OF ALL WORK FOR A PERIOD OF ONE YEAR FROM DATE OF PROJECT CLOSE -OUT
13. THE CONTRACTOR SHALL BE RESPONSIBLE TO VERIFY THE AVAILABLE SHORT CIRCUIT CURRENT
AT THE SUPPLY TERMINALS FROM THE POWER COMPANY & /OR MALL/SHOPPING CENTER POWER
SOURCE. THE SERVICE EQUIPMENT SHALL MEET OR EXCEED THIS RATING PER N.E.C.
14. THE CONTRACTOR SHALL MAKE ARRANGEMENTS PITH THE LOCAL TELEPHONE UTILITY COMPANY
FOR TELEPHONE SERVICE TO THE SPACE, CONDUIT SYSTEM FOR TELEPHONE DISTRIBUTION TO
THE LEASED PREMISES SHALL BE PROVIDED WHERE REQUIRED FOR UTILITY COMPANY WIRES.
15. THIS CONTRACTOR SHALL PROVIDE, INSTALL AND CONNECT A COMPLETE SYSTEM OF
GROUNDING FOR ALL EQUIPMENT AND STRUCTURES. ELECTRICAL SYSTEM AND EQUIPMENT
GROUNDS SHALL COMPLY WITH ALL LOCAL, STATE AND NEC CODES AND REGULATIONS.
16. PANELBOARDS AND BREAKERS SHALL BE BY SQUARE -D OR EQUAL
PANEL SHALL BE CIRCUITED SO THAT THE LOAD IS DISTRIBUTED EVENLY ACROSS ALL THREE
PHASES.
PANELBOARDS SHALL CONTAIN A TYPEWRITTEN DIRECTORY WITH A PLASTIC COVER AFFIXED TO
THE INSIDE DOOR.
17. ALL BREAKERS SHALL BE BOLTED TYPE, THERMAL MAGNETIC WITH ALL TWO OR THREE POLE
BREAKERS HAVING COMMON TRIP. CIRCUIT BREAKERS SHALL BE RATED FOR MINIMUM 10,000
AMP SYMMETRICAL SHORT CIRCUIT CURRENT AT 120/208V.
CIRCUIT BREAKERS SERVING LIGHTING CIRCUITS SHALL BE RATED FOR SWITCH SERVICE.
18. WIRING DEVICES:
WALL SWITCHES, SINGLE POLE, DOUBLE POLE, AND THREE WAY SHAM BE GENERAL DUTY,
FLUSH, TOGGLE SWITCHES; SPECIFICATION GRADE, 20A, 120 /277V, WITH SCREW TERMINALS.
MANUFACTURES SHALL BE HUBBELL, BRYANT, PASS & SEYMORE, OR LEVITRON.
GENERAL DUTY DUPLEX RECEPTACLES SHALL BE 2 -POLE, 3-WIRE GROUNDING TYPE,
SPECIFICATION GRADE, 20A, 125V, NEMA 5-208 UNLESS OTHERWISE INDICATED.
MANUFACTURES SHALL BE HUBBELL, BRYANT, PASS AND SEYMORE, OR LEVITRON.
GROUND FAULT INTERRUPTER RECEPTACLE SHALL BE GENERAL DUTY, DUPLEX RECEPTACLES,
GROUND FAULT CIRCUIT INTERRUPTER, FEED - THROUGH TYPE, CAPABLE OF PROTECTING
CONNECTED DOWNSTREAM RECEPTACLES ON A SINGLE CIRCUIT, GROUNDING TYPE UL -RATED
CLASS A, GROUP 1, 20A, 120V, 60 HZ; WITH SOLID -STATE GROUND FAULT SENSING AND
SIGNALING; WITH 5 MILLIAMPERES GROUND - FAULT TRIP LEVEL; IN NEMA 5-158
CONFIGURATION. MANUFACTURERS SHALL BE HUBBELL, BRYANT, PASS & SEYMORE, OR
LEVITRON.
DUPLEX ISOLATED GROUND TYPE RECEPTACLE MALL BE 2 -POLE, 4 -WIRE, 15A STRAIGHT
BLADE DEVICE WITH SEPARATE ISOLATED GROUND AND BUILDING GROUND CONNECTIONS, IN
NEMA 5-15R CONFIGURATION, AS MANUFACTURED BY HUBBELL IG -5362.
WIRING DEVICE ACCESSORIES INCLUDING ALL WALL PLATES SHALL BE PROVIDED AT EACH
DEVICE. WAIL PLATES SHALL BE SAME COLOR AS DEVICE AND MANUFACTURED AS A
COMPANION TO THE DEVICE.
ANY ELECTRICAL OUTLETS WITHIN 4 FEET OF A SINK SHALL BE GFI PROTECTED. PROVIDE
EITHER INDIVIDUAL GFI DEVICES OR GFI CIRCUIT BREAKERS, UNLESS SPECIFICALLY NOTED ON
THE DRAWINGS OR SCHEDULES.
PROVIDE A 120 VOLT RECEPTACLE WITHIN 25 FEET OF ALL HVAC EQUIPMENT.
ALL EXTERIOR RECEPTACLES AND DEVICES SHALL BE WEATHERPROOF
19. ALL FEEDERS & BRANCH CIRCUITS SHALL BE THHN/THWN (75' C). DESIGN IS BASED ON
COPPER CONDUCTORS & ALL BRANCH CIRCUIT WIRING SHALL BE COPPER. ALL WIRING SHALL
BE IN CONDUIT OR MC TYPE.
ADDITIONAL CONDUCTOR SPECIFICATIONS:
#10 AND SMALLER - SOUD WITH SINGLE BRAID.
#8 AND LARGER - STRANDED WITH AT LEAST DOUBLE BRAID.
MINIMUM WIRE SIZE SHALL BE #12 (#14 MAY BE USED FOR CONTROLS)
WIRES SHALL BE COLOR CODED IN KEEPING WITH NEC STANDARDS
ELECTRICAL LEGEND
POWER
SYMBOL
DESCRIPTION
(�
DUPLEX RECEPTACLE MOUNTED AT 18 "AFF
UNLESS NOTED OTHERWISE
QUAD PLEX RECEPTACLE MOUNTED AT 150AFF
UNLESS NOTED OTHERWISE
W
DUPLEX ISOLATED GROUND TYPE RECEPTACLE MOUNTED
AT 15 "AFF UNLESS NOTED OTHERWISE
-4W -S/N
QUAD PLEX ISOLATED GROUND TYPE RECEPTACLE MOUNTED
AT 15 "AFF UNLESS NOTED OTHERWISE
CKT.
DUPLEX GROUND FAULT INTERRUPTING TYPE RECEPTACLE
Q
JUNCTION BOX
PHASE
DISCONNECT SWITCH
SERVICE
SINGLE SECTION PANELBOARD
COT.
HEAVY DUTY RECEPTACLE (VERIFY NEMA CONFIGURATION)
SIZE
CIRCUIT HOME RUN
COMMUNICATIONS
b =�0
ROUGH -IN FOR TELEPHONE DATA LINE OR DATACOM
MOUNTED AT 15 "AFF UNLESS NOTED OTHERWISE
LIGHTING CONTROL
SQE
WALL MOUNTED TOGGLE SWITCH
0
OCCUPANCY SENSING CONTROL, VERIFY EQUIPMENT SPEC WITH ROOM
LAYOUT AND OWNER IN FIELD (LEVITON OR EQUAL)
MC
TIME CLOCK
A
PHOTOCELL
IC
LIGHTING CONTACTOR
ABBREVIATIONS
AFF
ABOVE FINISHED FLOOR
KW
KILOWATT
A
AMPERE
NIC
NOT IN CONTRACT
ELEC
ELECTRICAL
PNL
PANEL
EXIST
EXISTING
SW
SWITCH
EQUIP
EQUIPMENT
TYP
TYPICAL, ,
FA
FIRE ALARM
V
VOLT
G,GND
GROUND
W
WIRE
GFI
GROUND FAULT INTERRUPTER
WP
WEATHERPROOF
HP
HORSEPOWER
PH
PHASE
IG
ISOLATED GROUND
XFMR
TRANSFORMER
PANEL M
i
400A h�C:R
120/208V
-3PH -4W -SIN
100 A ML0
1201208V
- 3PH
-4W -S/N
_ 42 POLE
CKT.
BRKR.
...... ..._ ...........................
SERVICE
_...................................._............ ...............................
LOAD
, ...............................
PHASE
LOAD
SERVICE
BRKR.
COT.
BRKR.
SIZE
NO.
A
b =�0
_..........._....
VA
............ ...........
SQE
f NO.
1
100/3
PANEL A
8040
A
6900
RTU -1
m 6013
2
q
3
7420
B
6900
5
7640
C
6900
6
7
20/1
SPARE
-
A
3600
RTU -2
45/3
8
9
20 /1
SPARE
-
B
3600
10
11
20/1
SPARE
-
C
3600
12
13
20/1
SPARE
-
A
3600
RTU -3
45/3
14
15
20/1
SPARE
-
B
3600
16
17
20/1
SPARE
A
C
3600
18
19
20/1
SPARE
-
A
3600
RTU4
45/3
20
21
20/1
SPARE
LIGHTING - SALES
B
3600
22
23
20/1
SPARE
19
C
3600
24
25
20/1
SPARE
-
A
3600
RTU -5
45/3
26
27
20/1
SPARE
20/1
B
3600
28
29
20/1
SPARE
-
C
3600
30
31
20/1
SPARE
300
A
2770
RTU-6
30/3
32
33
20/1
SPARE
-
B
2770
34
35
20/1
SPARE
-
C
2770
36
37
20 /1
SPARE
-
A
-
SPARE
20/1
38
39
20/1
SPARE
32
B
-
SPARE
20/1
40
41
20/1
SPARE
-
C
-
SPARE
20/1 1
42
:.....,
p
.. _.._ CONNECTED LOAD A:1-1,21.1.
32110 ..._,
VA 95310.. VA :TOTAL LOAD 264.6
2011
SPARE
13:
39490 iVA
.. 95310 VA .DEMAND LOAD 264.6 _
SPARE
20/1
C.
31710
VA
PANEL A I
i
100 A ML0
1201208V
- 3PH
-4W -S/N
42 POLE
CKT
BRKR.
SERVICE w N
m...... _ _ �.
LOAD
w._. ,..�
PHASE
LOAD
o
BRKR.
CKT
NO.
SIZE
b =�0
_
_w..r..u.�.
....._...
_....w._... _... w.__ ._ .._..__.,.. ..... ..._..__
".'S'ERVICE
...._._...._
SIZ£
_._..__r .
NO,
1
20/1
LIGHTING - SALES
1020
A
1080
SALES FLOOR RECEPTACLES
2011
2
3
20/1
LIGHTING - SALES
1020
B
900
SALES FLOOR RECEPTACLES
20/1
4
5
20/1
LIGHTING - SALES
1020
C
1080
SALES FLOOR RECEPTACLES
20/1
6
7
20/1
LIGHTING - SALES
740
A
900
SALES FLOOR RECEPTACLES
2011
8
9
20/1
LIGHTNG - SALES
740
B
900
STORAGE ROOM RECEPTACLES
20/1
10
11
20/1
LIGHTING - SALES
1270
C
720
TELEPHONE BOARD
20/1
12
13
20/1
LIGHTNG - SALES
1020
A
540
RESTROOM/WATER COOLER REC
20/1
14
15
20/1
LIGHTNG - SALES
1020
B
360
CASHWRAP
20/1
16
17
20/1
LIGHTING - SALES
740
C
1080
RTU SERVICE RECEPTACLES
20/1
181
19
2011
LIGHTING - SALES
740
A
720
SHOW WNDOdV RECEPTACLES
20/1
20
21
20/1
LIGHTING - SALES
740
B
540
SHOW WNDCW RECEPTACLES
20/1
22
23
20/1
LIGHTNG - RESTROOMS/EF -1
530
C
SPARE
2011
24
25
20/1
LIGHTNG - EXTERIOR
300
A
680
LIGHTING - STORAGE
20/1
26
27
20/1
EXTERIOR SIGN
1200
13
SPARE
2011
28
29
2011
EXTERIOR SIGN
1200
C
-
SPARE
2011
30
31
2011
TIMECLOCKIPHOTOCELL
300
A
-
SPARE
20/1
32
33
20/1 ISPARE
-
B
-
SPARE
20/1
34
35
20/1
SPARE
C
-
SPARE
20/1
36
37
2011
SPARE
-
A
-
SPARE
20/1
38
39
2011
SPARE
-
B
-
SPARE
20/1
40
41
20/1
SPARE
C
-
SPARE
20/1
42
i
CONNECTED LOAD A: $040 €VA
................ ._.._ _....
231A
00
V :TOTAL LOAD
641
_...._.
..8 :.... .............7420£VA_
_..._......1
23100
_ ..... ...._..................__._._ . _....._
VA..._DEMAND.LOAD .........
641
C: 764W
VA
VA
_...
1�3 ►1��1 ►1aNJ /Glc1UIA I
•
EXISTING CONDITION NOTES
rr « + r�r �•�r..
r � r « � r �+ r �y• « r+
••« •• r• r : � r +r r
GENERAL NOTES - ONE LINE
1. ALL WORK AND MATERIALS BY THE ELECTRICAL CONTRACTOR,
UNLESS OTHERWISE NOTED.
2. ELECTRICAL SERVICE: EXISTING 600 AMP, 120/208 VOLT 3
PHASE 4 WIRE MAIN DISTRIBUTION PANEL. AND CONDUIT STUB
INTO SPACE TO REMAIN. ELECTRICAL CONTRACTOR SHALL
PROVIDE CONDUCTORS FROM DISTRIBUTION PANEL TO PANEL
'M' AND EXTEND CONDUIT STUB TO PANEL. V.
3. COORDINATE THE INSTALLATION WITH THE POWER COMPANY
AND OWNER REPRESENTATIVE FOR THE EXACT REQUIREMENTS,
INCLUDING A.I.C. REQUIREMENTS FOR THE PANELBOARDS AND
CIRCUIT BREAKERS.
4. VERIFY SERVICE VOLTAGE AND AMPERAGE WITH POWER
COMPANY PRIOR TO BID.
5. WIRE AND CONDUIT SIZES SHOWN ARE FOR COPPER
CONDUCTORS WITH 751C RATED INSULATION AND ARE SHOWN
FOR REFERENCE ONLY. CONTRACTOR TO PROVIDE PROPERLY
SIZED WIRE TO COMPENSATE FOR ALUMINUM FEEDER OR
VOLTAGE DROP AS REQUIRED.
design, ire.
p.o. box 14.2116
coral gables, florida
33114.2116 s
v. 305.443.3100
f. 305.259.3986
e. info @whadesign.com
architect of record:
William Arthur
License Number: 0012074
4� +�r��r
4 ,gr
o• ,.�
of `. • u► w
r"♦ ts, l�lI�%
design associate:
bFORD
These plans and specifications are
the exclusive property of WHA
Design. Any reproduction,
modification, disclosure, and/or use
of these materials (or any portion
thereof) without WHA Design's prior
written consent is strictly prohibited.
W
E e r
3: �� w
-
A
A
project information:
date:
07/08/13
project number:
13 -20
sheet title:
ONE -LINE
DIAGRAM ffig
ep
sheet number. 7tl:
E3 a 01.
V.,
file:
88413 e3.0.dwg
0 . X
o
(U co�
b =�0
�.«
®
-
A
A
project information:
date:
07/08/13
project number:
13 -20
sheet title:
ONE -LINE
DIAGRAM ffig
ep
sheet number. 7tl:
E3 a 01.
V.,
file:
88413 e3.0.dwg