14-952-035TIMECLOCK CONTACTOR CONTROL DIAGrN^ Lve ALL INTERIOR LIGHTING SHALL BE CONTROLLED VIA TIMECLOCK WITH A MASTER OVERRIDE SWITCH INSTALLED IN ACCORDANCE WITH THE FLORIDA ENERGY CODE. All EXIT do EMERGENCY LIGHTING FIXTURES SHALL BE PROVIDED WITH A 90 MINUTE (MINIMUM) EMERGENCY BATTERY AND CONNECTED TO THE NEAREST 'LOCAL' LIGHTING CIRCUIT AHEAD OF ANY SWTC RING. THE ELECTRICAL CONTRACTOR SHALL COORDINATE WITH ALL OTHER TRADES IN LOCATING DEVICES, WIRING, CONDUIT, AND EQUIPMENT TO AVOID ANY INTERFERENCE. ALL WIRING INSTALLED IN RETURN PLENUM SHALL BE UL LISTED FOR PLENUM INSTALLATION OR RUN IN CONDUIT IN ACCORDANCE WITH THE FLORIDA ELECTRICAL CODE CONTRACTOR TO VERIFY ALL SWITCH LOCATIONS WITH OWNER. CONTRACTOR TO INSTALL ALL WORK IN STRICT COMPLIANCE WITH LOCAL CODES AND ORDINANCES. SEE ARCHITECTURAL SHEETS FOR LIGHT FIXTURE SCHEDULE. KFYF n KI OTF q PROVIDE ROUGH —IN AND FINAL CONNECTION TO STOREFRONT SIGN. COORDINATE LOCATION AND REQUIREMENTS WITH SIGN VENDOR. CIRCUIT EXTERIOR BUILDING UGHTS AND BUILDING SIGNS VIA AUTOMATIC TIME SWITCH WITH PHOTOCELL OVERRIDE. PROVIDE ROUGH —IN AND FINAL CONNECTION TO RESTROOM EXHAUST FAN. COORDINATE ALL WORK WITH MECHANICAL CONTRACTOR. uunnuum — AREA OF WORK ELECTRICAL LIGHTING PLAN SCALE: 3116" = 1' -0" KEY PLAN SCALE: 1" = 50' -0" W N design, inc. p.o. box 14.2116 coral gables, florida 33114.2116 v. 305.443.3100 f. 305.259.3986 e. info @whadesign.com architect of record: William Arthur License Number. 0012074 ``t%IIIIIIJ/ * y4F nn� W . ;w � E:z w www� design associate: bFORD These plans and specifications are the exclusive property of WHA Design. Any reproduction, modification, disclosure, and/or use of these materials (or any portion thereof) without WHA Design's prior written consent is strictly prohibited { �w nn� W w www� III / Cn ., .� a) d .� .�Cl)� Co C coc- 0 0 C�Li C!3 -0c ++ 0 y C a ;z project history: A A A A