14-952-031GENERAL NOTES 1. THIS CONTRACTOR SHALL COORDINATE WITH ALL OTHER TRADES IN LOCATING DUCTWORK, PIPING AND EQUIPMENT TO AVOID ANY INTERFERENCE. 2. COORDINATE INSTALLATION OF NEW DUCT W/ STRUCTURE. 3. CONTRACTOR TO INSTALL ALL WORK IN STRICT COMPLIANCE WITH LOCAL CODES AND ORDINANCES. 4. MECHANICAL CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND EQUIP. SUBMITTAL PRIOR TO INSTALLING OR FABRICATING ANY DUCTWORK. 5. PROVIDE FIBERGLASS INSULATION BLANKET ABOVE TOPS OF ALL SUPPLY AIR DIFFUSERS. 6. PROVIDE ADJUSTABLE VOLUME DAMPER AT ALL SUPPLY BRANCH, RETURN DUCTWORK AND EXHAUST REGISTER. 7. PROVIDE TURNING VANES AT ALL ELBOWS (TYPICAL). 8. MECHANICAL CONTRACTOR TO REPLACE FILTER AFTER CONSTRUCTION COMPLETED. 9. MECHANICAL CONTRACTOR TO PROVIDE 12' HIGH REFLECTIVE UNIT NUMBERS WITH SPECIFIC A/C UNIT # TO BE POSTED ON EACH UNIT ON THE CONTROL PANEL DOOR AND SIDE WITH THE DISCONNECT IN LOCATION VISIBLE FROM THE ROOF HATCH. NOTE: TESTING AND BALANCING REPORT SHALL BE COMPLIED AND BE AVAILABLE PRIOR TO FINAL INSPECTION AND COPY OF THE REPOT SHALL BE PROVIDE TO THE OWNER'S REPRESENTATIVE. - KEYED NOTES QPROVIDE AND INSTALL NEW ROOF TOP UNIT AS SHOWN IN SCHEDULE ON THIS SHEET UNIT SHALL BE LOCATED SUCH THAT SUPPLY AND RETURN DUCTWORK DROP BETWEEN JOISTS. RUN CONDENSATE LINE TO NEAREST EXISTING CONDENSATE DISCHARGE. VERIFY LOCATION OF DRAIN IN FIELD. VERIFY OUTSIDE AIR INTAKE IS A MINIMUM OF 10' FROM ANY EXHAUST OR FLUE. MODIFY EXISTING ROOF OPENING FOR RTU -1,2,3 CURB INSTALLATION. PROVIDE AND INSTALL U.L LISTED IONIZATION TYPE SMOKE DETECTOR INTERLOCKED WITH RTU CONTROLS TO SHUT RTU DOWN UPON ACTIVATION OF DETECTOR. LOCATE IN SUPPLY AIR DUCTWORK. �3 PROVIDE AND INSTALL ONE PIECE PROGRAMMABLE THERMOSTAT AT 54" AF.F. PER ADA. COORDINATE LOCATIONS WITH OTHER ELEMENTS OF WALL /COLUMN. VERIFY EXACT LOCATIONS IN FIELD. ALL THERMOSTATS ON EXTERIOR WALL TO BE MOUNTED ON INSULATED BACK BOARD. EXTEND 8'0 EXHAUST DUCT DOWN FROM EF -1 ON ROOF AND CONNECT TO EXHAUST GRILLES IN TOILET ROOM. BALANCE AS INDICATED. PROVIDE BACK DRAFT DAMPER AT EACH GRILLE. SEE FAN DETAIL ON SHEET M -2 AND FAN SCHEDULE ON THIS SHEET. VERIFY FAN OUTLET IS 10' MINIMUM FROM ANY AIR INTAKE, VERIFY LOCATION. OUTSIDE AIR CALCULATION BASED FBC TABLE 403.3 PLAN MARK 1, Summary Ventilation Sizing Method ........ ............................ Sum of Space OA Airflows Design Ventilation Airflow Rate ................................. ............................... 2017 CFM 2. Space Ventilation Analysis Table MODULE FRAME Zone Name l Space Name Mutt. Floor Area (tl ;} Maximum Occupants Maximum Supply Air ': (CFM) Required Outdoor Air (CFNUpersan) Required Outdoor Air (CFMIR2) Uncorrected Outdoor Ai (CFM S3 TITUS TDC -AA Zone 1 DRYWALL R1 TITUS PAR -AA 24x24 LAY -IN E1 TITUS 5OF 12x12 LAY-IN SALES 1 8722.0 70.0 7134.2 0.00 0.30 2018. 0 ft2 0 RR passage 11 223.01 2.01 202.41 0.001 0.001 01 0 Door Loads storage 1 750.0 0.01 598.8 0.001 0.00 o. 13 -20 7695 W Totals rind. Space Multipliers} Partitions 01112 0 78334 0 ft2 0 2018. oft2 0 IN (WC) 0V PROVIDE TOTAL 2150 CFM AIR DEVICE SCHEDULE PLAN MARK MANUFACTURER\ MODEL NUMBER MODULE FRAME S1 TITUS TDC -AA 2424 LAY -IN S2 TITUS TDC -AA 2424 DRYWALL S3 TITUS TDC -AA 12x12 DRYWALL R1 TITUS PAR -AA 24x24 LAY -IN E1 TITUS 5OF 12x12 LAY-IN ALL TITUS DIFFUSERS do GRILLES SHALL BE ALUMINUM. PROVIDE TITUS SECTORIZING BAFFLE AS REQUIRED WHERE DIRECTIONAL ARROWS ARE SHOWN ON PLAN. AIR DEVICE LEGEND RETURN EXHAUST DUCT NECK SIZE t..t.: D. 1/ « 11 « HVAC LEGEND SYMBOL. DESCRIPTION MSUPPLY AIR DIFFUSER ZRETURN AIR GRILLE ® TOILET ROOM EXHAUST GRILL + SPRINKLER HEAD 0 DUCT MOUNTED SMOKE DETECTOR -�-�~ DIRECTION OF AIR FLOW Q THERMOSTAT (CONTROLLER) LOAD CALCULATION (SUMMARY) PLAN MANUFACTURER DESIGN COOLING DESIGN HFATIN SP COOLING DATA'ATJLd 140V1 COOLI NG OA D51 WB 80.7 °F / 76.9 °F HEATING DATA AT DES HTS HFAMNG dA D8 / WS ?4 &0 °F zoNELOADS Details Sensible (BTU/tr) Latent i Detatis SanstWv (B uffiry Window & Skylight Solar Loads 01112 0 EXTERNAL 0 ft2 - Wall Transmission 3087 ft2 5153 EF -1 3087 ft2 5963 Roof Transmission 7695 111:2 54962 120/1 /60 1/6 HP 7695 ft2 18539 Window Transmission 0 ft2 0 __ 0 ft2l 0 ,WghtTransrrission oft2 0 MOTOR 01ft2 0 Door Loads 84 ft2 1480 �-� 84 ft2 927 Flocr Transmission 7695 ft2 0 13 -20 7695 W 3472 Partitions 01112 0 0 ft2 0 Ceiling oft2 0 IN (WC) 0V 0 Overhead Lighting 11633 WI 33693 OUTPUT (MBH) 0 0 Task Lighting 6722 W 21010 0 0 Electric Equipment 0 W 0 0 0 People 72 15763 19140 0 0 Infiltration 929/7.5 0 0 - 0 Miscellaneous 0 0 - 0 Safety Factor 10%110%1 13206 1914 10% 2890 >> TotalZone Loads 1228 145267 21Q54 TTRANE 31791 Zone Conditioning - 160102 21054 33471 Plenum Wag Load 0",b 0 0 0 Plenum Roof Load NO 0 - 0 0 Plenum Lighting Load 0"k 0 0 0 Return Fan Load 7783 CFM 0 0.5' 7783 CFM 0 Ventilation Load 2017 CFM 30397 64329 2017 CFM '52098 Supply Fan Load 7933 CFM 2941 THROW AWAY 7933 CFM -2941 Space Fan Coil Fans - 0 60 - 0 Duct Heat Gain / Loss 00/0 0 0%1 0 >Total 'System Loads 193439 $5363 82Ei2$ Central Coding Coil 193439 85400 0 Central Heating Cal 0 - 82628 EXHAUST FAN SCHEDULE PLAN MANUFACTURER MODEL TYPE SP CFM ELECTRICAL OPTIONS SONES REMARKS CONTROL MARK PLAN MANUFACTURER SUPPLY OUTSIDE EXTERNAL COOLING CAPACITY rUL_ TY HEATING CAPACITY Cn W:_ _E EF -1 GREENHECK GB -071 -6 ROOF MID 0.25" 150 120/1 /60 1/6 HP ROOF CURB BACKDRAFT DAMPER 4.8 F.C.I.C. TIMER RELAY ©IE= M. I+ CM H 0 N IMN N iii -1- rm n MECHANICAL PLAN SCALE: 3/16" = 1' -0" a Cn r x 0. .4 design, inc....4' ry x p.o. box 14.2116 coral gables, florida 33114.2116 v. 305.443.3100 f. 305.259.3986 e. info @whadesign.com architect of record: William Arthur License Number: 0012074 �,4�`tttitrrt� `% DEL. ..... `mil ,• .,,� r i `. V O 4 design associate: LIFORD These plans and specifications are the exclusive property of WHA Design. Any reproduction, modification, disclosure, and/or use of these materials (or any portion thereof] without WHA Design's prior written consent is strictly prohibited. s ROOFTOP UNIT SCHEDULE co W 0. PLAN MANUFACTURER SUPPLY OUTSIDE EXTERNAL COOLING CAPACITY rUL_ TY HEATING CAPACITY Cn W:_ _E DEGREES AIR F AMBIENT FILTER HEATING COOLING T -STAY o ca �.. 0 >_ OPERATING __ MARK MODEL. AIR (CFM) AIR (CFM) S.P. MOTOR AIR TYPE STAGE(S) STAGE(S) TYPE �-� PH HZ MCA/MOCP WEIGHT NOTES 13 -20 NG NG NUMBER MIN. IN (WC) MBH/TON EER /SEER SENSIBLE(MBH) INPUT(MBH) OUTPUT (MBH) ELEC.( KW/hIIBH) DRY BULB WET BULB (DEG F) LBS. RTU -1 3000 550 0.5' 1.00 HP 929/7.5 12.6/ 68.63 - - 13.5/46.06 78 67 95' THROW AWAY TWO TWO PROGRAMM. 208 3 60 57.5/60 1228 1"2,3,4,5,6 TTRANE RTU -2 2000 375 0.5' 1.00 HP 63.49/5 /15 47.33 - - 4.5/15.35 78 67 95' THROW AWAY ONE ONE ONE CE IE 208 3 60 30.0/45 1025 1"2,3,4,5,6 TTRANE RTU -3 2000 375 0.5' 1.00 HP 63.49/5 /15 47.33 - - 4.5/15.35 78 67 95' THROW AWAY ONE ONE PRIM. 208 3 60 30.0/45 1025 1,2,3,4,5,6 THC60E RTU -4 60E 2000 375 0.5' 1.00 HP 63.49/5 /15 47.33 - - 4.5/15.35 78 67 95' THROW AWAY ONE ONE ONECRPIIECE 208 3 60 30.0/45 1025 1,2,3,4,5 TTR RTU -5 TRANE 2000 375 0.5' 1.00 HP 63.49/5 /15 47.33 - - 4.5/15.35 78 67 95• THROW AWAY ONE ONE ONE PIECE 208 3 60 30.0/45 1025 1,2,3,4,5 THC060E RTU -6 1200 100 0.5' 0.75 HP 38.49/3 /13 27.94 - - 4.5/15.35 78 67 95' THROW AWAY ONE ONE ON 208 3 60 23.1 - 773 1,2,3,4,5 THC036E NOTES: 1. PROVIDE WITH FACTORY ROOF CURB, ECONOMIZER (O.A. HOOD FOR RTU -6) WITH BAROMETRIC RELJEF, AND SUPPLY SMOKE DETECTOR. 2. CONTRACTOR SHALL INSTALL ALL NEW FILTERS PRIOR TO TEST AND BALANCE WORK. -' 1 S 0 3. RUN CONDENSATE LINE TO NEAREST EXISTING CONDENSATE DISCHARGE. 4. PROVIDE WITH FACTORY FITTED BURGLAR BARS, PRODIGY M2 WITH BACNET CONTROLS, HACR BREAKERS, NON -FUSED SERVICE DISCONNECTS, GFis ETC. 5. PROVIDE WITH OVERFLOW PROTECTION DEVICE INSIDE OF THE PRIMARY DRAIN PAN WITH WATER LEVEL MONITORING. 6. MODIFY EXISTING ROOF OPENING FOR CURB INSTALLATION. n MECHANICAL PLAN SCALE: 3/16" = 1' -0" a Cn r x 0. .4 design, inc....4' ry x p.o. box 14.2116 coral gables, florida 33114.2116 v. 305.443.3100 f. 305.259.3986 e. info @whadesign.com architect of record: William Arthur License Number: 0012074 �,4�`tttitrrt� `% DEL. ..... `mil ,• .,,� r i `. V O 4 design associate: LIFORD These plans and specifications are the exclusive property of WHA Design. Any reproduction, modification, disclosure, and/or use of these materials (or any portion thereof] without WHA Design's prior written consent is strictly prohibited. s a.. E n KEY PLAN SCALE: 1" = 50' -0' sheet title: MECHANICAL PLAN sheet number: M ii ■ 0 file: 884 -13 m1.0.dwg L co W 0. EM E � rUL_ Cn W:_ _E U) "X 0 6 .m � Co o ca �.. 0 >_ ° CEO Co G __ U ax o � N 3 CL o project history: A A A project information: date: 07/08/13 project number: 13 -20 a.. E n KEY PLAN SCALE: 1" = 50' -0' sheet title: MECHANICAL PLAN sheet number: M ii ■ 0 file: 884 -13 m1.0.dwg