14-952-0301. THIS CONTRACTOR SHALL COORDINATE WITH ALL OTHER TRADES IN LOCATING
DUCTWORK, PIPING AND EQUIPMENT TO AVOID ANY INTERFERENCE.
2. COORDINATE INSTALLATION OF NEW DUCT W/ STRUCTURE.
3. CONTRACTOR TO INSTALL ALL WORK IN STRICT COMPLIANCE WITH LOCAL
CODES AND ORDINANCES.
4. MECHANICAL CONTRACTOR SHALL SUBMIT SHOP DRAWINGS AND EQUIP.
SUBMITTAL PRIOR TO INSTALLING OR FABRICATING ANY DUCTWORK.
5. PROVIDE FIBERGLASS INSULATION BLANKET ABOVE TOPS OF ALL SUPPLY AIR
DIFFUSERS.
6. PROVIDE ADJUSTABLE VOLUME DAMPER AT ALL SUPPLY BRANCH, RETURN
DUCTWORK AND EXHAUST REGISTER.
7. PROVIDE TURNING VANES AT ALL ELBOWS (TYPICAL).
8. MECHANICAL CONTRACTOR TO REPLACE FILTER AFTER CONSTRUCTION
COMPLETED.
9. MECHANICAL CONTRACTOR TO PROVIDE 12" HIGH REFLECTIVE UNIT NUMBERS
WITH SPECIFIC A/C UNIT # TO BE POSTED ON EACH UNIT ON THE CONTROL
PANEL DOOR AND SIDE WITH THE DISCONNECT IN LOCATION VISIBLE FROM THE
10. PROVIDE RTU AUTOMATIC O.A. DAMPER SHUT -OFF CONTROL DURING
UNOCCUPIED MODE.
F914ftemius
MIN. DUCT CONNECTION/
NECK SIZE
f.-- TAG - -
�Ja AIR FLOW------ _
, X: CF
�614" 0911 Lire] 19
PROVIDE AND INSTALL NEW ROOF TOP UNIT AS SHOWN IN SCHEDULE ON THIS
SHEET. UNIT SHALL BE LOCATED SUCH THAT SUPPLY AND RETURN DUCTWORK DROP
BETWEEN JOISTS. RUN CONDENSATE LINE TO NEAREST EXISTING CONDENSATE
DISCHARGE. VERIFY LOCA11ON OF DRAIN IN FIELD. VERIFY OUTSIDE AIR INTAKE IS A
MINIMUM OF 10' FROM ANY EXHAUST OR FLUE. MODIFY EXISTING ROOF OPENING FOR
RTU -1,2,3 CURB INSTALLATION.
PROVIDE AND INSTALL U.L LISTED IONIZA11ON TYPE SMOKE DETECTOR INTERLOCKED
WITH RTU CONTROLS TO SHUT RTU DOWN UPON ACTIVATION OF DETECTOR. LOCATE
IN SUPPLY AIR DUCTWORK.
PROVIDE AND INSTALL ONE PIECE PROGRAMMABLE THERMOSTAT AT 54" AF.F. PER
ADA. COORDINATE LOCATIONS WITH OTHER ELEMENTS OF WALL /COLUMN. VERIFY
EXACT LOCATIONS IN FIELD. ALL THERMOSTATS ON EXTERIOR WALL TO BE MOUNTED
ON INSULATED BACK BOARD.
EXTEND 8 "0 EXHAUST DUCT DOWN FROM EF -1 ON ROOF AND CONNECT TO EXHAUST
GRILLES IN TOILET ROOM AND ABOVE MOP SINK. BALANCE AS INDICATED. PROVIDE
BACK DRAFT DAMPER AT EACH GRILLE. SEE FAN DETAIL ON SHEET M -2 AND FAN
SCHEDULE ON THIS SHEET. VERIFY FAN OUTLET IS 10' MINIMUM FROM ANY AIR
INTAKE, VERIFY LOCATION.
OUTSIDE AIR CALCULATION
BASED FBC TABLE 403.3
PLAN
MARK
1. Summary
Ventilation Sizing Method ........ ............................ Sum of Space OA Airflows
Design Ventilation Airflow Rate ................................. ............................... 2017 CFM
2. S ace Ventilation Analysis Table
MODULE
FRAME
Zone Name I Space Name
Mult
Floor
Area
(ft =)
Maximum
Occupants
Maximum
Supply Air
(CFM)
Required
Outdoor Air
(CFM/person)
Required
Outdoor Air
(CFM/Rx)
Uncorrected
Outdoor Ai
(CFM
S3
TITUS TDC -AA
Zone 1
DRYWALL
R1
TITUS PAR -AA
24x24
LAY -IN
E1
TITUS 50F
12x12
LAY -IN
SALES
11
6722.0
70.0
7134.2
0.00
0.30
20161
TIMER RELAY
.E
RR passage
1
223.0
2.0
202.41
0.001
0.00
01
AIR
TYPE
storage
1
750.0
0.0
596.8
0.00
0.001
01
NOTES
4
Totals find. Space Multi
C
O
NG
NG
79334
= 20113.
NUMBER
MIN.
IN (WC)
PROVIDE TOTAL 2150 CFM
AIR DEVICE SCHEDULE
PLAN
MARK
MANUFACTURER\
MODEL NUMBER
MODULE
FRAME
S1
11TUS TDC -AA
24x24
LAY -IN
S2
TITUS TDC -AA
2424
DRYWALL
S3
TITUS TDC -AA
12x12
DRYWALL
R1
TITUS PAR -AA
24x24
LAY -IN
E1
TITUS 50F
12x12
LAY -IN
ALL TITUS DIFFUSERS do GRILLES SHALL BE
ALUMINUM.
PROVIDE TITUS SECTORIZING BAFFLE AS REQUIRED
WHERE DIRECTIONAL ARROWS ARE SHOWN ON PLAN.
HVAC LEGEND
YES
NO
'o'
SE-
SP
r•
ELECTRICAL
TOILET • OOO EMAUST GRILL
FIRE DAMPER(S)
REMARKS
r%
DUCT MOUNTED SMOKE DETECTOR
CL
DIRECTION OF
FIRE RATED ENCLOSURE
T THERMOSTAT t •O 7•
HVAC DESIGN REQUIRES:
YES
NO
MODEL
TYPE
SP
DUCT SMOKE DETECTOR
ELECTRICAL
OPTIONS
FIRE DAMPER(S)
REMARKS
r%
SMOKE DAMPER(S)
CL
PLAN
FIRE RATED ENCLOSURE
SUPPLY
OUTSIDE
FIRE RATED ROOF ASSEMBLY
>1
COOLING CAPACITY
FIRE STOPPING
HEATING CAPACITY
EF -1
SMOKE CONTROL
GB -081 -6
ROOF MTD
EXHAUST FAN SCHEDULE
PLAN
MANUFACTURER
MODEL
TYPE
SP
CFM
ELECTRICAL
OPTIONS
SONES
REMARKS
CONTROL
MARK
CL
PLAN
MANUFACTURER
SUPPLY
OUTSIDE
EXTERNAL
>1
COOLING CAPACITY
HEATING CAPACITY
EF -1
GREENHECK
GB -081 -6
ROOF MTD
0.25"
225
120/1 /60 1/6 HP
ROOF CURB
BACKDRAFT DAMPER
4.8
F.C.I.C.
TIMER RELAY
MECHANICAL PLAN
SCALE: 3/16" = V -0"
L-0
C�t"Sfign, 1110ill
p.o. box 14.2116
coral gables, florida
33114.2116
v. 305.443.3100
f. 305.259.3986
e. info @whadesign.com
architect of record:
William Arthur
License Number: 0012074
�tttrr' art
.,, 2 +•
4 ,
.".n V • A /1n
• ')� Sf ATE
ORI
NA
design associate:
bFORD
These plans and specifications are
the exclusive property of WHA
Design. Any reproduction,
modification, disclosure, and/or use
of these materials (or any portion
thereof] without WHA Design's prior
written consent is strictly prohibited.
c�
ROOFTOP
UNIT SCHEDULE
L
(D
CL
PLAN
MANUFACTURER
SUPPLY
OUTSIDE
EXTERNAL
>1
COOLING CAPACITY
HEATING CAPACITY
ENTERING
DEGREES
AIR
F
AMBIENT
FILTER
HEATING
COOLING
T -STAT
i-i
U_
.E
OPERATING
MARK
MODEL
AIR (CFM}
AIR (CFM)
S.P.
MOTOR
AIR
TYPE
STAGS
(}
STAGES
()
TYPE
�-�'
PH
HZ
MCA/MQCP
WEIGHT
NOTES
4
C
O
NG
NG
NUMBER
MIN.
IN (WC)
MBH/TON
EER /SEER
SENSIBLE(MBH)
INPUT(MBH)
OUTPUT (MBH)
ELEC.(KW/MBH)
DRY BULB
WET BULB
(DEG F)
LBS
RTU -1
1TRANE
3000
550
0.5'
1.00 HP
929/7.5
12.6/
68.63
-
-
13.5/46.06
78
67
95'
THROW AWAY
TWO
TWO
PROGRAMM.
208
3
60
57.5/60
1228
1,2,3,4,5,6
RTU-2
T R E
2000
375
0.5"
1.00 HP
63.49/5
/15
47.33
-
-
4.5/15.35
78
67
95'
THROW AWAY
ONE
ONE
ONE PIECE
208
3
60
30.0/45
1025
1,2.3,4,5.6
RTU -3
TTRANE
2000
375
0.5'
1.00 HP
63.49/5
/15
47.33
-
-
4.5/15.35
78
67
95'
THROW AWAY
ONE
ONE
ONE(�RCE PIE
208
3
60
30.0/45
1025
1,2,3.4,5,6
RTU -4
THC 60E
2000
375
0.5"
1.00 HP
63.49/5
/15
47.33
-
-
4.5/15.35
78
67
95'
THROW AWAY
ONE
ONE
PROGRPIAMM.
208
3
60
30.0/45
1025
1,2,3.4.5
RTU -5
TTRANE
2000
375
0.5"
1.00 HP
63.49/5
/15
47.33
-
-
4.5/15.35
78
67
95'
THROW AWAY
ONE
ONE
ONEGRCE PIE
208
3
60
30.0/45
1025
1,2,3.4,5
RTU -6
TRANE 036E
TH
1200
100
0.5"
0.75 HP
38.49/3
/13
27,94
-
-
4.5/15.35
78
67
95'
THROW AWAY
ONE
ONE
PIECE
208
3
60
23.1/30
773
1,2,3,4,5
N NOTES:
1. PROVIDE WITH FACTORY ROOF CURB, ECONOMIZER (O.A. HOOD FOR RTU -6) WITH BAROMETRIC RELIEF, AND SUPPLY SMOKE
DETECTOR.
2. CONTRACTOR SHALL INSTALL ALL NEW FILTERS PRIOR TO TEST AND BALANCE WORK.
3. RUN CONDENSATE LINE TO NEAREST EXISTING CONDENSATE DISCHARGE.
4. PROVIDE WITH FACTORY FITTED BURGLAR BARS, PRODIGY M2 WITH BACNET CONTROLS, HACR BREAKERS, NON -FUSED SERVICE DISCONNECTS, GFIs ETC.
5. PROVIDE WITH OVERFLOW PROTECTION DEVICE INSIDE OF THE PRIMARY DRAIN PAN WITH WATER LEVEL MONITORING.
6. MODIFY EXISTING ROOF OPENING FOR CURB INSTALLATION.
MECHANICAL PLAN
SCALE: 3/16" = V -0"
L-0
C�t"Sfign, 1110ill
p.o. box 14.2116
coral gables, florida
33114.2116
v. 305.443.3100
f. 305.259.3986
e. info @whadesign.com
architect of record:
William Arthur
License Number: 0012074
�tttrr' art
.,, 2 +•
4 ,
.".n V • A /1n
• ')� Sf ATE
ORI
NA
design associate:
bFORD
These plans and specifications are
the exclusive property of WHA
Design. Any reproduction,
modification, disclosure, and/or use
of these materials (or any portion
thereof] without WHA Design's prior
written consent is strictly prohibited.
project history:
1a Mechanical 10 -07-14
A
A
A
project information:
date:
07/08/13
project number:
13 -20
MECHANICAL
PLAN
sheet number:
V
n
KEY PLAN M100
SCALE• 1" = 50' -0" file:
884 -13 m1.0.dwg
c�
L
(D
CL
>1
E M
cn
i-i
U_
.E
•X
0 5 t6
.
�-' u)
Q
CU C =�
o
N
:3 V
0
�
E
(0(/)
O
4
C
O
Q
project history:
1a Mechanical 10 -07-14
A
A
A
project information:
date:
07/08/13
project number:
13 -20
MECHANICAL
PLAN
sheet number:
V
n
KEY PLAN M100
SCALE• 1" = 50' -0" file:
884 -13 m1.0.dwg