14-1268-019NUMBERS 1NDICATE CIRCUIT. NOTE: HASH MARKS
INDICATES THE NUMBER OF WIRES EXCLUDING
THE REQUIRED EQUIPMENT GROUND.
ELECTRICAL SYME30L LEGEND
SYMBOL
DESCRIPTI ❑N
M ❑UNTING
i A -
1 X 4 FLUORESCENT FIXTURE
SEE FIXTURE
Pei
LETTER INDICATES TYPE
SCHEDULE
2 X 4 FLUORESCENT FIXTURE
SEE FIXTURE
Q
FAN • — AIR HANDLER SHUTDOWN RELAY
LETTER INDICATES TYPE
SCHEDULE
®SHADING
DENOTES FIXTURE WITH EM BATTERY PACK.
SEE FIXTURE
48" AFF
AS NOTED
..
NL' DENOTES FIXTURE UNSWITCHED FOR NIGHT LIGHT
SCHEDULE
FLUORESCENT STRIP FIXTURE
SEE FIXTURE
LETTER INDICATES TYPE
SCHEDULE
FLUORESCENT WALL BRACKET FIXTURE
SEE FIXTURE
LETTER INDICATES TYPE
SCHEDULE
PL FLUORESCENT DOWNLiGHT
SEE FIXTURE
LETTER INDICATES TYPE
SCHEDULE
EXIT -OR EM EXIT. LETTER
SEE FIXTURE
INDICATES TYPE. PROVIDE ARROWS AS REQUIRED.
SCHEDULE
SINGLE POLE SWITCH (20A- 120/211)
48" AFF OR AS
S S3 So
'3' DENOTES 3 -WAY 'O' DENOTES OCCUPANCY SENSOR
NOTED
A)__
DUPLEX RECEPTACLE, 125V, 20A
18" AFF OR AS
`IG' DENOTES ISOLATED GROUND
NOTED
+�
DUPLEX RECEPTACLE, 125V, 20A
18" AFF OR AS
NOTED
&
DUPLEX RECEPTACLE, 125V, 20A
48" AFF OR AS
NOTED
QUADRAPLEX RECEPTACLE, 125V, 20A
18" AFF OR AS
NOTED
V
COMBINATION VOICE/DATA OUTLET
18" AFF OR AS
NOTED
®
T.Y. OUTLET
18" AFF OR AS
NOTED
®
PANEL50ARD 120/240Y
SEE PANEL
SCHEDULE
/i
RACEWAY CONCEALED IN WALL OR ABOVE CEILING
SEE SPECIFICATIONS
HOMERUN TO PANEL. LETTERS INDICATE PANEL,
SEE SPECIFICATIONS
NUMBERS 1NDICATE CIRCUIT. NOTE: HASH MARKS
INDICATES THE NUMBER OF WIRES EXCLUDING
THE REQUIRED EQUIPMENT GROUND.
NOTE: ALL MOUNTING HEIGHTS SHOWN ARE TO THE TOP OF THE
DEVICE UNLESS NOTED OTHERWISE.
NOT ALL SYMBOLS APPEAR ON PLANS,
ABBREVIATIONS:
AFF - ABOVE FINISHED FLOOR
AHU - AIR HANDLING UNIT
EFG - BELOW FINISHED GRADE
C CONDUIT
CW - COOL WHITE
DACP - DOOR ALARM CONTROL PANEL
DN - DOWN
EF - EXHAUST FAN
EG - EQUIPMENT GROUND
ENCL - ENCLOSURE
EWC - ELECTRIC WATER COOLER
EWH - ELECTRIC WATER HEATER
EX - EXISTING
FCU - FAN COiL UNIT
FHP - FRACTIONAL HORSE POWER
FLA - FULL LOAD AMPERES
G - GROUND
GFI - GROUND FAULT INTERRUPTER
HiD - HiGH INTENS15TY DISCHARGE
HORIZ - HORIZONTAL
IG - ISOLATED GROUND
LW - LIGHT WHITE
HP - HORSEPOWER, HEAT PUMP
HVAC - HEATING, BENTiLATING, AIR CONDITIONING
JB - JUNCTION BOX
LRA - LOCKED ROTOR AMPERES
MCE - MAiN CiRCUiT BREAKER
MLO - MAIN LUGS ONLY
N - NEW
NL - NIGHT LIGHT
OB - OUTLET BOX
PB - PULL SOX, PUSH - SUTTON
R - RELOCATED
RECEPT - RECEPTACLE
SF - SUPPLY FAN
SPEC - SPECIFICATIONS
SWEGS - SMOKE WARNING EMERGENCY CALL SYSTEM
TL - TWiSTLOCK
TTB - TELEPHONE TERMINAL BOARD
TVTB - TELEVISION TERMINAL BOARD
UNO - UNLESS NOTED OTHERWISE
VERT - VERTICAL
WI- 1 - WATT MISER
WP - WEATHERPROOF
WW - WARM WHITE
XFMR - TRANSFORMER
System No. C -AJ -1259
F Rating - 3 Hr
T Rating - 0 Hr
L--.W,— A
Section A -A
1. Floor or Wall Assembly - Min 4 -1/2 in, thick reinforced lightweight or normal weight (100 -150 pco concrete. Floor may also be
constructed of any min 6 in. thick UL Classified hollow -core Precast Concrete Units *. Wall may also be constructed of any UL
Classified Concrete Blocks *. Max diam of opening is 7 in.
See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of
manufacturers.
2. Through Penetrants - One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the
firestop system. The annular space between the pipe, conduit or tubing and the periphery of the opening shall be a min of 0 in.
(point contact) to a max of 3 in. Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The
following types and sizes of metallic pipes, conduit or tubing may be used:
A. Steel Pipe - Nom 6 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe - Nom 6 in. diam (or smaller) cast or ductile iron pipe.
C. Conduit - Nom 4 in. diam (or smaller) steel electrical metallic tubing or steel conduit.
D. Copper Tube - Nom 4 in. diam (or smaller) Type L (or heavier) copper tube.
3. Forming Material - (Optional, Not Shown) - Mineral wool batt packing material or polyurethane backer rod friction fitted into
opening and recessed from floor or wall surfaces as required to accommodate required thickness of fill material.
4. Fill, Void or Cavity Material* - Sealant - Min 1/2 in. thickness of fill material applied within the annulus, flush with both
surfaces of floor or wall. At the point contact location between penetrating item and concrete, a min 1/4 in. thick bead of fill
material shall be applied at the concrete /penetrating item interface on both sides of floor or wall.
SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant
*Bearing the UL Classification Mark
—® �ecified Technologies Inc. 210 Evans Way Somerville, NJ 08876
® Reproduced courtesy of Underwriters Laboratories, Inc. @C-AJ-1259 [T� Created or Revised: January 2, 2009 11 800 992 -1180. 908 526-8000 • FAX 908 231 -8415 + E- Mail:techsery stifiresto com • Website :www.sbfiresto com AGE
( ) ( } ( } @ P• P� PAGE 1 OF 1
System No. W -L -1079
F Ratings -1 and 2 Hr (See Item 1B)
T Rating - 0 Hr
L Rating At Ambient - Less Than 1 CFM /sq ft
L Rating At 400 F - Less Than 1 CFM/sq ft
A
0
,'1. VIGIIon IA -,H
1. Wall Assembly - The 1 or 2 hr fire -rated gypsum board /stud wall assembly shall be constructed of the materials and in the
manner described in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall
include the following construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in.
lumber spaced 16 in. OC with nom 2 by 4 in. lumber end plates and cross braces. Steel studs to be min 3 -5/8 in. wide and
spaced max 24 in. OC.
B. Gypsum Board* - 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum board type, thickness, number of
layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire
Resistance Directory. Max diam of opening is in wood stud walls is 13 in. Max diam of opening in steel stud walls is 16 in.
The hourly F rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed.
2. Through Penetrant - One metallic pipe or conduit to be installed either concentrically or eccentrically within the firestop
system. The annular space between pipes or conduits and periphery of opening shall be min 0 in. (point contact) to max 3 in.
Pipe or conduit to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes or
conduits may be used:.
A. Steel Pipe - Nam 12 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe - Nom 12 in. diam (or smaller) cast or ductile iron pipe.
C. Conduit - Nom 4 in. diam (or smaller) electrical metallic tubing, nom 6 in. diam (or smaller) steel conduit or nom 1 in. diam
(or smaller) flexible steel tubing.
D. Copper Pipe - Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe.
E. Copper Tube - Nam 6 in. diam (or smaller) Type L (or heavier) copper tube.
Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876
�. Reproduced courtesy of Underwriters Laboratories, inc. (9)
1 1. Created or Revised: January 2,2009
1 800 992 -1180. 908 526 -8000 • FAX 908 231 -8415 • E- Mail:techsery stifiresto com • Website:www.stifiresto com W -L-10 F
t ) ( ) t } @ P• P• PAGE 1 OF 2
Walt Opening Protective Materials (CLIV)
SPECIFIED TECHNOLOGIES INC R14288
SUITE 2 200 EVANS WAY, SOMERVILLE, NJ 08876 USA
SpecSeal Putty Pads, for use with max 4 -11/16 by 4 -11/16 in. flush device UL Listed metallic
outlet boxes installed with steel cover plates in 1 and 2 h fire rated gypsum wallboard wall assemblies
framed with mint 3 -1/2 in. deep wood or steel studs and constructed of the materials and in the manner
specified in the individual U300 or U400 Series Wall and Partition Designs in the Fire Resistance
Directory. Min 3/16 in. thick moldable putty pads are to be installed to completely cover the exterior
surfaces of the outlet box (except for the side of the outlet box against the stud) and completely seal
against the stud within the stud cavity. An additional 3/16 in. thickness of putty to be formed around
the connector securing the end of each electrical metallic tube or conduit to the box. When used with
metallic outlet boxes larger than 4 by 4 in., a ball of putty is to be installed to plug the open end of
each electrical metallic tube or conduit within the outlet box. When max 4 by 4 in, metallic outlet
boxes are used, the ball of putty in the open end of each electrical metallic tube or conduit within the
outlet box is optional. When moldable putty pad outlet box protective material is used on boxes on
both sides of wall as directed, the horizontal separation between outlet boxes on the opposite sides of
the wall may be less than 24 in. provided that the boxes are not installed back -to -back.
SpecSeal Putty Pads for use with max 4 by 3 -3/4 by 3 in. deep UL Listed Nonmetallic Outlet
Boxes manufactured by Carlon Electrical Products and made from polyvinyl chloride, max 4 by 3 -3/4
by 3 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Allied Moulded Products Inc. and
made from fiber - reinforced thermosetting plastic or max 4 -1/16 by 3 -5/8 by 3 -1/8 in. deep UL Listed
Nonmetallic Outlet Boxes manufactured by Thomas & Betts Corp. and made from fiber- reinforced
thermosetting plastic. Boxes shall also bear a 2 It rating under the "Outlet Boxes and Fittings Classified
for Fire Resistance" category in the Fire Resistance Directory. Boxes installed with steel or plastic
cover plates. Putty pads and boxes for use in I and 2 h fire rated gypsum wallboard/wood stud wafl .
assemblies constructed of the materials and in the manner specified in the individual U300 Series Wall
and Partition Designs in the Fire Resistance Directory. Outlet box secured to wood stud by means of
two nailing tabs in conjunction with nails supplied with the outlet box. Min 3/16 in. thick moldable
putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the
side of the outlet box against the stud) including nailing tabs and completely seal against the stud
within the stud cavity. An additional 3/16 in. thickness of putty to be formed around the end of each
nonmetallic sheathed cable at its connection to the box and to extend a minimum of 1 in. from the box
onto the nonmetallic sheathed cable within the stud cavity. When moldable putty pad outlet box
protective material is used on boxes on both sides of wall as directed, the horizontal separation
between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are
not installed back -to -back.
_1�
1C
(-R
..
Cn to
to
LO
..
11 Lo
•
co
O
MOTOR RATED SWITCH WITH OVERLOAD
RELAYS i - •
i A -
NON-FUS15LE SAFETY SWITCH-6 ZE AS NOTED
Pei
FIRE • • i- -• • •,
ALARM
- • i SUPPLY -
�• MOUNTED
DUCTWORK
Q
FAN • — AIR HANDLER SHUTDOWN RELAY
i i 4 • • •�
s
FIRE ALARM MANUAL FULLSTATION
48" AFF
AS NOTED
..
FIRE ALARM AUDIBLE/VISUAL SIGNAL. ADA
COMPAT15LE
• i •
_
i • •—
ON OR
AS NOTED
FIRE ALARM PANEL . - • i - • A,
"Em r w r
NOTE: ALL MOUNTING HEIGHTS SHOWN ARE TO THE TOP OF THE
DEVICE UNLESS NOTED OTHERWISE.
NOT ALL SYMBOLS APPEAR ON PLANS,
ABBREVIATIONS:
AFF - ABOVE FINISHED FLOOR
AHU - AIR HANDLING UNIT
EFG - BELOW FINISHED GRADE
C CONDUIT
CW - COOL WHITE
DACP - DOOR ALARM CONTROL PANEL
DN - DOWN
EF - EXHAUST FAN
EG - EQUIPMENT GROUND
ENCL - ENCLOSURE
EWC - ELECTRIC WATER COOLER
EWH - ELECTRIC WATER HEATER
EX - EXISTING
FCU - FAN COiL UNIT
FHP - FRACTIONAL HORSE POWER
FLA - FULL LOAD AMPERES
G - GROUND
GFI - GROUND FAULT INTERRUPTER
HiD - HiGH INTENS15TY DISCHARGE
HORIZ - HORIZONTAL
IG - ISOLATED GROUND
LW - LIGHT WHITE
HP - HORSEPOWER, HEAT PUMP
HVAC - HEATING, BENTiLATING, AIR CONDITIONING
JB - JUNCTION BOX
LRA - LOCKED ROTOR AMPERES
MCE - MAiN CiRCUiT BREAKER
MLO - MAIN LUGS ONLY
N - NEW
NL - NIGHT LIGHT
OB - OUTLET BOX
PB - PULL SOX, PUSH - SUTTON
R - RELOCATED
RECEPT - RECEPTACLE
SF - SUPPLY FAN
SPEC - SPECIFICATIONS
SWEGS - SMOKE WARNING EMERGENCY CALL SYSTEM
TL - TWiSTLOCK
TTB - TELEPHONE TERMINAL BOARD
TVTB - TELEVISION TERMINAL BOARD
UNO - UNLESS NOTED OTHERWISE
VERT - VERTICAL
WI- 1 - WATT MISER
WP - WEATHERPROOF
WW - WARM WHITE
XFMR - TRANSFORMER
System No. C -AJ -1259
F Rating - 3 Hr
T Rating - 0 Hr
L--.W,— A
Section A -A
1. Floor or Wall Assembly - Min 4 -1/2 in, thick reinforced lightweight or normal weight (100 -150 pco concrete. Floor may also be
constructed of any min 6 in. thick UL Classified hollow -core Precast Concrete Units *. Wall may also be constructed of any UL
Classified Concrete Blocks *. Max diam of opening is 7 in.
See Concrete Blocks (CAZT) and Precast Concrete Units (CFTV) categories in the Fire Resistance Directory for names of
manufacturers.
2. Through Penetrants - One metallic pipe, conduit or tubing to be installed either concentrically or eccentrically within the
firestop system. The annular space between the pipe, conduit or tubing and the periphery of the opening shall be a min of 0 in.
(point contact) to a max of 3 in. Pipe, conduit or tubing to be rigidly supported on both sides of floor or wall assembly. The
following types and sizes of metallic pipes, conduit or tubing may be used:
A. Steel Pipe - Nom 6 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe - Nom 6 in. diam (or smaller) cast or ductile iron pipe.
C. Conduit - Nom 4 in. diam (or smaller) steel electrical metallic tubing or steel conduit.
D. Copper Tube - Nom 4 in. diam (or smaller) Type L (or heavier) copper tube.
3. Forming Material - (Optional, Not Shown) - Mineral wool batt packing material or polyurethane backer rod friction fitted into
opening and recessed from floor or wall surfaces as required to accommodate required thickness of fill material.
4. Fill, Void or Cavity Material* - Sealant - Min 1/2 in. thickness of fill material applied within the annulus, flush with both
surfaces of floor or wall. At the point contact location between penetrating item and concrete, a min 1/4 in. thick bead of fill
material shall be applied at the concrete /penetrating item interface on both sides of floor or wall.
SPECIFIED TECHNOLOGIES INC - SpecSeal Series SSS Sealant or SpecSeal LCI Sealant
*Bearing the UL Classification Mark
—® �ecified Technologies Inc. 210 Evans Way Somerville, NJ 08876
® Reproduced courtesy of Underwriters Laboratories, Inc. @C-AJ-1259 [T� Created or Revised: January 2, 2009 11 800 992 -1180. 908 526-8000 • FAX 908 231 -8415 + E- Mail:techsery stifiresto com • Website :www.sbfiresto com AGE
( ) ( } ( } @ P• P� PAGE 1 OF 1
System No. W -L -1079
F Ratings -1 and 2 Hr (See Item 1B)
T Rating - 0 Hr
L Rating At Ambient - Less Than 1 CFM /sq ft
L Rating At 400 F - Less Than 1 CFM/sq ft
A
0
,'1. VIGIIon IA -,H
1. Wall Assembly - The 1 or 2 hr fire -rated gypsum board /stud wall assembly shall be constructed of the materials and in the
manner described in the individual U300 or U400 Series Wall or Partition Design in the UL Fire Resistance Directory and shall
include the following construction features:
A. Studs - Wall framing may consist of either wood studs or steel channel studs. Wood studs to consist of nom 2 by 4 in.
lumber spaced 16 in. OC with nom 2 by 4 in. lumber end plates and cross braces. Steel studs to be min 3 -5/8 in. wide and
spaced max 24 in. OC.
B. Gypsum Board* - 5/8 in. thick, 4 ft wide with square or tapered edges. The gypsum board type, thickness, number of
layers, fastener type and sheet orientation shall be as specified in the individual U300 or U400 Series Design in the UL Fire
Resistance Directory. Max diam of opening is in wood stud walls is 13 in. Max diam of opening in steel stud walls is 16 in.
The hourly F rating of the firestop system is equal to the hourly fire rating of the wall assembly in which it is installed.
2. Through Penetrant - One metallic pipe or conduit to be installed either concentrically or eccentrically within the firestop
system. The annular space between pipes or conduits and periphery of opening shall be min 0 in. (point contact) to max 3 in.
Pipe or conduit to be rigidly supported on both sides of wall assembly. The following types and sizes of metallic pipes or
conduits may be used:.
A. Steel Pipe - Nam 12 in. diam (or smaller) Schedule 10 (or heavier) steel pipe.
B. Iron Pipe - Nom 12 in. diam (or smaller) cast or ductile iron pipe.
C. Conduit - Nom 4 in. diam (or smaller) electrical metallic tubing, nom 6 in. diam (or smaller) steel conduit or nom 1 in. diam
(or smaller) flexible steel tubing.
D. Copper Pipe - Nom 6 in. diam (or smaller) Regular (or heavier) copper pipe.
E. Copper Tube - Nam 6 in. diam (or smaller) Type L (or heavier) copper tube.
Specified Technologies Inc. 210 Evans Way Somerville, NJ 08876
�. Reproduced courtesy of Underwriters Laboratories, inc. (9)
1 1. Created or Revised: January 2,2009
1 800 992 -1180. 908 526 -8000 • FAX 908 231 -8415 • E- Mail:techsery stifiresto com • Website:www.stifiresto com W -L-10 F
t ) ( ) t } @ P• P• PAGE 1 OF 2
Walt Opening Protective Materials (CLIV)
SPECIFIED TECHNOLOGIES INC R14288
SUITE 2 200 EVANS WAY, SOMERVILLE, NJ 08876 USA
SpecSeal Putty Pads, for use with max 4 -11/16 by 4 -11/16 in. flush device UL Listed metallic
outlet boxes installed with steel cover plates in 1 and 2 h fire rated gypsum wallboard wall assemblies
framed with mint 3 -1/2 in. deep wood or steel studs and constructed of the materials and in the manner
specified in the individual U300 or U400 Series Wall and Partition Designs in the Fire Resistance
Directory. Min 3/16 in. thick moldable putty pads are to be installed to completely cover the exterior
surfaces of the outlet box (except for the side of the outlet box against the stud) and completely seal
against the stud within the stud cavity. An additional 3/16 in. thickness of putty to be formed around
the connector securing the end of each electrical metallic tube or conduit to the box. When used with
metallic outlet boxes larger than 4 by 4 in., a ball of putty is to be installed to plug the open end of
each electrical metallic tube or conduit within the outlet box. When max 4 by 4 in, metallic outlet
boxes are used, the ball of putty in the open end of each electrical metallic tube or conduit within the
outlet box is optional. When moldable putty pad outlet box protective material is used on boxes on
both sides of wall as directed, the horizontal separation between outlet boxes on the opposite sides of
the wall may be less than 24 in. provided that the boxes are not installed back -to -back.
SpecSeal Putty Pads for use with max 4 by 3 -3/4 by 3 in. deep UL Listed Nonmetallic Outlet
Boxes manufactured by Carlon Electrical Products and made from polyvinyl chloride, max 4 by 3 -3/4
by 3 in. deep UL Listed Nonmetallic Outlet Boxes manufactured by Allied Moulded Products Inc. and
made from fiber - reinforced thermosetting plastic or max 4 -1/16 by 3 -5/8 by 3 -1/8 in. deep UL Listed
Nonmetallic Outlet Boxes manufactured by Thomas & Betts Corp. and made from fiber- reinforced
thermosetting plastic. Boxes shall also bear a 2 It rating under the "Outlet Boxes and Fittings Classified
for Fire Resistance" category in the Fire Resistance Directory. Boxes installed with steel or plastic
cover plates. Putty pads and boxes for use in I and 2 h fire rated gypsum wallboard/wood stud wafl .
assemblies constructed of the materials and in the manner specified in the individual U300 Series Wall
and Partition Designs in the Fire Resistance Directory. Outlet box secured to wood stud by means of
two nailing tabs in conjunction with nails supplied with the outlet box. Min 3/16 in. thick moldable
putty pads are to be installed to completely cover the exterior surfaces of the outlet box (except for the
side of the outlet box against the stud) including nailing tabs and completely seal against the stud
within the stud cavity. An additional 3/16 in. thickness of putty to be formed around the end of each
nonmetallic sheathed cable at its connection to the box and to extend a minimum of 1 in. from the box
onto the nonmetallic sheathed cable within the stud cavity. When moldable putty pad outlet box
protective material is used on boxes on both sides of wall as directed, the horizontal separation
between outlet boxes on opposite sides of the wall may be less than 24 in. provided that the boxes are
not installed back -to -back.
_1�
1C
(-R
..
Cn to
to
LO
..
11 Lo
•
co
O
Sheet
E 1
i
•
Pei
•
s
..
i
CO
•
Sheet
E 1