13-1154-004EXISTING ELECTRICAL LOAD ANALYSIS— PNL A 1) GENERAL LIGHTING: AREA SERVED GEN -88 2929 SRO 3 VA/SF 8181 2) AHU /CU -1 (10KW HEAT - COOLING NON- COINC): 10,100 (.IK U FAN 3) OVEN 8000 4) COOKTOP 8000 5) DRYER 5000 (0) EWH -I 4,500 1) WASHER 1,500 8) DISH WASHER 1,500 9) REFRIGERATOR 1,500 10) SMALL APPLIANCE (2 CKT5.e1500 VA) 300 REFRIGERANT LINES SUCTION (IN) - LIQUID (IN) TOTAL EXISTING CONNECTED LOAD: 52,481 V-& EXISTING ELECTRICAL LOAD ANALYSIS— PNL B 1) AHU /CU -2 (E)KW HEAT- COOLING NON -CONCJ 5,100 (.10) FAN) 2) POOL PUMP (15 HP) 2300 3) SPRNKLER PUMP (15 HP) 2,300 TOTAL EXISTING CONNECTED LOAD: 10300 VA L-OAID ANAL-Y515 BASED ON 120/ 24011, 17, 3W A. EXIST PNL "A" TOTAL LOAD 52,481 VA LIGHT DEMAND LOADS AREA SERVED GEN -88 w SM APPLIANCE- 3000 22.0 TOTAL LT DEMAND LOAD- 11,181 COOLING CAPACITY, MBH FIRST 3000 VA a 1009.: 3OW VA FV IAINNG 1500 VA a 359'.: 3015 VA OVEN- 12OW (8 KW PER NEC 220.19) 8000 VA REMAINING PNL LOAD 28,100 VA TOTAL: 42,71'15 VA / 240 V = 118 A B. EXIST PNL 11511 TOTAL LOAD 10300 VA TOTAL: 10,300 VA / 240 V ■ 43 A C. NEW PNL "C" TOTAL LOAD 19,800 VA TOTAL: 19,900 VA / 240 V = 83 A D. SERVICE DEMAND LOADS 82081 VA HEATING LOAD -9 659'0 9"150 VA let 10 KVA is 1009'0 10,000 VA REMAINDER 51,681 VA ,0 4090 23,075 VA 42,625 V4/ 240 V - 118 A SERVICE FEEDER: EXIST 3 03/0- 2- 1 /2 "C. EXIST O.HEAD FPL LAT RATED 22OW A.I.C. A/C EQUIPMENT 5 UNIT DESIGNATION AC -1/ HEAT PUMP -1 AREA SERVED SEE PLAN w TOTAL COOLING CAPACITY, MBH 22.0 QSENSIBLE COOLING CAPACITY, MBH 11.6 z AIR SUPPLY (CFM) 100 = OUTSIDE AIR, CFM (MINIMUM) N/A _W ELECTRICAL SERVICE AVAILABLE 240 -1 -60 4 F.L. AMPS NA W F.L. AMPS NA z MINIMUM CIRCUIT AMP / MAXIMUM FUSE 20/20 Q SEER 15.0 z REFRIGERANT LINES SUCTION (IN) - LIQUID (IN) 5/811-3/Vi U 0 DESIGN MANUFACTURER GOODMAN INDOOR MODEL MSH243E15AX OUTDOOR MODEL MSH24BE15MC NOTES ACCESSORIES 0 NOTE: UNIT TO BE INSTALLED ABOVE FLOOD ELEVATION / EOLT CONDENSING UNIT TO CONDENSING SUPPORTS TO WITHSTAND UNIT 1 -I5 MPH HURRICANE FORCE WINDS INSTALL (2) MIN 1/8"0 STAINLESS 0 0 STEEL CABLES. ATTACHED TO MIN 1/24, ST. ASTL. A .M. W/ CLOSED EYE BOLT. CABLE TO BE INSTALLED TIGHT AND LOOPED THRU EYE BOLT AND CRIMPED AT BOTH ENDS. MIN 3/32" TH. 2 "x2 "A" WIDE CLIPS . AT EA CORNER SECURE W/ (2)"12 TEK SCREWS AT UNIT 4 (2 )1/4 "A -3/4" TAPCON TO CONC SLAB. 4" T14 CONC BASE 6" MIN 6 X 6 - 10/10 WWF SCH. 40 PVC CONDUIT W/ SOLVENT WELDED JOINTS RUN UNDER SLAB. USE 3" OR 4" DIA. AS REQ. POWER 4 CONTROL CONNECTIONS 711 4" MIN. AIR CONDITIONING GENERAL NOTES. THIS JOB REQUIRES A VERY THOROUGH COORDINATION BETWEEN ALL TRADES AND I. THE CONTRACTOR SHALL COORDINATE THE INSTALLATIONS OF THE DIFFERENT TRADES t NOTIFY THE ARCHITECT IF ANY CONFLICTS OCCUR BEFORE INSTALLATIONS BEGIN. CONTRACTOR SHALL FURNISH WRITTEN GUARANTEE THAT ALL WORK SHALL 2.- 5E FREE FROM DEFECTS OF MATERIALS AND WORKMANSHIP FOR A PERIOD OF ONE YEAR FROM DATE OF FINAL ACCEPTANCE. ALL WORK SHALL BE IN ACCORDANCE WITH THE 2010 FLORIDA BUILDING 3•- CODE AND ALL LOCAL CODES HAVING JURISDICTIONt NFPA 90 A 4 B, ASWRAE GUIDE AND SMACNAS DUCT CONSTRUCTION STANDARDS. ALL REFRIGERATION PIPING TO BE COPPER TYPE "K" HARD DRAWN WITH 4 " SWEAT AND WROUGHT COPPER FITTINGS. 5.- SUCTION REFRIGERATION LINES SHALL BE INSULATED WITH 3/4" ARMAFLEX. 6.- PROVIDE ALL NECESSARY CONTROLS FOR THE OPERATION OF THE A/C SYSTEM. is VOLTAGES SHOULD BE VERIFIED PRIOR TO ANY INSTALLATION. LIQUID 4 SUCTION LINE W/ INSULATION SEAL W/ U.L. LABEL SILICONE SEALANT COND. UNIT FASTENING DETAIL/ REFRIGERANT PIPING N.T.S. EXIST MAN I OF 1: 2P -225A. MAN C$. IN NEMA 3R U.LS.E. ENCL., RATED 22000 AI.C. 200A CB EXIST METER M EXIST 120/24OV. 100A CB EXIST 3 -0'3/0 4 04 CND- 2 -1/2" C I F=W .; -7 • G LXW- 1- EXIST- 104 SERVICE GROUND CLAMPED TO WATER WATER PIPING AND 5 /8N x 6' C RD ROD ELECTRICAL RISER DIAGRAM XTA PANEL NEW ACCESS �. BLDG •210 4 04 GND- 2' C RATED LL 10RATED4.I.0 100A : CB EXIST EXIST NEW PNL. PNL. PNL. IIQN IIAII MU N/'•N V HOUSE�HOUSE � I F=W .; -7 • G LXW- 1- EXIST- 104 SERVICE GROUND CLAMPED TO WATER WATER PIPING AND 5 /8N x 6' C RD ROD ELECTRICAL RISER DIAGRAM XTA PANEL NEW TYF�E: GE MAIN BUS: 100 A NOTES; SERVICE: IPH-3tU. NEUTRAL- 100 A vOLTAC-sE: 120/240 MAINS: ,,. mcjB. MOUNTIWas �. ... - �. 0 LL : Z 1 J m 0 J W I 0 fn W V LIJ © Q � - ■ ■ ■ ■_� Q 0 - w. - �© :iii m�- D ■ ■ ■■ ■gym ■ ■ ■ ■ ■� E)UST TYFEt Sa . moo, MAIN BUS: 225 A SERVICE: IF44-3W. NEUTRAL: 225 A VOLTAGEs 120/240 MAINS: 225A t-M li7° W 1/4" DRAIN DRAIN LINE TO TERMINATE MIN 6" AF�G. AND MIN 12" FROM WALL( TYP OF ALL UNITS) FLOOR/ CEILINGS STRUCTURE MM 26 GA FLAT MTL STRAP HANGERS SECURED TO STRUCTURE FLOOR/ CEILING STRUCTURE MIN 26 GA FLAT MTL STRAP HANGERS — SECURED TO STRUCTURE MIN 26 GA SHEET i METAL PROTECTVE SLEEVE AT EXTERIOR INSTALLATIONS MIN P WIDE 26 GA SUPPORT STRAPS 0 16" O.G. SECURED T< CMU W/ TAPCONS REFRIGERANT LIQUID LINE. COMB. TO INSULATION W/ PLASTIC STRAP. REFR*ERANT SUCTION LINE CONTINUOUS INSULATION END VIEW o REFRIGERANT LIQUID LINE CONN. TO INSULATION IW �— PLASTIC STRAP. REFRIGERANT SUCTION LINE CONTINUOUS INSULATION SADDLE VERTICAL INSTALLATION I-,-- C - U WALL REFRIGERANT PIPING HANGER ELECTRICAL & MECHANICAL PLAN SCALE: 1/4" = V -0" "V DJ 2JOv- NEMA 3R C10,12 HEAT PUMP C2 GFI/WP REVISION BY A M Alj� �� ' % 15790 SW 88TH AVE MIAMI, FL 33157 AR 0017521 NOTE: ALL DRAWINGS FOR THIS PROJECT ARE TO BE READ IN CONJUNCTION WITH EACH OTHER. THESE INCLUDE, BUT ARE NOT LIMITED TO: ARCHITECTURAL, SURVEYING, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL, SPECIALTY DRAWINGS, & WRITTEN SPECIFICATIONS. CONTRACTOR TO VERIFY ALL EXISTING SITE CONDITIONS AND THOROUGHLY CHECK ELEVATIONS AND DIMENSIONS BEFORE COMMENCING WORK. REPORT TO THE ARCHITECT ENGINEER ANY DISCREPANCIES, ERRORS OR CONDITIONS THAT WILL ALTER CONSTRUCTION AS INTENDED BY THESE DRAWINGS. ARCHITECT IS NOT RESPONSIBLE FOR ANY WORK AND /OR MATERIALS FURNISHED ON THE JOB. All graphic material appearing herein, unless indicated otherwise, are the property of the Architect as instruments of service for use solely on this project, and may not be duplicated, used or disclosed without the written consent of Mark E. Reardon, R.A. The architect retains all common law, statutory -and other reserved rights. .7, D • Q. Be at 0 LL 0 Z 1 J m 0 J W C) 0 A M Alj� �� ' % 15790 SW 88TH AVE MIAMI, FL 33157 AR 0017521 NOTE: ALL DRAWINGS FOR THIS PROJECT ARE TO BE READ IN CONJUNCTION WITH EACH OTHER. THESE INCLUDE, BUT ARE NOT LIMITED TO: ARCHITECTURAL, SURVEYING, STRUCTURAL, CIVIL, MECHANICAL, ELECTRICAL, SPECIALTY DRAWINGS, & WRITTEN SPECIFICATIONS. CONTRACTOR TO VERIFY ALL EXISTING SITE CONDITIONS AND THOROUGHLY CHECK ELEVATIONS AND DIMENSIONS BEFORE COMMENCING WORK. REPORT TO THE ARCHITECT ENGINEER ANY DISCREPANCIES, ERRORS OR CONDITIONS THAT WILL ALTER CONSTRUCTION AS INTENDED BY THESE DRAWINGS. ARCHITECT IS NOT RESPONSIBLE FOR ANY WORK AND /OR MATERIALS FURNISHED ON THE JOB. All graphic material appearing herein, unless indicated otherwise, are the property of the Architect as instruments of service for use solely on this project, and may not be duplicated, used or disclosed without the written consent of Mark E. Reardon, R.A. The architect retains all common law, statutory -and other reserved rights. .7, D • Q. Be at 0 LL 0 Z J m 0 J W � fn W V LIJ J J Q � V w W 0) 0 Z Q 0 N MER DATE: 9/12/13 SCALE: AS NOTED SHEET NO.: ME -1