GENERAL NOTES - ELECTRICAL ( SINCE NOTES ARE GENERAL, SOME NOTE OR PORTION OF A NOTE MAY
NOT BE APPLICABLE)
1. -DO NOT SCALE ELECTRICAL DRAWINGS, REFER TO ARCHITECTURAL PLANS AND
ELEVATIONS FOR EXACT LOCATIONS OF ALL EQUIPMENT AND CONFIRM WITH
OWNER.
2. -ALL WORK SHALL BE DONE IN ACCORDANCE WITH THE N.E.C. AND SHALL COMPLY
WITH THE CURRENT FLORIDA BUILDING CODE, AND ALL STATE AND LOCAL RULES AND
ORDINANCES.
3.- MINIMUM WIRE SIZE SHALL BE NO. 14 AWG, EXCLUDING CONTROL WIRING, UNLESS
OTHERWISE INDICATED. ALSO, UNLESS OTHERWISE INDICATED, ALL CONDUCTORS
SHALL BE COPPER WITH TW INSULATION FOR SIZES NO. 6 AND SMALLER.
CONDUCTORS LARGER THAN NO. 6 SHALL HAVE TYPE THW NO. 8 AND LARGER SHALL
BE STRANDED. ALL RACEWAYS AND PIPES PLACED IN OR THROUGH ANY CONCRETE
SLAB SHALL BE SPACED A MINIMUM OF 3 DIAMETERS OF THE LARGEST CONDUIT OR
PIPE OF ANY OTHER SERVICE.
4. -ALL RACEWAYS UNDERGROUND AND /OR LARGER THAN 2 INCHES IN DIAMETER,
SHALL BE GALVANIZED RIGID STEEL. PVC PIPE SCH. 40 WILL BE ACCEPTABLE IF
APPROVED BY LOCAL REGULATIONS. CONTRACTOR TO VERIFY. ALL OTHER
RACEWAYS 2 INCHES AND SMALLER IN DIAMETER MAY BE E.M.T. WHEN ABOVE GROUND
PVC PIPE WILL BE ACCEPTABLE IF APPROVED BY LOCAL REGULATIONS.
5.- OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, AND CAST ALLOY
WITH THREADED HUBS IN WET OR DAMP LOCATIONS (4" x 4" MINIMUM SIZE).
6.- DISCONNECT SWITCHES SHALL BE HORSEPOWER RATED, HEAVY DUTY,
QUICK -MAKE, QUICK - BREAK, IN NEMA 1 OR 3R ENCLOSURE AS REQUIRED BY
EXPOSURE.
7AT IS NOT THE INTENT OF THESE PLANS TO SHOW EVERY MINOR DETAIL OF
CONSTRUCTION. THE CONTRACTOR IS EXPECTED TO FURNISH AND INSTALL ALL
ITEMS FOR A COMPLETE ELECTRICAL SYSTEM, AND PROVIDE ALL REQUIREMENTS
NECESSARY FOR EQUIPMENT TO BE PLACED IN PROPER WORKING ORDER.
&MOTOR STARTERS SHALL BE MANUAL OR MAGNETIC WITH THREE OVERLOAD
RELAYS.
9. -THE ELECTRICAL SYSTEM SHALL BE FULLY OPERATIONAL AND TESTED WHEN
COMPLETED, AS WELL AS COMPLETELY GROUNDED AS REQUIRED BY THE LATEST
EDITION OF THE N.E.C. THE ELECTRICAL CONTRACTOR REQUESTS ALL ELECTRICAL
INSPECTIONS AND SHALL HAVE A QUALIFIED REPRESENTATIVE AT JOB SITE DURING
ALL INSPECTIONS. THE ELECTRICAL CONTRACTOR SHALL PROVIDE THE OWNER A
SEPARATE PERMIT FOR ALL ELECTRICAL WORK AND SHALL INSURE THAT ALL REQUIRED
INSPECTIONS ARE COMPLETED AND APPROVED THROUGH THE FINAL INSPECTION.
10. -LOAD DATA IS BASED ON INFORMATION GIVEN TO THE ARCHITECT AT THE TIME
OF DESIGN. VERIFY ALL EQUIPMENT CONDUCTOR SIZE, PROTECTION, ETC.
REQUIREMENTS PRIOR TO ORDERING PANEL BOARDS, OR PRIOR TO INSTALLATION.
1 I.-ALL MATERIALS, DEVICES, FIXTURES, ETC, SHALL BE NEW AND SHALL BEAR
UNDERWRITERS AND UNION LABELS WHERE APPLICABLE. SUBMIT LIGHT FIXTURE
SCHEDULE FOR OWNER APPROVAL,
12.-ALL WORK SHALL BE PERFORMED BY A LICENSED ELECTRICAL CONTRACTOR IN
A FIRST CLASS WORKMANLIKE MANNER. THE COMPLETED SYSTEM SHALL BE FULLY
OPERATIVE AND ACCEPTANCE BY THE ARCHITECT MUST BE A CONDITION OF
THE CONTRACT.
13.-ALL WORK SHALL BE COORDINATED WITH OTHER TRADES TO AVOID
INTERFERENCE WITH PROGRESS OF CONSTRUCTION.
14.- CONTRACTOR SHALL GUARANTEE ALL MATERIALS, EQUIPMENT AND WORKMANSHIP
ARE FREE OF DEFECT FOR A PERIOD OF NO LESS THAN ONE YEAR FROM THE DATE OF
ACCEPTANCE.
15.-CONTRACTOR SHALL REMOVE ALL DEBRIS AND UNUSED FIXTURES AND RETURN
TO OWNER OR DISPOSE OF PROPERLY IF SO DIRECTED BY OWNER.
16.- CONTRACTOR SHALL INCLUDE IN HIS PRICE, PERMIT, TAXES AND /OR IMPACT FEES,
INSURANCE, ETC. AND PREPARATION OF AS -BUILT DRAWINGS AT THE FINAL CLOSE OUT
OF ALL THE WORK.
17.-IT IS SUGGESTED THAT THE CONTRACTOR CONFER WITH LOCAL UTILITY TO
LOCATE THE ELECTRIC METER WHEN REINSTALLED TO COMPLY WITH FEMA REQUIREMENTS
1 8. -ALL CONTROL WIRES AND CONNECTIONS REQURED FOR ALL ELECTRICAL
APPLIANCES, AIR CONDITIONING AND VENTILATING EQUIPMENT OPERATION
SHALL BE PROVIDED AND TESTED FOR A FULLY OPERATIONAL SYSTEM.
19.- MAINTAIN 12" MINIMUM SEPERATION BETWEEN OUTLET BOXES ON OPPOSITE
SIDES OF SOUND INSULATED WALLS
20.- CLAIMS FOR EXTRAS ON NEW WORK DUE TO MEETING CODE REQUIREMENTS
WILL NOT BE CONSIDERED.
21 . -COVER PLATES FOR SWITCHES AND RECEPTACLES SHALL BE WHITE OR CREAM
PER OWNER APPROVAL AND SMOOTH, MULTIPLE GANG BOXES WITH COVER PLATE SHALL
BE USED FOR MULTIPLE SWITCHING, VERIFY WITH OWNER.
22.- CONTRACTOR SHALL VERIFY ALL EXISTING CONDITIONS AND VERIFY EXACT
LOCATIONS PRIOR TO BIDDING THE PROJECT.
ELECTRICAL CALCULATIONS (EXISTING HOUSE PANEL)
1 1 2 5 SQ. FT. x 3.0 WATTS /SQ. FT. =
3,5 70 WATTS
ELECTRICAL SCHEDULE
3,000
WATER HEATER (NEW TANK LESS)
19,200
DISHWASHER
800
REFRIGERATOR
FOR SINGLE RESIDENCE
CLOTHE WASHER
1,500
DRYER
5,000
RANGE /OVEN
12,000
MICROWAY
1,200
SPARES
MAINS TYPE: 150 AMPS, 1- PHASE,
3 -WIRE,
48,970 WATTS
240/120 VOLTS,
MOUNTED
S/N
10,000
TOTAL A/C LOAD
MANUFACTURER CUTLER-
HAMMER
6500
A/C FAN 750 WATTS x 1
TYPE
EXISTING PANEL SCIC=
10,000 AMP
V
BRANCH CIRCUIT LOAD
BREAKER
CIRCUIT No
BREAKER
_
u.
LOAD
BRANCH CIRCUIT
Co
o
V)
CD
a
O
ui
o
a
O
w
uu DESCRIPTION
c)
DESCRIPTION
u
a-
A/C AHU #1 .
5,000 50A
1
2
50A
12,000
OVEN / RANGE
O
C�
C
O
50A
3
4
50A
CCU
CL
N
DRYER
5,000 30A
5,,--'
6
60A
19,200
NEW TANK LESS W/H
6
30A
7
8
60A
19,200
NEW TANK LESS W/H
6
MICROWAVE
1,200 20A
9
10
20A
1,500
REFRIGERATOR
z_
WASHER
1,500 20A
11
_
12
20A
800
DISHWASHER
E"
SMALL APPLIANCE
1,500 500 20A
13
14
20A
1,500
SMALL APPLIANCE
V)
X
cn
GFI RECEPTACLE
1,500 20A
15
16
20A
1,500
GFI RECEPT
w
w
GENERAL LIGHTS
3,312 15A
17
18
20A
DINING /LIVING
GENERAL LIGHTS
15A
19
20
15A
GRAL. RECEPT
GENERAL LIGHTS
15A
21
22
20A
GFI RECEPT
GFI RECEPTACLE
20A
23
24
30A
4,800
A/C COND #1 .
GRAL. RECEPTACLE
15A
25
26
30A
27
28
29
30
ELECTRICAL SCHEDULE
FOR SINGLE RESIDENCE
Panel #2 "C"
MAINS TYPE: 150 AMPS, 1- PHASE,
3 -WIRE,
240/120
VOLTS, MOUNTED S/N
MANUFACTURER CUTLER - HAMMER
TYPE
NEW PANEL SCIC =
10,000 AMP
BRANCH CIRCUIT LOAD
BREAKER
CIRCUIT No
BREAKER
LOAD
BRANCH CIRCUIT
V)
Lu
z
w 0
p
r a
< cr
°-
1--
DESCRIPTION
cC
0
u
u DESCRIPTION
3 -10 112- A/C COND. #2.
4,800 30
1
2
40
7,000
A/C AHU #2.
3-8
3/4'
A/C COND. #2.
3
4
40
A/C AHU #2.
14 ROMEX GEN, LIGHTS
1,200 is
5
6
15
1,200
GEN. LIGHTS
14
ROMEX
ROMEX GEN. LIGHTS /RECEPT
1,200 Is
7
8
20
1,500
GEN. RECEPTACLE
12
ROMEX
14
14 GEN. LIGHTS /RECEPT
1,500 15
9
10
20
4,000
GFI. RECEPT.
12
ROMEX
w
GEN. LIGHTS /RECEPT
14
1,500 15
11
12
20
1,500
GFI. RECEPT.
12
ROMEX z
6 ROMEX TANK LESS W/H #2
14,400 60
1 3
14
6 ROMEX TANK LESS W/H #2
14,400 60
1 5
16
17
18
19
20
21
22
23
24
25
26
27
28
,--"2' 9
30
ELECTRICAL CALCULATIONS (EXISTING HOUSE PANEL)
1 1 2 5 SQ. FT. x 3.0 WATTS /SQ. FT. =
3,5 70 WATTS
SMALL APPLIANCE
3,000
WATER HEATER (NEW TANK LESS)
19,200
DISHWASHER
800
REFRIGERATOR
1,500
CLOTHE WASHER
1,500
DRYER
5,000
RANGE /OVEN
12,000
MICROWAY
1,200
SPARES
1,200
TOTAL WATTS
48,970 WATTS
EXISTING A/C STRIP HEATER
5,000
NEW A/C STRIP HEATER
10,000
TOTAL A/C LOAD
15,000
10,000 x 65% DEMAND LOAD
6500
A/C FAN 750 WATTS x 1
750
TOTAL A/C DEMAND LOAD
7,250
TOTAL CONNECTED LOAD
48,970 WATTS + A/C 7,250 WATTS
FIRST 10,000 WATTS @ 100% = 1 O,OOOWATTS
NEXT 38,970 @40%= 15,588 WATTS
A/C 7,2 5 0 WATTS @ 100% = 7,2 5 0 WATTS
TOTAL LOAD = 32,838 WATTS
32,838 WATTS / 240 = 136.8 AMPS
EXISTING PANEL IS 150 AMP CAPACITY
ELECTRICAL CALCULATIONS (NEW HOUSE PANEL)
978 SQ.FT. x 3.0 WATTS /SQ.FT. =
2,934 WATTS
WATER HEATER #2 (TANK LESS)
19,200 WATTS
SPARE
1 ,200 WATTS
TOTAL WATTS
23,334 WATTS
NEW A/C STRIP HEATER
u-
TOTAL A/C LOAD
7,000
7,000 x 65% DEMAND LOAD
4,550
A/C FAN 750 WATTS x 1
750
TOTAL A/C DEMAND LOAD
5,300
TOTAL CONNECTED LOAD
23,334 WATTS + A/C 5300 WATTS
FIRST 10,000 WATTS @ 100%= 10,000 WATTS
NEXT 23,334 @40%= 9,334 WATTS
A/C 5,300 WATTS @ 100% = 5,300 WATTS
TOTAL LOAD = 14,634 WATTS
14,634 WATTS/ 240 = 61 AMPS
NEW PANEL IS 150 AMP CAPACITY
TOTAL ELECTRIC LO AD
PANEL (EXISTING HOUSE PANEL) = 136.8 AMPS
PANEL (NEW HOUSE PANEL) = 61.0 AMPS
TOTAL CONNECTED LOAD = 197.8 AMPS
USE 225 AMPS MAIN SERVICE
An
❑O
C 13,15 TANK LESS
W/H TO BE
LOCATED INSIDE
CABINET
ELECTRICAL FLOOR PLAN
SCALE 1/4"
ELECTRICAL SYMBOLS
ALL SYMBOLS MAY NOT BE USED.
3W GROUNDED DUPLEX RECEPTACLE 20 A 120 V M.H. + 12' ' AF.
V V V U
3W GROUNDED DUPLEX RECEPTACLE 20 A 120 V M.H. -1- 12"
TOP HALF SWITCHED
-� 3W GROUNDED SINGLE RECEPTACLE V J u
2 POLE OUTLET
Q JUNCTION BOX CEILING OR FLOOR MOUNTED
JUNCTION BOX WALL MOUNTED M.H. AS INDICATED
KI TELEPHONE OUTLET M.H. + 12" A.F.F. OR AS INDICATED
TELEVISION OUTLET M.H. + 12" A.F.F.
SPEAKER OUTLET CEILING MOUNTED
T� THERMOSTAT M.H. + 50" A.F.F.
CD BUZZER OUTLET M.H. AS INDICATED
Q TELEPHONE TERMINAL CABINET
@ EXHAUST FAN
Hi DISCONNECT SWITCH
�-O INTERCOM OUTLET MOUNTING HEIGHT -I- 72" A.F.F.
O INCANDESCENT FIXTURE OUTLET CEILING MOUNTED
52" FAN CEILING MOUNTED
1O) RECESSED INCANDESCENT FIXTURE
RECESSED WALL WASHER
Q POLE MOUNTED LIGHT FIXTURE
O�=-5p INCANDESCENT FIXTURE OUTLET WALL RECESSED MOUNTED
(D INCANDESCENT FIXTURE OUTLET FLUSH GROUND MOUNTED
FO INCANDESCENT FIXTURE OUTLET WALL MOUNTED M.H. AS INDICATED
0 FLUORESCENT FIXTURE OUTLET CEILING MOUNTED
FLUORESCENT FIXTURE OUTLET WALL MOUNTED
I--I FLUORESCENT FIXTURE OUTLET STRIP
O INCANDESCENT FIXTURE OUTLET CEILING MOUNTED CONNECTED
TO EMERGENCY CIRCUIT OR NIGHT LIGHT CIRCUIT
NEW SERVICE
2"0 CONDUIT W/
CU.THWN
NEW 225 AMP
SERVICE METER
CAN
NEW 1 #4 GROUND
IN y" O CONDUIT
EXISTING 3 #1 CU. THWN
& 1 46 CU. IN 1 Y2" RIGIO
CONDUIT
1 "O CONDUIT W/
3 #4 CU. & 1 #6 CU.
NEW 1 #4 CU. IN 1/2" GROUND
CONDUIT W/ 2 -5 /8 "O
VERTICAL GROUND
BAR AND TO C.W PIPE
ELECTRICAL RISER DIAGRAM
N.T.S. 'u" U
J U U
W
/I-
V J J V L V V
VVU V
U VUVUU
REVISI- S BY
U
.' gi9 c 2014 J.M.
5 �Jy 1 Q;Q8 -2014 J.M.
J
PANEL
PANEL
A
B
MAIN
MAIN
u-
DISC
DISC
Z
75 AMP
150 AMP
1 "O CONDUIT W/
3 #4 CU. & 1 #6 CU.
NEW 1 #4 CU. IN 1/2" GROUND
CONDUIT W/ 2 -5 /8 "O
VERTICAL GROUND
BAR AND TO C.W PIPE
ELECTRICAL RISER DIAGRAM
N.T.S. 'u" U
J U U
W
/I-
V J J V L V V
VVU V
U VUVUU
REVISI- S BY
U
.' gi9 c 2014 J.M.
5 �Jy 1 Q;Q8 -2014 J.M.
J
.y
REDR0' L FIA.L.L
FL; LIC...#,'7p00';,, -
DRAWN
Y.F
CHECKED
J.M.
DATE
10 -08 -14
SCALE
AS SHOWN
JOB No.
SHEE -r
E-1
OF 1 SHEETS
1f 1 6
^. Y:" �IE6'jl I`II
• St
& i.., IAI,
I
�w��
u-
O
Z
R
L-
1—
0
_P
E
cyD
Co
O
LLJ
V
Z
D
O
_
u.
-
�
N
Co
Co
E
CD
O
<
®C
O
c)
0QLO
4-'
Q0
a-
C
0
0
O
C�
C
O
E
c\j
CCU
CL
N
n
l
0-
.y
REDR0' L FIA.L.L
FL; LIC...#,'7p00';,, -
DRAWN
Y.F
CHECKED
J.M.
DATE
10 -08 -14
SCALE
AS SHOWN
JOB No.
SHEE -r
E-1
OF 1 SHEETS
1f 1 6
^. Y:" �IE6'jl I`II
• St
& i.., IAI,
I
�w��
u-
O
Z
0
L-
1—
0
_P
O
LLJ
V
Z
D
O
O
cJ
<
®C
O
c)
U)
O
4-'
Q0
a-
0
C!)
C�
.y
REDR0' L FIA.L.L
FL; LIC...#,'7p00';,, -
DRAWN
Y.F
CHECKED
J.M.
DATE
10 -08 -14
SCALE
AS SHOWN
JOB No.
SHEE -r
E-1
OF 1 SHEETS
1f 1 6
^. Y:" �IE6'jl I`II
• St
& i.., IAI,
I
�w��