12-120-004AIR CONDIRTIONING NOTES: 1.DUCTWORK SHALL BE 1 -1/2" THICK, 3 POUNDS PER CUBIC FOOT DENSITY FIBERGLASS WITH VAPOR BARRIER UNLESS OTHERWISE SOECIFIED. DUCTWORK SHALL BE FABRICATED AND INSTALLED IN ACCORDANCE WITH MANUFACTURES SPECIFICATIONS AND ACCORDANCE TO 'ASHRAE' AND "SMACNA" STANDARDS. DUCT DIMENSIONS ARE IN INCHES AND CORRESPOND TO INSIDE DIMENSIONS WIDTH X HEIGHT. DUCT SYSTEM SHALL COMPLY WITH 'NFPA' STANDARD No. 90A AND OR 908. DUCTWORK AND COMPONETS SHALL BE CLASS 1 MATERIALS IN ACCORDANCE WITH UL 0181. 2.COORDINATE LOCATIONS SIZES AND OPENINGS WITH OTHER TRADES ON THE JOB. AC CONTRACTOR SHALL PROVIDE THE COMPLETE DUCT SYSTEM. AC CONTRACTOR SHALL BE THE BEST PRACTICES OF THE TRADE IN THE FABRICATION AND INSTALLATION OF THE SYSTEM. 3DIFFUSERS SHALL BE SELECTED, LOCATED AND BALANCED IN ORDER THAT THEY DELIVER THE REQUIRED CFM'S TO THE ENTIRE ROOM EVENLY AND DRAFT FREE TO MAINTAIN THE FOLLOWING DESIGN CONDITIONS. INSIDE OUTSIDE RELATIVE HUMIDITY COOLING - 76D8 91 DB - -!9 WB 50% TO 60% HEATING - 10 DB 41 DB 4ALL FAN UNITS, MOTORS, COMPRESSORS, ETC SHALLBE ISOLATED AS REQUIRED TO OPERATE QUIETLY SO THAT NO OBJECTIONABLE SOUND WILL BE HEARD IN THE HABITABLE SPACES DUE TO AIR VELOCITY, MOTOR HUM VIBRATION OR MECHANICAL MOVEMENT. 5AC SYSTEM SHALL HAVE CLEANABLE AIR FILTERS LOCATED AS REQUIRED FOR EASY ACCESSIBILITY. 6AC SYSTEM SHALL BE CONTROLLED BY A THERMOSTAT. MOUNT THERMOSTAT 5' -0" ABOVE FINISH FLOOR U.O.N. 1ALL GRILLS AND DIFFUSERS TO BE ALUMINUM OR STEEL CONSTRUCTION. DIFFUSERS TO HAVE OPOSED BLADE DAMPERS. PROVIDE GASKETS ON ALL GRILLES AND DIFFUSERS. TITUS OR AIREGUIDE OR APPROVED EQUAL WITH ENAMEL FINISH. &UNDERCUT DOORS 1" AFF, AS INDICATED. 9ALL REFRIGERANT PIPING SHALL BE COPPER -TYPE L- ACR TYPE, DEHYDRATED AND SEALED. ALL FITTINGS SHALL BE WROUGHT COPPER. ALL JOINTS SHALL BE MADE WITH HIGH TEMPERATURE BRAZING ALLOY OF NOT LESS THAN 5% SILVER PIPING INSULATION NOT LESS THAN 3/4" THICK 'ARMAFLEX'. LIQUID AND SUCTION LINES SHALL BE SIZED ACCORDING TO EQUIPMENT MANUFACTURER'S RECOMMMENDAT IONS FOR EQUIVALENT LENGTH OF PIPING RUN FOR CONNECTED TONAGE. ALL PIPING ACCESSORIES SHALL BE CONNECTED AS SUGGESTED BY EQUIPMENT MANUFACTURER. ALL PIPING SHALL BE EVACUATED PER GOOD PIPING PRACTICE BEFORE START -UP. IOALL WORK SHALL CONFORM TO THE LATEST EDITION OF THE FLORIDA BUILDING CODE. REFR LINES W PIPE INSULAT TO AIR HAND] A C,_ _,.. ... �. �.. ....,.�,.. TO WITHSTAND 146 MPH WIND • t t REFR LINES W/ PIPE INSULATk TO CONDENSIN REFR LINES W/ PIPE INSULATION TO CONDENSING U LOUVER D( 3/4 "0 CONDE DRAIN W/3"' UNION 4 C.O. :)NDENSING UNIT MOUNTED CONC. SLAB OP OF SLAB ELEV. MATCH EXIST FLR SLAB) UCT 'FILING PARTITION PROVIDE 4" CLEARANCE AROUND AHU MTL STAND FLOAT SWITCH MTL PAN FLOOR nts 1 -1/2 "0 PVC SCH 40 CONDENSATE DRAIN TO EXTERIOR FLOOR PLAN 50 CFM EXH FAN W/ 4 "0 UP TO ROOF JACK REFR LINES W/ PIPE INSULATION TO CONDENSING UNIT IN GALV MTL GUTTER AIR CONDITIONING SCHEDULE UNIT MANUFACTURER MODEL NO. T� � HEAT � TOTAL �� TAL o� u�5 r ELECT. W/VOLLTS/14z SEER P �QSizs AHU "1 RHEEM RWLLHM2411JA 2.0 800 5.0 1/8 - 22 16,100 23,000 86 1 -60- 208/230 14.0 3/4" - 3/8" AC 44 13AJM024AOI 12.1 140 Lic. # AR0008374 r® ALL RAW � AND • HEREIN OF ORIGINAL , , UNPUBLISHED •• 'MICHAEL HURrAK, �D aJ . • • . • UT ITHE �► • 2000 IMICHAEL HURTAK ARCHITECT (c) IF�j immmmmmmmmmmmi I■■E■E■■N■EN ■I I■■■■■■■■■■■mi I■■■■■■■■■■■mi I■■■■■■■■■■■ml I■■■■■■■■■m■ ■I I■■■■■■■■■■m ■I • ow uj 0 (n w Z ftwftft Z 0 1 < LL • C-14 -q Z) 0 • LL Lic. # AR0008374 r® aWNUMAW Y WE m IF�j aWNUMAW Y