Loading...
14-252-0054010 Fire Alarm Control Panel - JIMMYS BBQ v v v v v v v v v APPLIANCE/ QUANTITIES I CURRENT DRAW @ M IMUM RMS Q BBQ PARTIAL FIRE A LA RM SYSTEM NAC SCHEDULE I VOLTAGE DROP CALCULATION AS DESIGNED MAXIMUM STROBE HORWSTRB Standby Total Alarm Total Module city Description MAXIMUM Current Standby Current Alarm Panel Equipment 15CD 30CD CIRCUIT CIRCUIT CIRCUIT VOLTAGE DEVICE CIRCUIT VOLTAGE 4010 -9101 1 FACP 250PT 4NAC 4A 120V BEIGE 0.2210 0.195000 0.195000 0295000 0.295000 4010.9803 1 ALM, SUPV, 8 TRBL RELAY MODULE VOLT 0.010000 0.010000 0.037000 0.037000 4010 -9811 1 DUAL RS232 INTERFACE CARD 0.075000 0.075000 0.075000 0.075000 4010 -9816 1 DACT (POINT REPORTING) 16.9 0.040000 0.040000 0.040000 0.040000 4010 -9820 1 BATTERY METER MODULE 150 0.000000 0.000000 0.000000 0.000000 4010 -9806 I 1 12PT CLASS A NAC ADAPTER 2.000 0.000000 0.000000 0.000000 0.000000 2.1 3.5 17.0% 16.9 Total Panel Slby 0,320000 Total Panel Alarm 0.447000 Peripheral Devices 0.00307 100 821 1 2 1 4090 -9002 6 IDNET RELAY IAM 0.6 0.000000 0.000000 0.000000 0.000000 4606 -9101 1 LCD ANNUN FOR 4010 FACP N2) SIG- 4 0065000 0.065000 0.140000 0.140000 4098.9755 6 TRUEALARM DUCT SMOKE SENSOR W/O RELAY OUTPUT 0 0.000000 0.000000 0.000000 0.000000 2098 -9806 6 REMOTE TEST STATION WI LED AND KEY SWITCH 0.05 0.000000 0.000000 0.000000 0.000000 2098 -9797 6 SAMPLING TUBE 49" 7 0.000000 0.000000 0.000000 0.000000 4098 -9714 1 TRUEALARM PHOTO SMOKE SENSOR 0.000000 0.000000 0.000000 0.000000 4098.9792 1 TRUEALARM SENSOR BASE Largest Single Circuit Load: 0.00 A 0.000000 0.000000 0.000000 0.000000 4099 -9001 4 IDNET SINGLE ACTION PULL STATION 0.000000 0.000000 0.000000 0.000000 ASWP- 2475CFR 1 HORNISTROBE 30CD 24VDC CEILING RED WP 0 0.000000 0.000000 0.168000 0.168000 4906.9103'15 2 TRUEALERT MULTI- CANDELA STROBE WHITE, WALL @ 15 CANDELA D 0.000000 0.000000 0.060000 0.120000 4906 - 9129'75 13 TRUEALERT MULTI - CANDELA HORNISTROBE L."HITE, WALL @ 75 CANDELA 0.000000 020000 0221000 2.873000 4906 - 9103'75 7 TRUEALERT MULTI-CANDELA STROBE WHITE, WALL @ 75 CANDELA Minimum Device Voltage: 16 V 0.000000 0.000000 1 0.186000 1.302000 Miscellaneous Outside Purchased Items Requiring System Power O 75 Degrees Celsius NOTE: Total Periph Stby 0,0650 Total Periph Alarm 4,603 Note: total Standby Amps 0,385 Total Alarm Amps 5.050 ' r Used additional current draws Current Draw Included With Device Addresses See U e ( ) °a "Regulated 24 VDC' refers to the voltage range of 16 to 33 VDC t 2-wire detector alarm current is included in the alarm current of the Initialing Device Circuit. OF SAFETY, TAKING INTO CONSIDERATION THE ACTUAL INSTALLED CIRCUIT ROUTING MAY DIFFER FROM WHAT IS SHOWN 2 50% of these devices In alarm, are used in the calculations below a z 12 GA = 0.001930 ON THE SHOP DRAWINGS. IF THE ACTUAL CIRCUIT LENGTH IS GOING TO EXCEED THE MAXIMUM ALLOWABLE CIRCUIT W Z U- Y w O Please note that 16VDC is the lowest operating voltage that is allowed Standby 14 GA = 0.003070 Alarm ~ N ww0 Wz Batte Set #1 CabineVChc, er #1 city Current Current 16 GA = 0.004890 L0 Cabinet #1 Card Power C) 0.320 Backup Amplifier 0.447 Z v� ° 18 GA = 0.007770 Current Draw For 100 Watt Or 95 Watt Amplifiers 0 0.000 0 0.000 o z The maximum RMS current listed is the nameplate rating. Current Draw For Flex 35 and 50 Watt Amplifiers 0 0.000 W 0.000 ¢ W U U Power For External Peripheral Devices N ¢ 0.06500 0.42800 a WW a U U 0.385 <- Sub Totals -> 0.875 WO -, LL U Additional Current Draws Not enough MAPNETIIDNet cards available H MAPNET /IDNet Device Addresses ordered I used 17 17.0 0.014 J a 0.017 O co Spare addressable point capacity included for battery calc 0% 0 000 Q rn W Q 0.000 WO 0.399 < -Grand Totals -> 0.892 Z y Additional Battery Capacity Required 0% 0.000 U w 0.000 O Standby Time = 24 Hrs 9 566 Standby Ah Z J J ow Alarm Time = 5 Mins. 0.074 Alarm Ah Z W U Battery Required 2081.928812.7AH 11.487 Total Ah Hz- J 0 v v v v v v v v .. .. v 'W .. .. '% NOTE: ADDED ROOM NAMES TO FLOOR PLAN 11 SGMIAMMI)RAFTINGWO- 2007VLLL 00 -2003 CAD DRAV41NGS%THE SHOPS AT SUNSET PLACE- 40198MUNSET SHOPS JIMMY'S BBQ- REV01- 975589MLVMTEPPSW&"V$7 - REVOt- 975584401.DILVM PLAITED: M-115,20114 DATE SAY=: March 5, 2014 4010 Fire Alarm Control Panel - JIMMYS BBQ v v v v v v v v v APPLIANCE/ QUANTITIES I CURRENT DRAW @ M IMUM RMS Q BBQ PARTIAL FIRE A LA RM SYSTEM NAC SCHEDULE I VOLTAGE DROP CALCULATION AS DESIGNED MAXIMUM STROBE HORWSTRB STROBE HORNISTRB AS DESIGNED AT MAX ALLOW. CIRC. LENGTH TOTAL MAXIMUM LAST 17% MAXIMUM VOLTAGE DROP CIRCUIT WIRE WIRE ESTIMATED ALLOWABLE 4906. 9103'75 4906- 9129'75 4906 - 9103'15 ASWP- 2475C -FR TOTAL MAX TOTAL ACTUAL LAST CIRCUIT OUTPUT VOLTAGE (FOR CALCULATIONS) = 20.4 TYPE GAUGE RESIST CIRCUIT CIRCUIT 75CD 75C5 15CD 30CD CIRCUIT CIRCUIT CIRCUIT VOLTAGE DEVICE CIRCUIT VOLTAGE DEVICE �Q W LENGTH LENGTH 0.1860 0.2210 0.0600 0.1680 LOAD CAP. RES. DROP VOLT RES. DROP VOLT OHMS VOLTS % VOLTS CIRCUIT SIG DESCRIPTION AWG OHM/FT FT FT AMPS AMPS OHMS VOLTS % VOLTS 1.7 3.5 17.0% 16.9 SIG- 1 JIMMY'S BBQ CKTI AN 14 0.00307 150 284 0 9 0 0 1.989 2.000 0.9 1.83 9.0% 18.6 SIG- 2 JIMMYS BBQ CKT2 1 AN 14 0.00307 150 349 6 � 2 1 0 1.618 2.000 0.9 1.49 7.3% 18.9 2.1 3.5 17.0% 16.9 SIG- 3 JIMMY'S BBQ CKT3 AN 14 0.00307 100 821 1 2 1 0 0.688 0.000 0.6 0.42 2.1% 20.0 5.0 3.5 17.0% 16.9 SIG- 4 JIMMYS BBQ CKT4 zw AN 14 0.00307 50 3,362 0 0' 0 1 0.168 0.000 0.3 0.05 0.3% 1 20.3 20.6 1 3.5 17.0% 16.9 7 13 >1 2 1 1 4.463 Total NAC Load: 4.46 A 56% d W Largest Single Circuit Load: 0.00 A 0% W w U Lowest Voltage at any Device: 20.4 V 128% O LL METHOD USED TO CALCULATE VOLTAGE DROP: O 1n W W Total NAC (4010 +EXP) Capacity: 8 A [(CIRCUIT LENGTH IN FEET X 2) (AMPS) (OHMS I FT)] D a Single Circuit Capacity: 2.0 A v ` Minimum Device Voltage: 16 V O C> Wire Resistance At WIRE RESISTANCE BASED ON TABLE 8 FROM NATIONAL ELECTRICAL CODE (UNCOATED SOLID COPPER WIRE) O 75 Degrees Celsius NOTE: r Note: Ohms/ft LUMP SUM METHOD WAS USED TO CALCULATE ALLOWABLE VOLTAGE DROP. THIS METHOD ALLOWS FOR A SMALL MARGIN W W °a "Regulated 24 VDC' refers to the voltage range of 16 to 33 VDC 10 GA = 0.001210 OF SAFETY, TAKING INTO CONSIDERATION THE ACTUAL INSTALLED CIRCUIT ROUTING MAY DIFFER FROM WHAT IS SHOWN per UL standard 1971. This voltage is the absolute operating range. a z 12 GA = 0.001930 ON THE SHOP DRAWINGS. IF THE ACTUAL CIRCUIT LENGTH IS GOING TO EXCEED THE MAXIMUM ALLOWABLE CIRCUIT W Z U- Y w O Please note that 16VDC is the lowest operating voltage that is allowed � a 14 GA = 0.003070 LENGTH, CONTACT YOUR LOCAL SIMPLEXGRINNELL DISTRICT OFFICE. ~ N ww0 Wz O J z w at the last appliance on the NAC under worst case conditions. 16 GA = 0.004890 L0 C) c) Z v� ° 18 GA = 0.007770 a. 0 o z The maximum RMS current listed is the nameplate rating. z U W ¢ W U U Strobe designs are constant wattage and the maximum RMS current N ¢ a WW a U U rating occurs at the lowest allowable operating voltage. BATTERY CALCULATION I I 1 1 �1 G SUNSET SHOPS JIMMY BBQ PARTIAL FIRE A LA RM SYSTEM SCALE: 1 18 " SCOPE OF WORK 1. PROVIDE FIRE ALARM DEVICES AS SHOWN ON THE DRAWINGS. NOTE: THIS NEW FIRE ALARM SYSTEM WILL INTERFACE WITH THE MAIN MALL FACP.. KEY PLAN KEY PLAN NTS �WLE M MIAW -DADS C'rrt'JNTY FIRE j)EPARTM BLDG. PGi1.ri _ M FT;!:ALARM_ FIRE SUPf?r�ES:�tit:v 4 ---",_ V" %" ' ' 1 E r FM AI.IRM SYSTEM TO BE INSTALLED IN f'-C p ANC . I V NFFA 72; 70; JIMMY'S BBQ STATE: REGISTRATION: FLORIDA 59407 DISCIPLINE: PHONE: FIRE PROTECTION (954)822 -5416 ADDRESS: 950 NE 171st Street Suite 208 North Miami Beach, FL. 33162 .a X��"-o • � = W U) U) Z �Q W _ 5 W MI LL �^ ZY v IL to d. tN r WC)Opp W Cr) I j( Q 00 1 y ���C c'`) M W � O�v't Z W UQLO Ln 20)rn O Z Lr Lr � Z W IL °tau. a 6n `` W J U) Z M J O ww 0 zw O Lu F- CO CL C/) _j °oQ Oz d W W w U O O LL M LL O 1n W W D a v v O C> M O Z r � w W W °a F- } cwi W a z W W Z U- Y w O W x' � a .9 ~ N ww0 Wz O J z w l� U O z Z g L0 C) c) Z v� ° I a. 0 o z U z U W ¢ W U U N ¢ a WW a U U F=- � Z = WO -, LL U H W Ha J a O co O O Q rn W Q WO O Z y ZO U w O Z J J ow I� O cj U Z z Z W U V) rA Hz- J O z O Q z U) W Q O U i W f/2 F-1 Z 0: U) D QO O V) L0 r, Z o 0 �W w UO z > Z l- 0Zd o boa �Z p"U�1vaili �¢¢ �o DRAWN BY: DATE: KS 02/13/14 DESIGNED BY: DATE: KS 02/13114 APPROVED BY: DATE: KS 02/13/14 PROJECT NUMBER: 263 - 401987/975584401 SHEET TITLE/ PATH: SHEET NUMBER: FA01 SIZE D (21-X38-)