08-1188-003I
,e
I
1.- OVERALL INSTALLATION: THE INSTALLATION SHALL COMPLY WITH THE NATIONAL
ELECTRICAL CODE (NEC), THE FLORIDA BUILDING CODE (FBC), AND ANY OTHER
APPLICABLE FEDERAL, STATE AND LOCAL CODES.
2.- CONDUCTOR CALCULATIONS: CONDUCTOR CALCULATIONS ARE BASED ON 35 °C.
3.- GENERAL: THE GENERAL AND SPECIAL CONDITIONS AND REQUIREMENTS OF THE
CONTRACT AND SPECIFICATIONS AS WELL AS PLANS AND SPECIFICATIONS OF OTHER
DISCIPLINES AND TRADES SHALL BE A PART OF THE WORK HEREBY SPECIFIED. THESE
SPECIFICATIONS AND ACCOMPANYING PLANS ARE INTENDED TO PROVIDE FOR THE
COMPLETE FURNISHING AND INSTALLATION OF THE ELECTRICAL SYSTEMS. TO PROVIDE
MEANS TO FURNISH AND INSTALL.
4.- COMPLIANCE: WORKMANSHIP, MATERIALS AND INSTALLATION SHALL BE IN STRICT
ACCORDANCE WITH THE APPLICABLE EDITION OF THE NEC, NFPA, NEMA, ASTM, OSHA,
HRS HEALTH AGENCIES, AND OTHER APPLICABLE NATIONAL, STATE, AND LOCAL
CODES AND PERTAINING REGULATIONS ESTABLISHED BY THE RULING AUTHORITY
HAVING JURISDICTION. CONTRACTORS SHALL ALSO MEET THE REQUIREMENTS OF
OTHER STANDARDS WHERE SUCH REQUIREMENTS ARE MORE STRICT THAN THOSE
STANDARDS CITED ABOVE.
5.- WORKMANSHIP: ALL WORK SHALL BE PERFORMED BY CONTRACTORS LICENSED IN
THEIR RESPECTIVE DISCIPLINE. WORK SHALL BE DONE IN A FIRST CLASS MANNER,
FULLY OPERATIVE, AND TO THE ACCEPTANCE OF THE ARCHITECT AND THE
ENGINEERS. CONTRACTOR SHALL PROVIDE FOR ALL NECESSARY LABOR AND MATERIAL
REQUIRED FOR THE COMPLETION OF THE WORK INCLUDING BUT NOT LIMITED TO
RELATED WORK SUCH AS CONNECTION OF EXISTING SYSTEMS, EXCAVATIONS AND
BACK FILLING.
6.- MATERIALS: CONTRACTOR SHALL PROVIDE ALL NEW MATERIALS OF AMERICAN
MANUFACTURE, BEARING THE UNDERWRITER'S LABORATORY (UL) LABEL AS
APPLICABLE. MATERIALS SHALL BE NEW, SUITABLE FOR THE APPLICATION AND
ABOVE STANDARD QUALITY NORMALLY USED FOR THE PURPOSE AS CALLED FOR ON
PLANS. SUPPLEMENTAL MATERIALS, PRODUCTS AND COMPONENTS NECESSARY TO
COMPLY WITH THE INTENT OF THE CONTRACT DRAWINGS AND /OR SPECIFICATIONS,
BUT NOT NOTED OR SPECIFIED ON THESE SECTIONS, SHALL BE PROVIDED BY THE
CONTRACTOR AS REQUIRED FOR THE COMPLETION OF THE WORK AT NO ADDITIONAL
COST TO THE OWNER. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVISIONS AND
COORDINATION OF DELIVERY OF MATERIALS. EQUIPMENT MARRED DURING SHIPMENT OR
INSTALLATION SHALL BE TOUCHED UP AND REFINISHED TO FACTORY FINISH,
REPLACED WHERE NOT ACCEPTABLE.
7.- PERMITS AND INSURANCE: CONTRACTOR SHALL SECURE AND PAY FOR ALL
PERMITS, FEES, TAXES, INSPECTIONS, TESTS, FINES AND OTHER ITEMS AS REQUIRED
FOR THE INSTALLATION OF THE COMPLETE ELECTRICAL SYSTEMS AS OUTLINED HEREIN
AND SHOWN ON PLANS. CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR
PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION
OF THE WORK.
8.- EXISTING CONDITIONS: BEFORE BIDDING, THE CONTRACTOR SHALL VISIT THE JOB
SITE AND ASCERTAIN ALL EXISTING CONDITIONS WHICH WILL AFFECT HIS WORK.
FAILURE TO DO SO WILL NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA
PAY WHERE THE EXISTING CONDITIONS RESULT IN EXTRA MATERIALS OR ANY
EXISTING CONDITIONS FOUND BY THE CONTRACTOR WHICH WILL ADVERSELY AFFECT
THE WORK SHALL BE IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE
ARCHITECT /ENGINEER. CORRECTION OF ANY DEFECTS SHALL BE COMPLETELY WITHOUT
ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENTS OR REPAIR OF ANY OTHER
PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY.
9.- SUBSTITUTIONS: PRODUCTS AND MATERIALS CALLED OUT BY TRADE NAME
AND /OR CATALOG NUMBERS ESTABLISH A STANDARD OF QUALITY, APPEARANCE,
PERFORMANCE AND DIMENSION. CONTRACTORS SHALL BASE HIS PROPOSAL ON THOSE
ITEMS AS THEY SHALL BE CONSIDERED AS A STANDARD BASIS OF BIDDING.
REQUESTS FOR SUBSTITUTION SHALL BE SUBMITTED IN WRITING TO THE
ARCHITECT /ENGINEER, DEMONSTRATING THAT PRODUCT IS OF COMPARABLE AND
BASIC DESIGN, CONSTRUCTION, STANDARDS AND WARRANTIES, DIMENSIONS TO FIT
WITHOUT CHANGE, AND DOES NOT CAUSE EXTRA WORK TO OTHER TRADES.
CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING EQUALITY OF SUBSTITUTION:
ARCHITECT /ENGINEER WILL, UNDER NO CIRCUMSTANCES, BE REQUIRED TO PROVE SUCH
ITEM IS OR IS NOT OF EQUAL QUALITY TO THE SPECIFIED ITEM. ARCHITECT /ENGINEER
EXPENSES INCURRED DUE TO CONTRACTOR'S REQUESTED REVISIONS OR
SUBSTITUTIONS SHALL BE PAID BY THE CONTRACTOR.
10.- MOTORS STARTERS SHALL BE MANUAL OR MAGNETIC AS INDICATED OR REQUIRED,
WITH OVERLOAD RELAYS OR FUSES IN EACH HOT LEG.
ELECTRICAL GENERAL NOTES
11.- DATA /TELECOMMUNICATION SYSTEMS: FOR DATA /TELECOMMUNICATION SYSTEMS
UTILIZE A CONTRACTOR EXPERIENCED IN THE INSTALLATION OF
COMMUNICATION SYSTEMS AND CERTIFIED BY BUILDING INDUSTRY CONSULTING
SERVICE INTERNATIONAL.
12- CUTTING AND PATCHING: MAJOR CUTTING, PATCHING & PAINTING REQUIRED BY
THIS CONTRACT WILL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER. ALL
SURFACES SHALL BE RETURNED TO ORIGINAL CONDITIONS AFTER THE INSTALLATION
OF THE EQUIPMENT.
13. -THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF
THE LOCAL ELECTRIC UTILITY AND THE TELEPHONE COMPANY.
14. -LOAD DATA IS BASED ON INFORMATION PROVIDED TO THE ENGINEER AT THE TIME
OF DESIGN. ALL EQUIPMENT AND PANEL SIZES SHALL BE VERIFIED BEFORE ORDERING.
15.- CIRCUITS SHOWN ON PLANS ARE USED TO DETERMINE LOAD DATA AND PANEL
SIZES. THE CONTRACTOR SHALL PROVIDE CIRCUIT ROUTING TO SUIT THE JOB
CONDITIONS.
16.- FURNISH AND INSTALL ALL FIXTURES AS CALLED FOR ON THE PLANS OR AS
SELECTED BY OWNER /ARCHITECT.
17.- MINIMUM WIRE SIZE SHALL BE #14 AWG. UNLESS OTHERWISE NOTED, ALL
CONDUCTORS SHALL BE COPPER WITH THHN /THWN INSULATION. CONDUCTORS #10 AND
SMALLER MAY BE SOLID; #8 AND LARGER SHALL BE STRANDED ALUMINUM
CONDUCTORS MAY BE ALLOWED FOR SERVICE ENTRANCE IF SPECIFICALLY APPROVED
BY THE ENGINEER.
18. -ALL CONDUCTORS SHALL BE RUN IN CONDUIT, U.O.N.
19.- INSTALL 3/4" EMPTY CONDUIT TO ALL TELEPHONE /DATA OUTLETS. PROVIDE PULL
WIRE.
20. -ALL CONDUITS SHALL BE GALVANIZED RIGID (GRC), EXCEPT AS FOLLOWS:
(A) UL LISTED PVC CONDUITS MAY BE USED UNDERGROUND OUTDOORS OR
UNDER SLAB INSIDE THE BUILDING AS ALLOWED BY CODE. CONDUIT FITTINGS AND
CEMENT SHALL BE PRODUCED BY THE SAME MANUFACTURER.
(B) ELECTRICAL METALIC TUBING (EMT), MAY BE USED IN OR ON WALLS OR
CEILINGS WHERE NOT SUBJECT TO MECHANICAL DAMAGE, CORROSIVE OR DAMP
CONDITIONS.
(C) ELECTRICAL NON METALIC TUBING (ENT), MAY BE USED WHEN INSTALLED IN
ACCORDANCE WITH THE RECUIREMENTS OF THE NEC ARTICLE 362 AND ONDUIT
MANUFACTURER'S INSTRUCTIONS.
(D) METAL CLAD CABLE (MC), SHALL BE LIMITED TO BRANCH CIRCUITING AND BE
INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF NEC ARTICLE 330 AND CABLE
MANUFACTURER'S INSTRUCTIONS.
(E) NONMETALLIC CAELE (NM), (NMC) & (NMS) MAY BE USED FOR INTERIOR
WIRING, EXPOSED OR CONCEALED IN DRY LOCATIONS, MUST NOT BE USED EMBEDDED
IN CONCRETE, MASONRY, FILL OR PLASTER. ITS USE AND INSTALLATION SHALL
COMPLY WITH NEC ARTICLE334.
(F) FLEXIBLE CONDUIT SHALL BE USED FOR CONNECTIONS TO VIBRATING
EQUIPMENT AND RECESSED TIGHT FIXTURES, WHERE PERMITTED BY CODE. EMBEDDED
IN CONCRETE, MASONRY, FILL OR PLASTER. IF USED OUTDOORS, IT SHALL BE
LIQUIDTIGHT.
21.- PROVIDE FIRE RETARDAIT U.L. APPROVED SEALANT ON ALL PENETRATIONS,
WALLS AND STRUCTURAL SLABS. IT SHALL BE THE RESPONSIBILITY OF THE
ELECTRICAL CONTRACTOR TO VERIFY, PRIOR TO SUBMITTING BID, THE LOCATIONS OF
ALL SUCH FIRE.RATED PARTITIONS, WALLS, AND STRUCTURAL SLABS.
22.- INTERFERENCE: THE CONTRACTOR SHALL COORDINATE HIS WORK WITH OTHER
TRADES SO THAT INTERFERENCE WITH EXISTING CONDITIONS, CONDUITS, PIPING,
EQUIPMENT, ARCHITECTURAL AND STRUCTURAL MEMBERS BE AVOIDED,
23.- PLANS: DRAWINGS ARE BASICALLY DIAGRAMS INTENDED TO DEPICT
APPROXIMATELY EQUIPMENT LOCATIONS AND ARRANGEMENTS, NOT TO SHOW EVERY
MINOR DETAIL. PLANS SHALL NOT BE SCALED TO DETERMINE EXACT LOCATION AND
DIMENSIONS.
1- CLOSE OVERHANG SOFFIT VENTS WITHIN 10' OF GENERATOR
EXAUST TERMINATION POINT AID RE -OPEN THE SAME NUMBER OF
CLOSED /SEALED VENTS AT OTHER OVERHANG LOCATION
2- GENERATOR EXHAUST TERMNATION POINT SHALL NOT BE
LOCATED WITHIN 10' OF ANY BUILDING OPENING (WINDOW, DOOR ,
WALL /ROOF VENTS, WALL A/C UNITS, ETC.)
GENERATOR SCHEDULE
MANUFACTURE
ARMSTRONG
MODEL #
AGM60Si
RATED POWER
60 kW
VOLTAGE(SINGLE PHASE)
120/240
Amps (ia 120/240
225 NG
ENGINE /ALTERNATOR(RPM)
1,800
MAIN LINE CIRCUIT BREAKER
400 Amp
SOUND OUTPUT AT FULL LOAD(23 ft)
72 dB(A)
DIMENSIONS (L "xW "xH ")
97 x 37 x 57.6
WEIGHT
1,207 Kg
24. -ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN ACCESIBLE AREAS ONLY
AND ABOVE BASE FLOOD ELEVATION.
25.- CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL WIRING, BREAKER AND FUSES
SIZES IN ACCORDANCE WITH A/C EQUIPMENT NAMEPLATES, IF DIFFERENT FROM THOSE
SPECIFIED ON DRAWINGS, AS WELL AS ANY FEEDER CHANGES BEING AFFECTED BY
THIS CHANGE. CONTRACTOR SHALL MAKE ABOVE MENTIONED CHANGES AT NO EXTRA
COST.
26.- ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL CONTRACTOR TO
PROVIDE ALL REQUIRED J -BOXES AND CONDUITS FOR INSTALLATION OF CONTROL
WIRING. LOW VOLTAGE CONTROL WIRING AND THEIR TERMINATION IS THE
RESPONSIBILITY OF THE MECHANICAL CONTRACTOR.
27.- ELECTRICAL METER AND PANEL LOCATIONS SHOWN MAY VARY DEPENDING ON
SERVICE ENTRANCE LOCATION.
28. -ALL LIGHTING FIXTURES TO BE SELECTED BY THE OWNER /ARCHITECT, U.O.N. AND
SHALL BE INSTALLED BY THIS CONTRACTOR.
29.- BALANCE ALL PHASES AT EACH PANEL AND MDP /SERVICE MAINS.
30. -CHECK AVAILABLE ELECTRICAL SERVICE CHARACTERISTICS WITH THE LOCAL
POWER COMPANY PRIOR TO ORDERING ANY EQUIPMENT. INFORM THE ARCH /ENGINEER
IF IT IS DIFFERENT FROM WHAT IS SHOWN ON PLANS.
31.- CONTRACTOR SHALL PROVIDE TEMPORARY SERVICE AND LIGHTING FOR USE OF
ALL TRADES AS REQUIRED FOR CONSTRUCTION AND AUTHORITIES HAVING
JURISDICTION.
32.- ELECTRICAL CONTRACTOR SHALL ASSURE THAT ALL FEATURES OF SERVICE
COMPLY WITH THE POWER COMPANY'S REQUIREMENTS AND SHALL MAKE ALL
NECESSARY ARRANGEMENTS WITH POWER COMPANY FOR SERVICE. ALL EQUIPMENT
NOT FURNISHED AND /OR INSTALLED BY THE POWER CO. IS TO BE FURNISHED AND
INSTALLED BY THE ELECTRICAL CONTRACTOR.
33.- U.O.N., COORDINATE REQUIRED A.I.C. RATINGS WITH POWER COMPANY.
34. -WHERE MORE THAN ONE DEVICE IS INDICATED AT ANY LOCATION, THESE SHALL
BE GANGED UNDER ONE COMMON COVER.
35.- QUANTITY AND LOCATION OF ELECTRICAL, TELEPHONE /DATA & TV OUTLETS,
LIGHTS AND LIGHT CONTROLS, SHALL BE ADJUSTED TO SUIT THE OWNER'S
REQUIREMENTS AS PER OWNER /ARCHITECT INSTRUCTIONS. SAID ARRANGEMENTS
SHALL NOT BE IN CONFLICT WITH APPLICABLE CODES.
36.- ELECTRICAL CONTRACTOR SHALL VERIFY REQUIREMENTS, EXACT LOCATIONS, TYPE
AND ARRANGEMENT OF OUTLETS FOR ALL ELECTRICAL FIXTURES, APPLIANCES AND
EQUIPMENT, PRIOR TO INSTALLATION.
37. -ALL BRANCH CIRCUITS THAT SUPPLY 125 - VOLTS, SINGLE PHASE, 15 AND 20
AMPERE OUTLETS INSTALLED IN DWELLING UNIT BEDROOMS SHALL BE PROTECTED BY
AN ARC -FAULT CIRCUIT INTERRUPTER (AFCI) LISTED TO PROVIDE PROTECTION OF THE
ENTIRE BRANCH CIRCUIT.
38.- INSTALLATION OF LIGHTING FIXTURES INSIDE CLOTHES CLOSETS SHALL COMPLY
WITH THE NEC ARTICLE 410 -8.
39.- PROVIDE A TYPEWRITTEN DIRECTORY FOR EACH ELECTRICAL PANEL.
40.- CONTRACTOR SHALL FURNISH AS -BUILT DRAWINGS TO THE OWNER UPON
COMPLETION OF WORK AND PRIOR TO FINAL PAYMENT.
41.- OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY
WITH THREADED HUBS IN WET /DAMP LOCATIONS AND SPECIAL ENCLOSURES AS
REQUIRED FOR OTHER CLASSIFIED AREAS AND SHALL CONFORM TO NEMA STANDARDS.
PLASTIC BOXES MAY BE USED WHERE PERMITTED UNDER APPLICABLE CODES AND
ORDINANCES.
42 -ALL DISCONNECT SWITCHES SHALL BE SIZED BY NEC REQUIREMENTS TO
ACCOMODATE THE EQUIPMENT SERVED, INCLUDING REJECTION CLIPS AND FUSES, WHEN
APPLICABLE. SWITCHES SHALL BE HP RATED, QUICK -MAKE, QUICK - BREAK, IN NEMA 1
ENCLOSURES FOR INDOOR AND NEMA 311 FOR OUTDOOR.
43.- VERIFY SLAB STRUCTURAL DESIGN WITH STRUCTURAL ENGINEER.
GENERATOR NOTES
1.- GENERATOR MUST BE SET AT, OR ABOVE THE MINIMUM FEMA FLOOD ELEVATION.
2. -A PERMANENT SIGN SHALL BE PLACED AT THE ELECTRICAL SERVICE EQUIPMENT THAT INDICATES THE
LOCATION OF ON -SITE OPTIONAL STANDBY POWER SOURCES.
3.- PROVIDE RELAY TO PREVENT A/C HEATER FUNCTION DURING GENERATOR USE.
PHASE: 10
VOLTAGE: 120/240 v
?ANEL AMPS: 400 Amps
EXISTING PANEL '1TATT TYPE: SQD -QO /FLUSH
MAIN BREAKER: 400
(BRANCH BREAKERS TYPE OP, 10KAIC)
GFk Ground Fault Interrupter NCL= Non - concurrent load REC= Receptacle Ckt Lts= Lighting Ckt ST= Breaker with shunt trip T= Via timer
IS= Isolated ground Ckt C= Via contactor SWD= On -Off Switching Duty /or HID= Rated Breaker,as per NEC 240 -83(D) LV= Via low voltage transformer
HAIR= Breaker suitable for the protection of heating,A /C and refrigeration equipment AFCI= Breaker suitable for arc -fault Ckt. protection interrupter bkr.
Ck
No'
USE
SPEC
VOLT
BKR
AMP
WIRE
AWG
COND
SIZE
VA
PHASEI
Ckt
No.
USE
SPEC
VOLT
BKR
AMP
WIRE
AWG
COND
SIZE
VA
A
C
11
ROOF TOP UNIT
f�
"mil
240
80
EXIST
EXIST
16,000
•
I
2
X -RAY
(
240
80
EXIST
EXIST
16,000
3
Ij
4
10,120/240V I
I
400A, 10, (
1400A, 10 I
•
4
L
120/240V
120/240V
L
WP
120/240V 120/240V
- �WP
WP -
5
ROOF RECEPTACLES
- -J
7 I
GFI
120
20
EXIST
EXIST
200
•
6
REFRIGERATOR
(1) #3 GND CU IN 2 -1/2"
120
20
EXIST
EXIST
1,000
7
OUTDOOR LIGHTS
THWN (CU)
( 3/4 THWN (CU) I
120
20
EXIST
EXIST
1,000
•
8
FREEZER
VERIFY)
120
20
EXIST
EXIST
1,000
9
ULTRASOUND #5
120
20
EXIST
EXIST
1,200
10
AUTOCLAVE #1
120
20
EXIST
EXIST
1,400
11
ULTRASOUND #20
120
20
EXIST
EXIST
2,000
•
12
AUTOCLAVE #2
120
20
EXIST
EXIST
1,400
13
•
14
GENERAL RECEPTACLES
120
20
EXIST
EXIST
900
15
16
GENERAL RECEPTACLES
120
20
EXIST
EXIST
1,000
17
•
18
GENERAL RECEPTACLES
120
20
EXIST
EXIST
1,600
19
GENERAL RECEPTACLES
120
1 20
EXIST
EXIST
1,200
•
20
GENERAL RECEPTACLES
120
20
1EXIST
EXISTI
1,600
21
GENERAL RECEPTACLES
120
1 20
EXIST
EXISTI
1,400
•
22
GENERAL RECEPTACLES
120
20
1EXIST
EXISTI
1,600
23
GENERAL RECEPTACLES
120
1 20
EXIST
EXISTI
500
•
24
GENERAL RECEPTACLES
120
20
1EXIST
EXISTI
1,400
25
GENERAL RECEPTACLES
120
1 20
EXIST
EXISTI
2,000
•
26
GENERAL RECEPTACLES
120
20
EXIST
EXIST
1,200
27
GENERAL LIGHTS
120
20
EXIST
EXIST
800
•
28
GENERAL RECEPTACLES
120
20
EXIST
EXIST
800
29
GENERAL LIGHTS
120
20
EXIST
EXIST
1,000
30
GENERAL RECEPTACLES
120
20
EXIST
EXIST
1,200
31
GENERAL LIGHTS
120
20
EXIST
EXIST
1,000
•
32
GENERAL RECEPTACLES
120
20
EXIST
EXIST
1,000
33
GENERAL LIGHTS
120
20
EXIST
EXIST
800
•
34
35
•
36
37
38
391
40
411
1421
* SEE LOAD CALCULATION
*� VERIFY NAME PLATE
Load Calculation for Panel A:
Equipment Load = 62,100 va
25% Continuos Lights = 625 va
25% Largest Motor = 900 va
-50% Rectp demand over 10kW= -3,700
Total VA = 59,925 va
Panel Load = 59,925/240= 250 Amps
GENERATOR CALCULATION:
(A /C with out heater, see generator notes.)
Equipment Load = 52,100 va
25% Continuos Lights = 625 va
25% Largest Motor = 900 va
-50% Rectp demand over 10kW= -3,700
Total VA = 49,925 va
Panel Load = 49,925/240= 208 Amps
1 #8 GND IN
1/2" PVC
CONDUIT
NEW (3) #500 CU & (1) #3 GND
CU IN 2 -1/2" THWN (CU)
WEATHERPROOF
HOUSING -�
ANCHORING BOLTS 6 "X5/8"
"RED HEAD" AND NUTS
(SEE DETAIL ( "A ")
8" FIBER
CONCRETE PAD
U
3
1Q
WIRE MESH, ATTACH 8" CONS. SLAB W/ #5 @ 12"
TO #5 RIGID BAR O.C. IN 'E A. DIRECTION ON 6 MIL.
\ _ _ WELL COMPACTED FILL;-
mu
\ I 12" X 18" CONC. FOOTING W/
(1) #5 CONTINUOUS
o`
>O \
DETAIL „A.,
J JJ PAD ANCHORING
JJ ( MIN. 3/8"x2" TAP CONS, OR EQUAL)
J �.
EXISTING I J
EXISTING _I A.T.S. 1
METER /MAIN J -�-�JJ ;DETER GAS �\
JJJ-_)JJ \
JJJJJJJ
JJJJJJ . ".
JJJJ_IJ \
_1JJJJJ
_j _j
\"GENERATOR \
CONC.POL
V AW M
;AL 51TE FLAN s
N J40
PROPERTY LINE 168.91'
N.T.5
I
EXISTING
GROUNDING RODS
Cf
g
0
I:
0
CA. # 9360
THE ENGINEERING
CONSULTING GROUP, P.A.
MECHANICAL, ELECTRICAL, PLUMBING. &
FIRE PROTECTION ENGINEERING DESIGN
4937 S.W. 74th Ct
Miami, Florida 33155
Tel: (305) 663 -9191 `
Fax: (305) 663-8788
tecgroup@tecgroup-pa.com
n
W }'��- .�,� °► -,-sue
ERh6 0DRPGUEZ
MECHANIC L ENGINEER
PE# 58155
0
......... .
_0 .�
J.
0
Clio Q Q
W Z W
C.7 W W o�w1
W U
p`�
VJ •wz�-
W ` .r
W W W
U =u- x
�'- W
CY) 0
a) to o
(a E
Z W sb
d"-
W •
a.
WRITTEN DIMENSIONS ON THIS DRAWINI;`
SHALL HAVE PRECEDENCE OVER SCALED
DIMENSIONS. CONTRACTOR SHALL VERI
AND BE RESPONSIBLE FOR ALL
DIMENSIONS AND CONDITIONS ON THEO
JOB. THE DESIGN PROFESSIONAL MUST ErE
NOTIFIED IN WRITING OF ANY VARIATIC;W;h
FROM THE DIMENSIONS.
PLANS ARE PROTECTED UNDER THE
COPYRIGHT LAWS OF FLORIDA:
ALL RIGHTS RESERVED
ALL IDEAS DESIGN ARRANGEMENTS AND
PLANS INDICATED OR REPRESENTED BY
THIS DRAWINGS ARE OWNED BY AND THE
PROPERTY OF THE DESIGN PROFESSIONAL
AND WERE CREATED EVOLVED AND
DEVELOPED FOR USE ON AND IN
CONNECTION WITH THE SPECIFIED
PROJECT. ANY CHANGES TO THESE PLANS
WITHOUT THE WRITTEN APPROVAL OF THE
DESIGN PROFESSIONAL OR ANY
CONSTRUCTION EXECUTED FROM THESE
PLANS WITHOUT EXPRESSED APPROVAL
OF THE DESIGN PROFESSIONAL SHALL
AUTOMATICALLY RENDER THE DESIGN
PROFESSIONAL HARMLESS TO ANY
LIABILITY CLAIMS, SLIT OR LITIGATION BY
ANY INTERESTED PARTIES OF THE
PROJECT. PART THEREOF OF THESE
PLANS SHALL BE COPIED OR REPRODUCED
BY ANY MEANS, OR USED IN CONNECTION
WITH ANY WORK OTHER THAN FOR THE
SPECIFIC PROTECT FOR WHICH THEY HAVE
BEEN PREPARED WITHOUT WRITTEN
CONSENT OF THE DESIGN PROFESSIONAL.
Revisions:
ISSUE DATE SeDt.19, 2008
DVVN E.R. APPRV E.R.
Phase:
CONSTRUCTION
DOCUMENTS
Scale:
AS NOTED
Dwg Title: .- --
ELECTRICAL GENERATOR
SITE PLAN,`CALCS. & SCHED.
® Sheet No.:
E -1
I- 7
EXISTING 60A PLUG
F- - EXISTING (3) #500 CU IN 2 -1/2"
FOR PORTABLE
THWN (CU) TO "FP &L" POLE
L _j
GENERATOR.
r (CONTRACTOR TO VERIFY)
J
r- - - EXISTING SERVICE TO
"FP
F I= p 1
f�
"mil
F- T
&L" POLE
I I
`
EXISTING
I
I ( -,/ I
PANEL 'A I
(
EXISTING jI
I EXISTING I
EXISTING I I EXISTING
ATS
METER METER
10,120/240V I
I
400A, 10, (
1400A, 10 I
400A, 10 I I 150A, 10
42 SPACE
L
L
120/240V
120/240V
L
WP
120/240V 120/240V
- �WP
WP -
- -J
7 I
EXISTING (3) #500 CU &
�_
(1) #3 GND CU IN 2 -1/2"
EXISTING (1) #1/0 CU IN
THWN (CU)
( 3/4 THWN (CU) I
(CONTRACTOR TO VERIFY)
(CONTRACTOR TO
( :6--TO C.W.P
VERIFY)
L- - - - - - - -i
_B
N.T.5
I
EXISTING
GROUNDING RODS
Cf
g
0
I:
0
CA. # 9360
THE ENGINEERING
CONSULTING GROUP, P.A.
MECHANICAL, ELECTRICAL, PLUMBING. &
FIRE PROTECTION ENGINEERING DESIGN
4937 S.W. 74th Ct
Miami, Florida 33155
Tel: (305) 663 -9191 `
Fax: (305) 663-8788
tecgroup@tecgroup-pa.com
n
W }'��- .�,� °► -,-sue
ERh6 0DRPGUEZ
MECHANIC L ENGINEER
PE# 58155
0
......... .
_0 .�
J.
0
Clio Q Q
W Z W
C.7 W W o�w1
W U
p`�
VJ •wz�-
W ` .r
W W W
U =u- x
�'- W
CY) 0
a) to o
(a E
Z W sb
d"-
W •
a.
WRITTEN DIMENSIONS ON THIS DRAWINI;`
SHALL HAVE PRECEDENCE OVER SCALED
DIMENSIONS. CONTRACTOR SHALL VERI
AND BE RESPONSIBLE FOR ALL
DIMENSIONS AND CONDITIONS ON THEO
JOB. THE DESIGN PROFESSIONAL MUST ErE
NOTIFIED IN WRITING OF ANY VARIATIC;W;h
FROM THE DIMENSIONS.
PLANS ARE PROTECTED UNDER THE
COPYRIGHT LAWS OF FLORIDA:
ALL RIGHTS RESERVED
ALL IDEAS DESIGN ARRANGEMENTS AND
PLANS INDICATED OR REPRESENTED BY
THIS DRAWINGS ARE OWNED BY AND THE
PROPERTY OF THE DESIGN PROFESSIONAL
AND WERE CREATED EVOLVED AND
DEVELOPED FOR USE ON AND IN
CONNECTION WITH THE SPECIFIED
PROJECT. ANY CHANGES TO THESE PLANS
WITHOUT THE WRITTEN APPROVAL OF THE
DESIGN PROFESSIONAL OR ANY
CONSTRUCTION EXECUTED FROM THESE
PLANS WITHOUT EXPRESSED APPROVAL
OF THE DESIGN PROFESSIONAL SHALL
AUTOMATICALLY RENDER THE DESIGN
PROFESSIONAL HARMLESS TO ANY
LIABILITY CLAIMS, SLIT OR LITIGATION BY
ANY INTERESTED PARTIES OF THE
PROJECT. PART THEREOF OF THESE
PLANS SHALL BE COPIED OR REPRODUCED
BY ANY MEANS, OR USED IN CONNECTION
WITH ANY WORK OTHER THAN FOR THE
SPECIFIC PROTECT FOR WHICH THEY HAVE
BEEN PREPARED WITHOUT WRITTEN
CONSENT OF THE DESIGN PROFESSIONAL.
Revisions:
ISSUE DATE SeDt.19, 2008
DVVN E.R. APPRV E.R.
Phase:
CONSTRUCTION
DOCUMENTS
Scale:
AS NOTED
Dwg Title: .- --
ELECTRICAL GENERATOR
SITE PLAN,`CALCS. & SCHED.
® Sheet No.:
E -1