08-1188-003I ,e I 1.- OVERALL INSTALLATION: THE INSTALLATION SHALL COMPLY WITH THE NATIONAL ELECTRICAL CODE (NEC), THE FLORIDA BUILDING CODE (FBC), AND ANY OTHER APPLICABLE FEDERAL, STATE AND LOCAL CODES. 2.- CONDUCTOR CALCULATIONS: CONDUCTOR CALCULATIONS ARE BASED ON 35 °C. 3.- GENERAL: THE GENERAL AND SPECIAL CONDITIONS AND REQUIREMENTS OF THE CONTRACT AND SPECIFICATIONS AS WELL AS PLANS AND SPECIFICATIONS OF OTHER DISCIPLINES AND TRADES SHALL BE A PART OF THE WORK HEREBY SPECIFIED. THESE SPECIFICATIONS AND ACCOMPANYING PLANS ARE INTENDED TO PROVIDE FOR THE COMPLETE FURNISHING AND INSTALLATION OF THE ELECTRICAL SYSTEMS. TO PROVIDE MEANS TO FURNISH AND INSTALL. 4.- COMPLIANCE: WORKMANSHIP, MATERIALS AND INSTALLATION SHALL BE IN STRICT ACCORDANCE WITH THE APPLICABLE EDITION OF THE NEC, NFPA, NEMA, ASTM, OSHA, HRS HEALTH AGENCIES, AND OTHER APPLICABLE NATIONAL, STATE, AND LOCAL CODES AND PERTAINING REGULATIONS ESTABLISHED BY THE RULING AUTHORITY HAVING JURISDICTION. CONTRACTORS SHALL ALSO MEET THE REQUIREMENTS OF OTHER STANDARDS WHERE SUCH REQUIREMENTS ARE MORE STRICT THAN THOSE STANDARDS CITED ABOVE. 5.- WORKMANSHIP: ALL WORK SHALL BE PERFORMED BY CONTRACTORS LICENSED IN THEIR RESPECTIVE DISCIPLINE. WORK SHALL BE DONE IN A FIRST CLASS MANNER, FULLY OPERATIVE, AND TO THE ACCEPTANCE OF THE ARCHITECT AND THE ENGINEERS. CONTRACTOR SHALL PROVIDE FOR ALL NECESSARY LABOR AND MATERIAL REQUIRED FOR THE COMPLETION OF THE WORK INCLUDING BUT NOT LIMITED TO RELATED WORK SUCH AS CONNECTION OF EXISTING SYSTEMS, EXCAVATIONS AND BACK FILLING. 6.- MATERIALS: CONTRACTOR SHALL PROVIDE ALL NEW MATERIALS OF AMERICAN MANUFACTURE, BEARING THE UNDERWRITER'S LABORATORY (UL) LABEL AS APPLICABLE. MATERIALS SHALL BE NEW, SUITABLE FOR THE APPLICATION AND ABOVE STANDARD QUALITY NORMALLY USED FOR THE PURPOSE AS CALLED FOR ON PLANS. SUPPLEMENTAL MATERIALS, PRODUCTS AND COMPONENTS NECESSARY TO COMPLY WITH THE INTENT OF THE CONTRACT DRAWINGS AND /OR SPECIFICATIONS, BUT NOT NOTED OR SPECIFIED ON THESE SECTIONS, SHALL BE PROVIDED BY THE CONTRACTOR AS REQUIRED FOR THE COMPLETION OF THE WORK AT NO ADDITIONAL COST TO THE OWNER. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVISIONS AND COORDINATION OF DELIVERY OF MATERIALS. EQUIPMENT MARRED DURING SHIPMENT OR INSTALLATION SHALL BE TOUCHED UP AND REFINISHED TO FACTORY FINISH, REPLACED WHERE NOT ACCEPTABLE. 7.- PERMITS AND INSURANCE: CONTRACTOR SHALL SECURE AND PAY FOR ALL PERMITS, FEES, TAXES, INSPECTIONS, TESTS, FINES AND OTHER ITEMS AS REQUIRED FOR THE INSTALLATION OF THE COMPLETE ELECTRICAL SYSTEMS AS OUTLINED HEREIN AND SHOWN ON PLANS. CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION OF THE WORK. 8.- EXISTING CONDITIONS: BEFORE BIDDING, THE CONTRACTOR SHALL VISIT THE JOB SITE AND ASCERTAIN ALL EXISTING CONDITIONS WHICH WILL AFFECT HIS WORK. FAILURE TO DO SO WILL NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA PAY WHERE THE EXISTING CONDITIONS RESULT IN EXTRA MATERIALS OR ANY EXISTING CONDITIONS FOUND BY THE CONTRACTOR WHICH WILL ADVERSELY AFFECT THE WORK SHALL BE IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE ARCHITECT /ENGINEER. CORRECTION OF ANY DEFECTS SHALL BE COMPLETELY WITHOUT ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENTS OR REPAIR OF ANY OTHER PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. 9.- SUBSTITUTIONS: PRODUCTS AND MATERIALS CALLED OUT BY TRADE NAME AND /OR CATALOG NUMBERS ESTABLISH A STANDARD OF QUALITY, APPEARANCE, PERFORMANCE AND DIMENSION. CONTRACTORS SHALL BASE HIS PROPOSAL ON THOSE ITEMS AS THEY SHALL BE CONSIDERED AS A STANDARD BASIS OF BIDDING. REQUESTS FOR SUBSTITUTION SHALL BE SUBMITTED IN WRITING TO THE ARCHITECT /ENGINEER, DEMONSTRATING THAT PRODUCT IS OF COMPARABLE AND BASIC DESIGN, CONSTRUCTION, STANDARDS AND WARRANTIES, DIMENSIONS TO FIT WITHOUT CHANGE, AND DOES NOT CAUSE EXTRA WORK TO OTHER TRADES. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVIDING EQUALITY OF SUBSTITUTION: ARCHITECT /ENGINEER WILL, UNDER NO CIRCUMSTANCES, BE REQUIRED TO PROVE SUCH ITEM IS OR IS NOT OF EQUAL QUALITY TO THE SPECIFIED ITEM. ARCHITECT /ENGINEER EXPENSES INCURRED DUE TO CONTRACTOR'S REQUESTED REVISIONS OR SUBSTITUTIONS SHALL BE PAID BY THE CONTRACTOR. 10.- MOTORS STARTERS SHALL BE MANUAL OR MAGNETIC AS INDICATED OR REQUIRED, WITH OVERLOAD RELAYS OR FUSES IN EACH HOT LEG. ELECTRICAL GENERAL NOTES 11.- DATA /TELECOMMUNICATION SYSTEMS: FOR DATA /TELECOMMUNICATION SYSTEMS UTILIZE A CONTRACTOR EXPERIENCED IN THE INSTALLATION OF COMMUNICATION SYSTEMS AND CERTIFIED BY BUILDING INDUSTRY CONSULTING SERVICE INTERNATIONAL. 12- CUTTING AND PATCHING: MAJOR CUTTING, PATCHING & PAINTING REQUIRED BY THIS CONTRACT WILL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER. ALL SURFACES SHALL BE RETURNED TO ORIGINAL CONDITIONS AFTER THE INSTALLATION OF THE EQUIPMENT. 13. -THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF THE LOCAL ELECTRIC UTILITY AND THE TELEPHONE COMPANY. 14. -LOAD DATA IS BASED ON INFORMATION PROVIDED TO THE ENGINEER AT THE TIME OF DESIGN. ALL EQUIPMENT AND PANEL SIZES SHALL BE VERIFIED BEFORE ORDERING. 15.- CIRCUITS SHOWN ON PLANS ARE USED TO DETERMINE LOAD DATA AND PANEL SIZES. THE CONTRACTOR SHALL PROVIDE CIRCUIT ROUTING TO SUIT THE JOB CONDITIONS. 16.- FURNISH AND INSTALL ALL FIXTURES AS CALLED FOR ON THE PLANS OR AS SELECTED BY OWNER /ARCHITECT. 17.- MINIMUM WIRE SIZE SHALL BE #14 AWG. UNLESS OTHERWISE NOTED, ALL CONDUCTORS SHALL BE COPPER WITH THHN /THWN INSULATION. CONDUCTORS #10 AND SMALLER MAY BE SOLID; #8 AND LARGER SHALL BE STRANDED ALUMINUM CONDUCTORS MAY BE ALLOWED FOR SERVICE ENTRANCE IF SPECIFICALLY APPROVED BY THE ENGINEER. 18. -ALL CONDUCTORS SHALL BE RUN IN CONDUIT, U.O.N. 19.- INSTALL 3/4" EMPTY CONDUIT TO ALL TELEPHONE /DATA OUTLETS. PROVIDE PULL WIRE. 20. -ALL CONDUITS SHALL BE GALVANIZED RIGID (GRC), EXCEPT AS FOLLOWS: (A) UL LISTED PVC CONDUITS MAY BE USED UNDERGROUND OUTDOORS OR UNDER SLAB INSIDE THE BUILDING AS ALLOWED BY CODE. CONDUIT FITTINGS AND CEMENT SHALL BE PRODUCED BY THE SAME MANUFACTURER. (B) ELECTRICAL METALIC TUBING (EMT), MAY BE USED IN OR ON WALLS OR CEILINGS WHERE NOT SUBJECT TO MECHANICAL DAMAGE, CORROSIVE OR DAMP CONDITIONS. (C) ELECTRICAL NON METALIC TUBING (ENT), MAY BE USED WHEN INSTALLED IN ACCORDANCE WITH THE RECUIREMENTS OF THE NEC ARTICLE 362 AND ONDUIT MANUFACTURER'S INSTRUCTIONS. (D) METAL CLAD CABLE (MC), SHALL BE LIMITED TO BRANCH CIRCUITING AND BE INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF NEC ARTICLE 330 AND CABLE MANUFACTURER'S INSTRUCTIONS. (E) NONMETALLIC CAELE (NM), (NMC) & (NMS) MAY BE USED FOR INTERIOR WIRING, EXPOSED OR CONCEALED IN DRY LOCATIONS, MUST NOT BE USED EMBEDDED IN CONCRETE, MASONRY, FILL OR PLASTER. ITS USE AND INSTALLATION SHALL COMPLY WITH NEC ARTICLE334. (F) FLEXIBLE CONDUIT SHALL BE USED FOR CONNECTIONS TO VIBRATING EQUIPMENT AND RECESSED TIGHT FIXTURES, WHERE PERMITTED BY CODE. EMBEDDED IN CONCRETE, MASONRY, FILL OR PLASTER. IF USED OUTDOORS, IT SHALL BE LIQUIDTIGHT. 21.- PROVIDE FIRE RETARDAIT U.L. APPROVED SEALANT ON ALL PENETRATIONS, WALLS AND STRUCTURAL SLABS. IT SHALL BE THE RESPONSIBILITY OF THE ELECTRICAL CONTRACTOR TO VERIFY, PRIOR TO SUBMITTING BID, THE LOCATIONS OF ALL SUCH FIRE.RATED PARTITIONS, WALLS, AND STRUCTURAL SLABS. 22.- INTERFERENCE: THE CONTRACTOR SHALL COORDINATE HIS WORK WITH OTHER TRADES SO THAT INTERFERENCE WITH EXISTING CONDITIONS, CONDUITS, PIPING, EQUIPMENT, ARCHITECTURAL AND STRUCTURAL MEMBERS BE AVOIDED, 23.- PLANS: DRAWINGS ARE BASICALLY DIAGRAMS INTENDED TO DEPICT APPROXIMATELY EQUIPMENT LOCATIONS AND ARRANGEMENTS, NOT TO SHOW EVERY MINOR DETAIL. PLANS SHALL NOT BE SCALED TO DETERMINE EXACT LOCATION AND DIMENSIONS. 1- CLOSE OVERHANG SOFFIT VENTS WITHIN 10' OF GENERATOR EXAUST TERMINATION POINT AID RE -OPEN THE SAME NUMBER OF CLOSED /SEALED VENTS AT OTHER OVERHANG LOCATION 2- GENERATOR EXHAUST TERMNATION POINT SHALL NOT BE LOCATED WITHIN 10' OF ANY BUILDING OPENING (WINDOW, DOOR , WALL /ROOF VENTS, WALL A/C UNITS, ETC.) GENERATOR SCHEDULE MANUFACTURE ARMSTRONG MODEL # AGM60Si RATED POWER 60 kW VOLTAGE(SINGLE PHASE) 120/240 Amps (ia 120/240 225 NG ENGINE /ALTERNATOR(RPM) 1,800 MAIN LINE CIRCUIT BREAKER 400 Amp SOUND OUTPUT AT FULL LOAD(23 ft) 72 dB(A) DIMENSIONS (L "xW "xH ") 97 x 37 x 57.6 WEIGHT 1,207 Kg 24. -ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN ACCESIBLE AREAS ONLY AND ABOVE BASE FLOOD ELEVATION. 25.- CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL WIRING, BREAKER AND FUSES SIZES IN ACCORDANCE WITH A/C EQUIPMENT NAMEPLATES, IF DIFFERENT FROM THOSE SPECIFIED ON DRAWINGS, AS WELL AS ANY FEEDER CHANGES BEING AFFECTED BY THIS CHANGE. CONTRACTOR SHALL MAKE ABOVE MENTIONED CHANGES AT NO EXTRA COST. 26.- ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL CONTRACTOR TO PROVIDE ALL REQUIRED J -BOXES AND CONDUITS FOR INSTALLATION OF CONTROL WIRING. LOW VOLTAGE CONTROL WIRING AND THEIR TERMINATION IS THE RESPONSIBILITY OF THE MECHANICAL CONTRACTOR. 27.- ELECTRICAL METER AND PANEL LOCATIONS SHOWN MAY VARY DEPENDING ON SERVICE ENTRANCE LOCATION. 28. -ALL LIGHTING FIXTURES TO BE SELECTED BY THE OWNER /ARCHITECT, U.O.N. AND SHALL BE INSTALLED BY THIS CONTRACTOR. 29.- BALANCE ALL PHASES AT EACH PANEL AND MDP /SERVICE MAINS. 30. -CHECK AVAILABLE ELECTRICAL SERVICE CHARACTERISTICS WITH THE LOCAL POWER COMPANY PRIOR TO ORDERING ANY EQUIPMENT. INFORM THE ARCH /ENGINEER IF IT IS DIFFERENT FROM WHAT IS SHOWN ON PLANS. 31.- CONTRACTOR SHALL PROVIDE TEMPORARY SERVICE AND LIGHTING FOR USE OF ALL TRADES AS REQUIRED FOR CONSTRUCTION AND AUTHORITIES HAVING JURISDICTION. 32.- ELECTRICAL CONTRACTOR SHALL ASSURE THAT ALL FEATURES OF SERVICE COMPLY WITH THE POWER COMPANY'S REQUIREMENTS AND SHALL MAKE ALL NECESSARY ARRANGEMENTS WITH POWER COMPANY FOR SERVICE. ALL EQUIPMENT NOT FURNISHED AND /OR INSTALLED BY THE POWER CO. IS TO BE FURNISHED AND INSTALLED BY THE ELECTRICAL CONTRACTOR. 33.- U.O.N., COORDINATE REQUIRED A.I.C. RATINGS WITH POWER COMPANY. 34. -WHERE MORE THAN ONE DEVICE IS INDICATED AT ANY LOCATION, THESE SHALL BE GANGED UNDER ONE COMMON COVER. 35.- QUANTITY AND LOCATION OF ELECTRICAL, TELEPHONE /DATA & TV OUTLETS, LIGHTS AND LIGHT CONTROLS, SHALL BE ADJUSTED TO SUIT THE OWNER'S REQUIREMENTS AS PER OWNER /ARCHITECT INSTRUCTIONS. SAID ARRANGEMENTS SHALL NOT BE IN CONFLICT WITH APPLICABLE CODES. 36.- ELECTRICAL CONTRACTOR SHALL VERIFY REQUIREMENTS, EXACT LOCATIONS, TYPE AND ARRANGEMENT OF OUTLETS FOR ALL ELECTRICAL FIXTURES, APPLIANCES AND EQUIPMENT, PRIOR TO INSTALLATION. 37. -ALL BRANCH CIRCUITS THAT SUPPLY 125 - VOLTS, SINGLE PHASE, 15 AND 20 AMPERE OUTLETS INSTALLED IN DWELLING UNIT BEDROOMS SHALL BE PROTECTED BY AN ARC -FAULT CIRCUIT INTERRUPTER (AFCI) LISTED TO PROVIDE PROTECTION OF THE ENTIRE BRANCH CIRCUIT. 38.- INSTALLATION OF LIGHTING FIXTURES INSIDE CLOTHES CLOSETS SHALL COMPLY WITH THE NEC ARTICLE 410 -8. 39.- PROVIDE A TYPEWRITTEN DIRECTORY FOR EACH ELECTRICAL PANEL. 40.- CONTRACTOR SHALL FURNISH AS -BUILT DRAWINGS TO THE OWNER UPON COMPLETION OF WORK AND PRIOR TO FINAL PAYMENT. 41.- OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST ALLOY WITH THREADED HUBS IN WET /DAMP LOCATIONS AND SPECIAL ENCLOSURES AS REQUIRED FOR OTHER CLASSIFIED AREAS AND SHALL CONFORM TO NEMA STANDARDS. PLASTIC BOXES MAY BE USED WHERE PERMITTED UNDER APPLICABLE CODES AND ORDINANCES. 42 -ALL DISCONNECT SWITCHES SHALL BE SIZED BY NEC REQUIREMENTS TO ACCOMODATE THE EQUIPMENT SERVED, INCLUDING REJECTION CLIPS AND FUSES, WHEN APPLICABLE. SWITCHES SHALL BE HP RATED, QUICK -MAKE, QUICK - BREAK, IN NEMA 1 ENCLOSURES FOR INDOOR AND NEMA 311 FOR OUTDOOR. 43.- VERIFY SLAB STRUCTURAL DESIGN WITH STRUCTURAL ENGINEER. GENERATOR NOTES 1.- GENERATOR MUST BE SET AT, OR ABOVE THE MINIMUM FEMA FLOOD ELEVATION. 2. -A PERMANENT SIGN SHALL BE PLACED AT THE ELECTRICAL SERVICE EQUIPMENT THAT INDICATES THE LOCATION OF ON -SITE OPTIONAL STANDBY POWER SOURCES. 3.- PROVIDE RELAY TO PREVENT A/C HEATER FUNCTION DURING GENERATOR USE. PHASE: 10 VOLTAGE: 120/240 v ?ANEL AMPS: 400 Amps EXISTING PANEL '1TATT TYPE: SQD -QO /FLUSH MAIN BREAKER: 400 (BRANCH BREAKERS TYPE OP, 10KAIC) GFk Ground Fault Interrupter NCL= Non - concurrent load REC= Receptacle Ckt Lts= Lighting Ckt ST= Breaker with shunt trip T= Via timer IS= Isolated ground Ckt C= Via contactor SWD= On -Off Switching Duty /or HID= Rated Breaker,as per NEC 240 -83(D) LV= Via low voltage transformer HAIR= Breaker suitable for the protection of heating,A /C and refrigeration equipment AFCI= Breaker suitable for arc -fault Ckt. protection interrupter bkr. Ck No' USE SPEC VOLT BKR AMP WIRE AWG COND SIZE VA PHASEI Ckt No. USE SPEC VOLT BKR AMP WIRE AWG COND SIZE VA A C 11 ROOF TOP UNIT f� "mil 240 80 EXIST EXIST 16,000 • I 2 X -RAY ( 240 80 EXIST EXIST 16,000 3 Ij 4 10,120/240V I I 400A, 10, ( 1400A, 10 I • 4 L 120/240V 120/240V L WP 120/240V 120/240V - �WP WP - 5 ROOF RECEPTACLES - -J 7 I GFI 120 20 EXIST EXIST 200 • 6 REFRIGERATOR (1) #3 GND CU IN 2 -1/2" 120 20 EXIST EXIST 1,000 7 OUTDOOR LIGHTS THWN (CU) ( 3/4 THWN (CU) I 120 20 EXIST EXIST 1,000 • 8 FREEZER VERIFY) 120 20 EXIST EXIST 1,000 9 ULTRASOUND #5 120 20 EXIST EXIST 1,200 10 AUTOCLAVE #1 120 20 EXIST EXIST 1,400 11 ULTRASOUND #20 120 20 EXIST EXIST 2,000 • 12 AUTOCLAVE #2 120 20 EXIST EXIST 1,400 13 • 14 GENERAL RECEPTACLES 120 20 EXIST EXIST 900 15 16 GENERAL RECEPTACLES 120 20 EXIST EXIST 1,000 17 • 18 GENERAL RECEPTACLES 120 20 EXIST EXIST 1,600 19 GENERAL RECEPTACLES 120 1 20 EXIST EXIST 1,200 • 20 GENERAL RECEPTACLES 120 20 1EXIST EXISTI 1,600 21 GENERAL RECEPTACLES 120 1 20 EXIST EXISTI 1,400 • 22 GENERAL RECEPTACLES 120 20 1EXIST EXISTI 1,600 23 GENERAL RECEPTACLES 120 1 20 EXIST EXISTI 500 • 24 GENERAL RECEPTACLES 120 20 1EXIST EXISTI 1,400 25 GENERAL RECEPTACLES 120 1 20 EXIST EXISTI 2,000 • 26 GENERAL RECEPTACLES 120 20 EXIST EXIST 1,200 27 GENERAL LIGHTS 120 20 EXIST EXIST 800 • 28 GENERAL RECEPTACLES 120 20 EXIST EXIST 800 29 GENERAL LIGHTS 120 20 EXIST EXIST 1,000 30 GENERAL RECEPTACLES 120 20 EXIST EXIST 1,200 31 GENERAL LIGHTS 120 20 EXIST EXIST 1,000 • 32 GENERAL RECEPTACLES 120 20 EXIST EXIST 1,000 33 GENERAL LIGHTS 120 20 EXIST EXIST 800 • 34 35 • 36 37 38 391 40 411 1421 * SEE LOAD CALCULATION *� VERIFY NAME PLATE Load Calculation for Panel A: Equipment Load = 62,100 va 25% Continuos Lights = 625 va 25% Largest Motor = 900 va -50% Rectp demand over 10kW= -3,700 Total VA = 59,925 va Panel Load = 59,925/240= 250 Amps GENERATOR CALCULATION: (A /C with out heater, see generator notes.) Equipment Load = 52,100 va 25% Continuos Lights = 625 va 25% Largest Motor = 900 va -50% Rectp demand over 10kW= -3,700 Total VA = 49,925 va Panel Load = 49,925/240= 208 Amps 1 #8 GND IN 1/2" PVC CONDUIT NEW (3) #500 CU & (1) #3 GND CU IN 2 -1/2" THWN (CU) WEATHERPROOF HOUSING -� ANCHORING BOLTS 6 "X5/8" "RED HEAD" AND NUTS (SEE DETAIL ( "A ") 8" FIBER CONCRETE PAD U 3 1Q WIRE MESH, ATTACH 8" CONS. SLAB W/ #5 @ 12" TO #5 RIGID BAR O.C. IN 'E A. DIRECTION ON 6 MIL. \ _ _ WELL COMPACTED FILL;- mu \ I 12" X 18" CONC. FOOTING W/ (1) #5 CONTINUOUS o` >O \ DETAIL „A., J JJ PAD ANCHORING JJ ( MIN. 3/8"x2" TAP CONS, OR EQUAL) J �. EXISTING I J EXISTING _I A.T.S. 1 METER /MAIN J -�-�JJ ;DETER GAS �\ JJJ-_)JJ \ JJJJJJJ JJJJJJ . ". JJJJ_IJ \ _1JJJJJ _j _j \"GENERATOR \ CONC.POL V AW M ;AL 51TE FLAN s N J40 PROPERTY LINE 168.91' N.T.5 I EXISTING GROUNDING RODS Cf g 0 I: 0 CA. # 9360 THE ENGINEERING CONSULTING GROUP, P.A. MECHANICAL, ELECTRICAL, PLUMBING. & FIRE PROTECTION ENGINEERING DESIGN 4937 S.W. 74th Ct Miami, Florida 33155 Tel: (305) 663 -9191 ` Fax: (305) 663-8788 tecgroup@tecgroup-pa.com n W }'��- .�,� °► -,-sue ERh6 0DRPGUEZ MECHANIC L ENGINEER PE# 58155 0 ......... . _0 .� J. 0 Clio Q Q W Z W C.7 W W o�w1 W U p`� VJ •wz�- W ` .r W W W U =u- x �'- W CY) 0 a) to o (a E Z W sb d"- W • a. WRITTEN DIMENSIONS ON THIS DRAWINI;` SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS. CONTRACTOR SHALL VERI AND BE RESPONSIBLE FOR ALL DIMENSIONS AND CONDITIONS ON THEO JOB. THE DESIGN PROFESSIONAL MUST ErE NOTIFIED IN WRITING OF ANY VARIATIC;W;h FROM THE DIMENSIONS. PLANS ARE PROTECTED UNDER THE COPYRIGHT LAWS OF FLORIDA: ALL RIGHTS RESERVED ALL IDEAS DESIGN ARRANGEMENTS AND PLANS INDICATED OR REPRESENTED BY THIS DRAWINGS ARE OWNED BY AND THE PROPERTY OF THE DESIGN PROFESSIONAL AND WERE CREATED EVOLVED AND DEVELOPED FOR USE ON AND IN CONNECTION WITH THE SPECIFIED PROJECT. ANY CHANGES TO THESE PLANS WITHOUT THE WRITTEN APPROVAL OF THE DESIGN PROFESSIONAL OR ANY CONSTRUCTION EXECUTED FROM THESE PLANS WITHOUT EXPRESSED APPROVAL OF THE DESIGN PROFESSIONAL SHALL AUTOMATICALLY RENDER THE DESIGN PROFESSIONAL HARMLESS TO ANY LIABILITY CLAIMS, SLIT OR LITIGATION BY ANY INTERESTED PARTIES OF THE PROJECT. PART THEREOF OF THESE PLANS SHALL BE COPIED OR REPRODUCED BY ANY MEANS, OR USED IN CONNECTION WITH ANY WORK OTHER THAN FOR THE SPECIFIC PROTECT FOR WHICH THEY HAVE BEEN PREPARED WITHOUT WRITTEN CONSENT OF THE DESIGN PROFESSIONAL. Revisions: ISSUE DATE SeDt.19, 2008 DVVN E.R. APPRV E.R. Phase: CONSTRUCTION DOCUMENTS Scale: AS NOTED Dwg Title: .- -- ELECTRICAL GENERATOR SITE PLAN,`CALCS. & SCHED. ® Sheet No.: E -1 I- 7 EXISTING 60A PLUG F- - EXISTING (3) #500 CU IN 2 -1/2" FOR PORTABLE THWN (CU) TO "FP &L" POLE L _j GENERATOR. r (CONTRACTOR TO VERIFY) J r- - - EXISTING SERVICE TO "FP F I= p 1 f� "mil F- T &L" POLE I I ` EXISTING I I ( -,/ I PANEL 'A I ( EXISTING jI I EXISTING I EXISTING I I EXISTING ATS METER METER 10,120/240V I I 400A, 10, ( 1400A, 10 I 400A, 10 I I 150A, 10 42 SPACE L L 120/240V 120/240V L WP 120/240V 120/240V - �WP WP - - -J 7 I EXISTING (3) #500 CU & �_ (1) #3 GND CU IN 2 -1/2" EXISTING (1) #1/0 CU IN THWN (CU) ( 3/4 THWN (CU) I (CONTRACTOR TO VERIFY) (CONTRACTOR TO ( :6--TO C.W.P VERIFY) L- - - - - - - -i _B N.T.5 I EXISTING GROUNDING RODS Cf g 0 I: 0 CA. # 9360 THE ENGINEERING CONSULTING GROUP, P.A. MECHANICAL, ELECTRICAL, PLUMBING. & FIRE PROTECTION ENGINEERING DESIGN 4937 S.W. 74th Ct Miami, Florida 33155 Tel: (305) 663 -9191 ` Fax: (305) 663-8788 tecgroup@tecgroup-pa.com n W }'��- .�,� °► -,-sue ERh6 0DRPGUEZ MECHANIC L ENGINEER PE# 58155 0 ......... . _0 .� J. 0 Clio Q Q W Z W C.7 W W o�w1 W U p`� VJ •wz�- W ` .r W W W U =u- x �'- W CY) 0 a) to o (a E Z W sb d"- W • a. WRITTEN DIMENSIONS ON THIS DRAWINI;` SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS. CONTRACTOR SHALL VERI AND BE RESPONSIBLE FOR ALL DIMENSIONS AND CONDITIONS ON THEO JOB. THE DESIGN PROFESSIONAL MUST ErE NOTIFIED IN WRITING OF ANY VARIATIC;W;h FROM THE DIMENSIONS. PLANS ARE PROTECTED UNDER THE COPYRIGHT LAWS OF FLORIDA: ALL RIGHTS RESERVED ALL IDEAS DESIGN ARRANGEMENTS AND PLANS INDICATED OR REPRESENTED BY THIS DRAWINGS ARE OWNED BY AND THE PROPERTY OF THE DESIGN PROFESSIONAL AND WERE CREATED EVOLVED AND DEVELOPED FOR USE ON AND IN CONNECTION WITH THE SPECIFIED PROJECT. ANY CHANGES TO THESE PLANS WITHOUT THE WRITTEN APPROVAL OF THE DESIGN PROFESSIONAL OR ANY CONSTRUCTION EXECUTED FROM THESE PLANS WITHOUT EXPRESSED APPROVAL OF THE DESIGN PROFESSIONAL SHALL AUTOMATICALLY RENDER THE DESIGN PROFESSIONAL HARMLESS TO ANY LIABILITY CLAIMS, SLIT OR LITIGATION BY ANY INTERESTED PARTIES OF THE PROJECT. PART THEREOF OF THESE PLANS SHALL BE COPIED OR REPRODUCED BY ANY MEANS, OR USED IN CONNECTION WITH ANY WORK OTHER THAN FOR THE SPECIFIC PROTECT FOR WHICH THEY HAVE BEEN PREPARED WITHOUT WRITTEN CONSENT OF THE DESIGN PROFESSIONAL. Revisions: ISSUE DATE SeDt.19, 2008 DVVN E.R. APPRV E.R. Phase: CONSTRUCTION DOCUMENTS Scale: AS NOTED Dwg Title: .- -- ELECTRICAL GENERATOR SITE PLAN,`CALCS. & SCHED. ® Sheet No.: E -1