08-1188-0011- CLOSE OVERHANG SOFFIT VENTS WITHIN 10' OF GENERATOR EXAUST TERMINATION POINT AND RE -OPEN THE SAME NUMBER OF CLOSED /SEALED VENTS AT OTHER OVERHANG LOCATION 2- GENERATOR EXHAUST TERMINATION POINT SHALL NOT BE LOCATED WITHIN 10' OF ANY BUILDING OPENING (WINDOW, DOOR WALL /ROOF VENTS, WALL A/C UNITS, ETC.) GENERATOR SCHEDULE ELECTRICAL GENERAL NOTES ARMSTRONG 1.- OVERALL INSTALLATION: THE INSTALLATION SHALL COMPLY WITH THE NATIONAL 11.- DATA /TELECOMMUNICATION SYSTEMS: FOR DATA /TELECOMMUNICATION SYSTEMS 24. -ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN ACCESIBLE AREAS ONLY AND ELECTRICAL CODE (NEC), THE FLORIDA BUILDING CODE (FBC), AND ANY OTHER UTILIZE A CONTRACTOR EXPERIENCED IN THE INSTALLATION OF ABOVE BASE FLOOD ELEVATION. APPLICABLE FEDERAL, STATE AND LOCAL CODES. COMMUNICATIONSYSTEMS AND CERTIFIED BY BUILDING INDUSTRY CONSULTING SERVICE ENGINE /ALTERNATOR(RPM) 1,800 INTERNATIONAL. 25.- CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL WIRING, BREAKER AND FUSES 2.'�'CONDUCTOR CALCULATIONS: CONDUCTOR CALCULATIONS ARE BASED ON 75'C, 72 dB(A) SIZES IN ACCORDANCE WITH.A /C EQUIPMENT NAMEPLATES, IF DIFFERENT FROM THOSE 97 x 37 x 57.6 12- CUTTING AND PATCHING: MAJOR CUTTING, PATCHING & PAINTING REQUIRED BY THIS SPECIFIED ON DRAWINGS, AS WELL AS ANY FEEDER CHANGES BEING AFFECTED BY 3. 'GENERAL: THE GENERAL AND SPECIAL CONDITIONS AND REQUIREMENTS OF THE CONTRACT WILL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER. ALL THIS CHANGE. CONTRACTOR SHALL MAKE ABOVE MENTIONED CHANGES AT NO EXTRA CONTRACT AND SPECIFICATIONS AS WELL AS PLANS AND SPECIFICATIONS OF OTHER SURFACES SHALL BE RETURNED TO ORIGINAL CONDITIONS AFTER THE INSTALLATION COST. DISCIPLINES AND TRADES SHALL BE A PART OF THE WORK HEREBY SPECIFIED. THESE OF THE EQUIPMENT. EXIST SPECIFICATIONS AND ACCOMPANYING PLANS ARE INTENDED TO PROVIDE FOR THE 16,000 26.- ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL; CONTRACTOR TO COMPLETE FURNISHING AND INSTALLATION OF THE ELECTRICAL SYSTEMS. TO PROVIDE 13. -THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF PROVIDE ALL REQUIRED J =BOXES AND CONDUITS FOR INSTALLATION OF CONTROL MEANS TO FURNISH AND INSTALL. THE LOCAL ELECTRIC UTILITY AND THE TELEPHONE COMPANY. WIRING. LOW VOLTAGE CONTROL WIRING AND THEIR TERMINATION IS THE EXIST EXIST RESPONSIBILITY OF THE, MECHANICAL CONTRACTOR. 4.- COMPLIANCE: WORKMANSHIP, MATERIALS AND INSTALLATION SHALL BE IN STRICT 14. -LOAD DATA IS BASED ON INFORMATION PROVIDED TO THE ENGINEER AT THE TIME ACCORDANCE WITH THE APPLICABLE EDITION OF THE NEC, NFPA, NEMA, ASTM, OSHA, OF DESIGN. ALL EQUIPMENT AND PANEL SIZES SHALL BE VERIFIED BEFORE ORDERING. 27.- ELECTRICAL METER AND .PANEL LOCATIONS SHOWN MAY :VARY. DEPENDING ON HRS HEALTH AGENCIES, AND OTHER APPLICABLE NATIONAL, STATE, AND LOCAL SERVICE ENTRANCE LOCATION. CODES AND PERTAINING REGULATIONS ESTABLISHED BY THE RULING AUTHORITY 15.- CIRCUITS SHOWN ON PLANS ARE USED TO DETERMINE LOAD DATA AND PANEL 4 HAVING JURISDICTION, CONTRACTORS SHALL ALSO MEET THE REQUIREMENTS OF SIZES. THE CONTRACTOR SHALL PROVIDE CIRCUIT ROUTING TO SUIT THE JOB 28. -ALL LIGHTING FIXTURES TO BE SELECTED, BY THE OWNER /ARCHITECT, U.O.N. AND OTHER STANDARDS WHERE SUCH REQUIREMENTS ARE MORE STRICT THAN THOSE CONDITIONS. SHALL BE INSTALLED BY THIS CONTRACTOR. STANDARDS CITED ABOVE. 5 ROOF RECEPTACLES 16.- FURNISH AND INSTALL ALL FIXTURES AS CALLED FOR ON THE PLANS OR AS 29.- BALANCE ALL PHASES AT EACH PANEL AND MDP /SERVICE MAINS. 5.- WORKMANSHIP: ALL WORK SHALL BE PERFORMED BY CONTRACTORS LICENSED IN SELECTED BY OWNER /ARCHITECT. EXIST THEIR RESPECTIVE DISCIPLINE. WORK SHALL BE DONE IN A FIRST CLASS MANNER, 30. -CHECK AVAILABLE ELECTRICAL SERVICE CHARACTERISTICS WITH THE LOCAL FULLY OPERATIVE, AND TO THE ACCEPTANCE OF THE ARCHITECT AND THE ENGINEERS. 17.- MINIMUM WIRE SIZE SHALL BE #14 AWG. UNLESS OTHERWISE NOTED, ALL POWER COMPANY PRIOR TO ORDERING ANY EQUIPMENT. INFORM THE ARCH /ENGINEER IF CONTRACTOR SHALL PROVIDE FOR ALL NECESSARY LABOR AND MATERIAL REQUIRED CONDUCTORS SHALL BE COPPER WITH THHN /THWN INSULATION. CONDUCTORS #10 AND IT IS DIFFERENT FROM WHAT IS SHOWN ON PLANS. FOR THE COMPLETION OF THE WORK INCLUDING BUT NOT LIMITED TO RELATED WORK SMALLER MAY BE SOLID; #8 AND LARGER SHALL BE STRANDED ALUMINUM 7 SUCH AS CONNECTION OF EXISTING SYSTEMS, EXCAVATIONS AND BACK FILLING. CONDUCTORS MAY BE ALLOWED FOR SERVICE ENTRANCE IF SPECIFICALLY APPROVED 31.- CONTRACTOR SHALL PROVIDE TEMPORARY SERVICE AND LIGHTING FOR USE OF 120 BY THE ENGINEER. ALL TRADES AS REQUIRED FOR CONSTRUCTION AND AUTHORITIES HAVING 6.- MATERIALS: CONTRACTOR SHALL PROVIDE ALL NEW MATERIALS OF AMERICAN 1,000 JURISDICTION. MANUFACTURE, BEARING THE UNDERWRITER'S LABORATORY (UL) LABEL AS 18. -ALL CONDUCTORS SHALL BE RUN IN CONDUIT, U.O.N. FREEZER APPLICABLE. MATERIALS SHALL BE NEW, SUITABLE FOR THE APPLICATION AND 120 32.- ELECTRICAL CONTRACTOR SHALL ASSURE THAT ALL FEATURES OF SERVICE ABOVE STANDARD QUALITY NORMALLY USED FOR THE PURPOSE AS CALLED FOR ON 19.- INSTALL 3/4" EMPTY CONDUIT TO ALL TELEPHONE /DATA OUTLETS. PROVIDE PULL COMPLY WITH THE POWER COMPANY'S REQUIREMENTS AND SHALL MAKE ALL PLANS, SUPPLEMENTAL MATERIALS, PRODUCTS AND COMPONENTS NECESSARY TO WIRE. NECESSARY ARRANGEMENTS WITH POWER COMPANY FOR SERVICE. ALL EQUIPMENT COMPLY WITH THE INTENT OF THE CONTRACT DRAWINGS AND /OR SPECIFICATIONS, 120 NOT FURNISHED AND /OR INSTALLED BY THE POWER CO. IS TO BE FURNISHED AND BUT NOT NOTED OR SPECIFIED ON THESE SECTIONS, SHALL BE PROVIDED BY THE 20. -ALL CONDUITS SHALL BE GALVANIZED RIGID (GRC), EXCEPT AS FOLLOWS: INSTALLED BY THE ELECTRICAL CONTRACTOR. CONTRACTOR AS REQUIRED FOR THE COMPLETION OF THE WORK AT NO ADDITIONAL 10 COST TO THE OWNER. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVISIONS AND (A) UL LISTED PVC CONDUITS MAY BE USED UNDERGROUND OUTDOORS OR 33.- U.O.N., COORDINATE REQUIRED A.I.C. RATINGS WITH POWER COMPANY. COORDINATION OF DELIVERY OF MATERIALS. EQUIPMENT MARRED DURING SHIPMENT OR UNDER SLAB INSIDE THE BUILDING AS ALLOWED BY CODE. CONDUIT FITTINGS AND EXIST INSTALLATION SHALL BE TOUCHED UP AND REFINISHED TO FACTORY FINISH, CEMENT SHALL BE PRODUCED BY THE SAME MANUFACTURER. 34. -WHERE MORE THAN ONE DEVICE IS INDICATED AT ANY LOCATION, THESE SHALL REPLACED WHERE NOT ACCEPTABLE. BE GANGED UNDER ONE COMMON COVER. 20 (B) ELECTRICAL METALIC TUBING (EMT), MAY BE USED IN OR ON WALLS OR EXIST 7.- PERMITS AND INSURANCE: CONTRACTOR SHALL SECURE AND PAY FOR ALL CEILINGS WHERE NOT SUBJECT TO MECHANICAL DAMAGE, CORROSIVE OR DAMP 35.- QUANTITY AND LOCATION OF ELECTRICAL, TELEPHONE /DATA & TV OUTLETS, PERMITS, FEES, TAXES, INSPECTIONS, TESTS, FINES AND OTHER ITEMS AS REQUIRED CONDITIONS. LIGHTS AND LIGHT CONTROLS, SHALL BE ADJUSTED TO SUIT THE OWNER'S FOR THE INSTALLATION OF THE COMPLETE ELECTRICAL SYSTEMS AS OUTLINED HEREIN 20 REQUIREMENTS AS PER OWNER /ARCHITECT INSTRUCTIONS. SAID ARRANGEMENTS AND SHOWN ON PLANS, CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR (C) ELECTRICAL NON METALIC TUBING (ENT), MAY BE USED WHEN INSTALLED IN SHALL NOT BE IN CONFLICT WITH APPLICABLE CODES. PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION ACCORDANCE WITH THE REQUIREMENTS OF THE NEC ARTICLE 362 AND ONDUIT OF THE WORK. MANUFACTURER'S INSTRUCTIONS. 36.- ELECTRICAL CONTRACTOR SHALL VERIFY REQUIREMENTS, EXACT LOCATIONS, ,TYPE AND ARRANGEMENT OF OUTLETS FOR ALL ELECTRICAL FIXTURES;. APPLIANCES AND 8.- EXISTING CONDITIONS: BEFORE BIDDING, THE CONTRACTOR SHALL VISIT THE JOB (D) METAL CLAD CABLE (MC), SHALL BE LIMITED TO BRANCH CIRCUITING AND BE EQUIPMENT, PRIOR TO INSTALLATION. SITE AND ASCERTAIN ALL EXISTING CONDITIONS WHICH WILL AFFECT HIS WORK. INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF NEC ARTICLE 330 AND CABLE 20 FAILURE TO DO SO WILL NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA MANUFACTURER'S INSTRUCTIONS. 3i. -ALL BRANCH CIRCUITS THAT SUPPLY 125 - VOLTS, SINGLE PHASE, 15 AND 20 PAY WHERE THE EXISTING CONDITIONS RESULT IN EXTRA MATERIALS OR ANY AMPERE OUTLETS INSTALLED IN DWELLING UNIT BEDROOMS SHALL BE PROTECTED BY EXISTING CONDITIONS FOUND BY THE CONTRACTOR WHICH WILL ADVERSELY AFFECT (E) NONMETALLIC CABLE (NM), (NMC) & (NMS) MAY BE USED FOR INTERIOR AN ARC -FAULT CIRCUIT INTERRUPTER (AFCI) LISTED TO PROVIDE PROTECTION OF THE THE WORK SHALL BE IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE WIRING, EXPOSED OR CONCEALED IN DRY LOCATIONS, MUST NOT BE USED EMBEDDED ENTIRE BRANCH CIRCUIT. ARCHITECT /ENGINEER. CORRECTION OF ANY DEFECTS SHALL BE COMPLETELY WITHOUT IN CONCRETE, MASONRY, FILL OR PLASTER, ITS USE AND INSTALLATION SHALL 16 ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENTS OR REPAIR OF ANY OTHER COMPLY WITH NEC ARTICLE 334. 38.- INSTALLATION OF LIGHTING FIXTURES INSIDE CLOTHES CLOSETS SHALL COMPLY PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY. EXIST WITH THE NEC ARTICLE 410 -8. 1,000 (F) FLEXIBLE CONDUIT SHALL BE USED FOR CONNECTIONS TO VIBRATING 9.- SUBSTITUTIONS: PRODUCTS AND MATERIALS CALLED OUT BY TRADE NAME EQUIPMENT AND RECESSED LIGHT FIXTURES, WHERE PERMITTED BY CODE. EMBEDDED 39.- PROVIDE A TYPEWRITTEN DIRECTORY FOR EACH ELECTRICAL PANEL. AND /OR CATALOG NUMBERS ESTABLISH A STANDARD OF QUALITY, APPEARANCE, IN CONCRETE, MASONRY, FILL OR PLASTER. IF USED OUTDOORS, IT SHALL BE 40.'-CONTRACTOR SHALL FURNISH -AS =BUILT DRAWINGS TO THE OWNER UPON PERFORMANCE AND DIMENSION. CONTRACTORS SHALL BASE HIS PROPOSAL ON THOSE LIQUIDTIGHT. ITEMS AS THEY SHALL BE CONSIDERED AS A STANDARD BASIS OF BIDDING. GENERAL RECEPTACLES COMPLETION OF WORK AND PRIOR TO FINAL PAYMENT. REQUESTS FOR SUBSTITUTION SHALL BE SUBMITTED IN WRITING TO THE 21.- PROVIDE FIRE RETARDANT U.L. APPROVED SEALANT ON ALL PENETRATIONS, 'ALLOY ARCHITECT /ENGINEER, DEMONSTRATING THAT PRODUCT IS OF COMPARABLE AND BASIC WALLS AND STRUCTURAL SLABS. IT SHALL BE THE RESPONSIBILITY OF THE 41.- OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST WITH DESIGN, CONSTRUCTION, STANDARDS AND WARRANTIES, DIMENSIONS TO FIT WITHOUT ELECTRICAL CONTRACTOR TO VERIFY, PRIOR TO SUBMITTING BID, THE LOCATIONS OF THREADED' HUBS-IN WET /DAMP LOCATIONS AND SPECIAL ENCLOSURES AS REQUIRED CHANGE, AND DOES NOT CAUSE EXTRA WORK TO OTHER TRADES. CONTRACTOR ALL SUCH FIRE RATED PARTITIONS, WALLS, AND STRUCTURAL SLABS. FOR OTHER CLASSIFIED AREASiAND'SHALL CONFORM TO NEMA STANDARDS. PLASTIC SHALL BE RESPONSIBLE FOR PROVIDING EQUALITY OF SUBSTITUTION: 1,200 BOXES MAY BE USED WHERE PERMITTED UNDER APPLICABLE CODES AND ORDINANCES. ARCHITECT /ENGINEER WILL, UNDER NO CIRCUMSTANCES, BE REQUIRED TO PROVE SUCH 22,- INTERFERENCE: THE CONTRACTOR SHALL COORDINATE HIS WORK WITH OTHER GENERAL RECEPTACLES ITEM IS OR IS NOT OF EQUAL QUALITY TO THE SPECIFIED ITEM. ARCHITECT /ENGINEER TRADES SO THAT INTERFERENCE WITH EXISTING CONDITIONS, CONDUITS, PIPING, 42 -ALL DISCONNECT SWITCHES SHALL BE SIZED BY NEC REQUIREMENTS TO EXPENSES INCURRED DUE TO CONTRACTOR'S REQUESTED REVISIONS OR EQUIPMENT, ARCHITECTURAL AND STRUCTURAL MEMBERS BE AVOIDED. ACCOMODATE THE EQUIPMENT SERVED, INCLUDING REJECTION CLIPS AND FUSES, WHEN SUBSTITUTIONS SHALL BE PAID BY THE CONTRACTOR. GENERAL RECEPTACLES APPLICABLE. SWITCHES SHALL BE HP RATED, QUICK -MAKE, QUICK - BREAK, IN NEMA 1 23.- PLANS: DRAWINGS ARE BASICALLY DIAGRAMS INTENDED TO DEPICT ENCLOSURES FOR INDOOR AND NEMA 3R FOR OUTDOOR. 10.- MOTORS STARTERS SHALL BE MANUAL OR MAGNETIC AS INDICATED OR REQUIRED, APPROXIMATELY EQUIPMENT LOCATIONS AND ARRANGEMENTS, NOT TO SHOW EVERY 1,400 WITH OVERLOAD RELAYS OR FUSES IN EACH HOT LEG. MINOR DETAIL. PLANS SHALL NOT BE SCALED TO DETERMINE EXACT LOCATION AND 43.= VERIFY SLAB STRUCTURAL DESIGN WITH STRUCTURAL ENGINEER. GENERAL RECEPTACLES DIMENSIONS. 120 1- CLOSE OVERHANG SOFFIT VENTS WITHIN 10' OF GENERATOR EXAUST TERMINATION POINT AND RE -OPEN THE SAME NUMBER OF CLOSED /SEALED VENTS AT OTHER OVERHANG LOCATION 2- GENERATOR EXHAUST TERMINATION POINT SHALL NOT BE LOCATED WITHIN 10' OF ANY BUILDING OPENING (WINDOW, DOOR WALL /ROOF VENTS, WALL A/C UNITS, ETC.) GENERATOR SCHEDULE MANUFACTURE ARMSTRONG MODEL # AGM60Si RATED POWER 60 kW VOLTAGNSINGLE PHASE) 120/240 Amps (la 120/240 225 NG ENGINE /ALTERNATOR(RPM) 1,800 MAIN LINE CIRCUIT BREAKER 400 Am SOUND OUTPUT AT FULL LOAO(23 ft) 72 dB(A) DIMENSIONS (L "xW "xH ") 97 x 37 x 57.6 WEIGHT 1,207 Kg GENERATOR NOTES 1.- GENERATOR MUST BE SET AT, OR ABOVE THE MINIMUM FEMA FLOOD ELEVATION. 2. -A PERMANENT SIGN SHALL BE PLACED AT THE ELECTRICAL SERVICE EQUIPMENT THAT INDICATES THE LOCATION OF ON -SITE OPTIONAL STANDBY POWER SOURCES. 3.- PROVIDE RELAY TO PREVENT A/C HEATER FUNCTION DURING GENERATOR USE. PHASE: 10 VOLTAGE: 120/240 v PANEL AMPS: 400 Amps EXISTING PANEL •'A" TYPE: SQD -QO /FLUSH MAIN BREAKER: 400 (BRANCH BREAKERS TYPE GP, 10KAIC) GFI= Ground Fault Interrupter NCL= Non - concurrent load REC= Receptacle Ckt Lts= Lighting Ckt ST= Breaker with shunt trip T= Via timer IS= Isolated ground Ckt C= Via contactor SWO= On -Off Switching Duty /or HID= Rated Breaker,as per NEC 240 -83(0) LV= Via low voltage transformer HACK= Breaker suitable for the protection of heating,A /C and refrigeration equipment AFCI= Breaker suitable for arc -fault Ckt. protection Interrupter bkr. Ckt No USE PANEL SPEC VOLT BKR AMP WIRE AWG COND SIZE VA PHASE Ckt No. USE SPEC VOLT BKR AMP WIRE AWG COND SIZE VA A C 1 ROOF TOP UNIT 240 80 EXIST EXIST 16,000 • 2 X -RAY 240 80 EXIST EXIST 16,000 3 11 u 4 11 u 5 ROOF RECEPTACLES GFI 120 20 EXIST EXIST 200 6 REFRIGERATOR 120 20 EXIST EXIST 1,000 7 OUTDOOR LIGHTS 120 20 EXIST EXIST 1,000 • 8 FREEZER 120 20 EXIST EXIST 1,000. 9 ULTRASOUND #5 120 20 EXIST EXIST 1,200 • 10 AUTOCLAVE #1 120 20 EXIST EXIST 1,400 11 ULTRASOUND #20 120 20 EXIST EXIST 2,000 12 AUTOCLAVE #2 120 20 EXIST EXIST 1,400 13 • 1 14 GENERAL RECEPTACLES 120 20 EXIST EXIST 900 15 • 16 GENERAL RECEPTACLES 120 20 EXIST EXIST 1,000 17 • 18 GENERAL RECEPTACLES 120 20 EXIST EXIST 1,600 19 GENERAL RECEPTACLES 120 20 EXIST EXIST 1,200 • 20 GENERAL RECEPTACLES 120 20 EXIST EXIST 1,600 21 GENERAL RECEPTACLES 120 20 EXIST EXIST 1,400 • 22 GENERAL RECEPTACLES 120 20 EXIST EXIST 1,600 23 GENERAL RECEPTACLES 120 20 EXIST EXIST 500 • 1 24 GENERAL RECEPTACLES 120 20 EXIST EXIST 1,400 25 GENERAL RECEPTACLES 120 20 EXIST EXIST 2,000 • 1 26 GENERAL RECEPTACLES 120 20 EXIST EXIST 1,200 27 GENERAL LIGHTS 120 20 EXIST EXIST 800 • 28 GENERAL RECEPTACLES 120 20 EXIST EXIST 800 29 GENERAL LIGHTS 120 20 EXIST EXIST 1,000 30 GENERAL RECEPTACLES 120 20 EXIST EXIST 1,200 31 GENERAL LIGHTS 120 20 EXIST EXIST 1,000 • 32 GENERAL RECEPTACLES 120 20 EXIST EXIST 1,000 33 GENERAL LIGHTS 120 20 EXIST EXIST 800 • 34 351 • 36 37 1 J a 38 39 1 1 • 40 41 * SEE LOAD CALCULATION ** VERIFY NAME PLATE • Load Calculation for Panel A: Equipment Load = 62,100 va 25% Continuos Lights = 625 va 25% Largest Motor = 900 va -50% Rectp demand over 10kW= -3,700 Total VA = 59,925 va Panel Load = 59,925/240= 250 Amps 42 GENERATOR CALCULATION: (A /C with out heater, see generator notes.) Equipment Load = 52,100 va 25% Continuos Lights = 625 va 25% Largest Motor = 900 va -50% Rectp demand over 10kW= -31700 Total VA = 49,925 va Panel Load = 49,925/240= 208 Amps #8 GND IN 1/2" PVC CONDUIT v/ \` WEATHERPROOF HOUSING �y NEW (3) #500 CU & (03 GND CU IN 2 -1/2" THWN (CU) ANCHORING "RED H (S ` WIRE MESH, ATTACH 8" C IN EA. DIRECTION ON 12" TO #5 RIGID BAR 6 MIL. \ WELL COMPACTED FILL. \ al '�I I IIIr 12" X 18" CONC. FOOTING W/ (1) #5 CONTINUOUS � \ � \app y °qF DETAIL "A" IQ lz11- 1 PAD ANCHORING �_j _j _j ( MIN. 3/8 "x2" TAP CONS. OR EQUAL) EXISTING I I EXISTING J _ A.T.S. I J NAT GAS \ METER /MAIN _j -j-I -I ETER ` JJJJJJ P_jJJJJJ .:.. JJJJJJ `� JJJJJJ JJJJ _j _j \ GENERATOR CONC.POLE \ �L SITE PLAN ' . N 40 soly PROPERTY LINE 168.91' P,???, 0,4f X. EXISTING 60A PLUG EXISTING (3) #500 CU IN 2 -1/2" L J FOR PORTABLE THWN (CU) TO "FP &L" 10066:_ GENERATOR. (CONTRACTOR TO VERIFY) I- - - EXISTING SERVICE TO J "FP &L" POLE co F -T" r M _ IC1TY OF SOUTH MIAMI I EXISTING � --� � � � _ ( � -i I I �' -�' I PANEL "A" ' I EXISTING I ( EXISTING EXISTING EXISTING _ BUILDING DEPT. 400A MCB, ATS MCB I METER I I METER I ELECTRICAL SECTION 10,120/240V ( I 400A, 10, I 1400A, 10 I 400A,10 I I 150A, 10 42 SPACE 120/240V 120/240V 120/240V 120/240V L J L - L WP 7 J W W P I P APPROVED BY. EXISTING (3) #500 CU & b- EXISTING (1) #1/0 CU IN (1) #3 GND CU IN 2 -1/2" I 3/4 THWN (CU) I DAM c THWN (CU) (CONTRACTOR TO (CONTRACTOR TO VERIFY) I VERIFY) -TO C.W.P - - - - CITY OF SOUTH MIA BUILDING DEPT. STRUCTURAL SECTION EXISTING ��� �;PPROVED BY: GROUNDING RODS CL4TE 1111 f ELECTRICAL RISER DIAGRAM N.T.S C.A. # 9360 THE ENGINEERING CONSULTING GROUP, P.A. MECHANICAL, ELECTRICAL, PLUMBING, 8 PRE PROTECTION ENGINEERING DESIGN 4937 S.W. 74th CL Miami, Florida 33155 Tel: (305) 663 -9191 Fax: (305)663 -6768 tecgroup@tecgroup- pa.com Seal /. o � �s .... ERNESTi0:RODRIGUEZ MECHANICAL ENGINEER PE #:58155 L � �O 0 L >- LL 0 ICU < Q N z W 2 I- Vr W Z n c�WU -L > J Q W WQ� _ �W W W X C: o a) :D _ 0) O E O 0 m E W Z m W 0) o M EL (U WRITTEN DIMENSIONS ON THIS DRAWING SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS. CONTRACTOR SHALL VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND CONDITIONS ON THE JOB. THE DESIGN PROFESSIONAL MUST BE NOTIFIED IN WRITING OF ANY VARIATION FROM THE DIMENSIONS. PLANS ARE PROTECTED UNDER THE COPYRIGHT LAWS OF FLORIDA: ALL RIGHTS RESERVED ALL IDEAS DESIGN ARRANGEMENTS AND PLANS INDICATED OR REPRESENTED BY THIS DRAWINGS ARE OWNED BY AND THE PROPERTY OF THE DESIGN PROFESSIONAL AND WERE CREATED EVOLVED AND DEVELOPED FOR USE ON AND IN CONNECTION WITH THE SPECIFIED PROJECT. ANY CHANGES TO THESE PLANS WITHOUT THE WRITTEN APPROVAL OF THE DESIGN PROFESSIONAL OR ANY CONSTRUCTION EXECUTED FROM THESE PLANS WITHOUT EXPRESSED APPROVAL OF THE DESIGN PROFESSIONAL SHALL AUTOMATICALLY RENDER THE DESIGN PROFESSIONAL HARMLESS TO ANY LIABILITY CLAIMS, SUIT OR LITIGATION BY ANY INTERESTED PARTIES OF THE PROJECT. NO PART THEREOF OF THESE PLANS SHALL BE COPIED OR REPRODUCED BY ANY MEANS, OR USED IN CONNECTION WITH ANY WORK OTHER THAN FOR THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN PREPARED WITHOUT WRITTEN CONSENT OF THE DESIGN PROFESSIONAL Revisions: 1 11/17/08 BLD OPT COMMS ISSUE DATE Sept. 19, 2008 DWN E.R. APPRV E.R. Phase: CONSTRUCTION DOCUMENTS Scale: AS NOTED S f Dwg Title: ELECTRICAL GENERATOR SITE PLAN, CALLS. & SCHED S Sheet No.: r E_1 N. GENERATOR - ENGINE CONTROL PANEL ANCHORING "RED H (S ` WIRE MESH, ATTACH 8" C IN EA. DIRECTION ON 12" TO #5 RIGID BAR 6 MIL. \ WELL COMPACTED FILL. \ al '�I I IIIr 12" X 18" CONC. FOOTING W/ (1) #5 CONTINUOUS � \ � \app y °qF DETAIL "A" IQ lz11- 1 PAD ANCHORING �_j _j _j ( MIN. 3/8 "x2" TAP CONS. OR EQUAL) EXISTING I I EXISTING J _ A.T.S. I J NAT GAS \ METER /MAIN _j -j-I -I ETER ` JJJJJJ P_jJJJJJ .:.. JJJJJJ `� JJJJJJ JJJJ _j _j \ GENERATOR CONC.POLE \ �L SITE PLAN ' . N 40 soly PROPERTY LINE 168.91' P,???, 0,4f X. EXISTING 60A PLUG EXISTING (3) #500 CU IN 2 -1/2" L J FOR PORTABLE THWN (CU) TO "FP &L" 10066:_ GENERATOR. (CONTRACTOR TO VERIFY) I- - - EXISTING SERVICE TO J "FP &L" POLE co F -T" r M _ IC1TY OF SOUTH MIAMI I EXISTING � --� � � � _ ( � -i I I �' -�' I PANEL "A" ' I EXISTING I ( EXISTING EXISTING EXISTING _ BUILDING DEPT. 400A MCB, ATS MCB I METER I I METER I ELECTRICAL SECTION 10,120/240V ( I 400A, 10, I 1400A, 10 I 400A,10 I I 150A, 10 42 SPACE 120/240V 120/240V 120/240V 120/240V L J L - L WP 7 J W W P I P APPROVED BY. EXISTING (3) #500 CU & b- EXISTING (1) #1/0 CU IN (1) #3 GND CU IN 2 -1/2" I 3/4 THWN (CU) I DAM c THWN (CU) (CONTRACTOR TO (CONTRACTOR TO VERIFY) I VERIFY) -TO C.W.P - - - - CITY OF SOUTH MIA BUILDING DEPT. STRUCTURAL SECTION EXISTING ��� �;PPROVED BY: GROUNDING RODS CL4TE 1111 f ELECTRICAL RISER DIAGRAM N.T.S C.A. # 9360 THE ENGINEERING CONSULTING GROUP, P.A. MECHANICAL, ELECTRICAL, PLUMBING, 8 PRE PROTECTION ENGINEERING DESIGN 4937 S.W. 74th CL Miami, Florida 33155 Tel: (305) 663 -9191 Fax: (305)663 -6768 tecgroup@tecgroup- pa.com Seal /. o � �s .... ERNESTi0:RODRIGUEZ MECHANICAL ENGINEER PE #:58155 L � �O 0 L >- LL 0 ICU < Q N z W 2 I- Vr W Z n c�WU -L > J Q W WQ� _ �W W W X C: o a) :D _ 0) O E O 0 m E W Z m W 0) o M EL (U WRITTEN DIMENSIONS ON THIS DRAWING SHALL HAVE PRECEDENCE OVER SCALED DIMENSIONS. CONTRACTOR SHALL VERIFY AND BE RESPONSIBLE FOR ALL DIMENSIONS AND CONDITIONS ON THE JOB. THE DESIGN PROFESSIONAL MUST BE NOTIFIED IN WRITING OF ANY VARIATION FROM THE DIMENSIONS. PLANS ARE PROTECTED UNDER THE COPYRIGHT LAWS OF FLORIDA: ALL RIGHTS RESERVED ALL IDEAS DESIGN ARRANGEMENTS AND PLANS INDICATED OR REPRESENTED BY THIS DRAWINGS ARE OWNED BY AND THE PROPERTY OF THE DESIGN PROFESSIONAL AND WERE CREATED EVOLVED AND DEVELOPED FOR USE ON AND IN CONNECTION WITH THE SPECIFIED PROJECT. ANY CHANGES TO THESE PLANS WITHOUT THE WRITTEN APPROVAL OF THE DESIGN PROFESSIONAL OR ANY CONSTRUCTION EXECUTED FROM THESE PLANS WITHOUT EXPRESSED APPROVAL OF THE DESIGN PROFESSIONAL SHALL AUTOMATICALLY RENDER THE DESIGN PROFESSIONAL HARMLESS TO ANY LIABILITY CLAIMS, SUIT OR LITIGATION BY ANY INTERESTED PARTIES OF THE PROJECT. NO PART THEREOF OF THESE PLANS SHALL BE COPIED OR REPRODUCED BY ANY MEANS, OR USED IN CONNECTION WITH ANY WORK OTHER THAN FOR THE SPECIFIC PROJECT FOR WHICH THEY HAVE BEEN PREPARED WITHOUT WRITTEN CONSENT OF THE DESIGN PROFESSIONAL Revisions: 1 11/17/08 BLD OPT COMMS ISSUE DATE Sept. 19, 2008 DWN E.R. APPRV E.R. Phase: CONSTRUCTION DOCUMENTS Scale: AS NOTED S f Dwg Title: ELECTRICAL GENERATOR SITE PLAN, CALLS. & SCHED S Sheet No.: r E_1