08-1188-0011- CLOSE OVERHANG SOFFIT VENTS WITHIN 10' OF GENERATOR
EXAUST TERMINATION POINT AND RE -OPEN THE SAME NUMBER OF
CLOSED /SEALED VENTS AT OTHER OVERHANG LOCATION
2- GENERATOR EXHAUST TERMINATION POINT SHALL NOT BE
LOCATED WITHIN 10' OF ANY BUILDING OPENING (WINDOW, DOOR
WALL /ROOF VENTS, WALL A/C UNITS, ETC.)
GENERATOR SCHEDULE
ELECTRICAL GENERAL NOTES
ARMSTRONG
1.- OVERALL INSTALLATION: THE INSTALLATION SHALL COMPLY WITH THE NATIONAL
11.- DATA /TELECOMMUNICATION SYSTEMS: FOR DATA /TELECOMMUNICATION SYSTEMS
24. -ALL ELECTRICAL EQUIPMENT SHALL BE INSTALLED IN ACCESIBLE AREAS ONLY AND
ELECTRICAL CODE (NEC), THE FLORIDA BUILDING CODE (FBC), AND ANY OTHER
UTILIZE A CONTRACTOR EXPERIENCED IN THE INSTALLATION OF
ABOVE BASE FLOOD ELEVATION.
APPLICABLE FEDERAL, STATE AND LOCAL CODES.
COMMUNICATIONSYSTEMS AND CERTIFIED BY BUILDING INDUSTRY CONSULTING SERVICE
ENGINE /ALTERNATOR(RPM)
1,800
INTERNATIONAL.
25.- CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL WIRING, BREAKER AND FUSES
2.'�'CONDUCTOR CALCULATIONS: CONDUCTOR CALCULATIONS ARE BASED ON 75'C,
72 dB(A)
SIZES IN ACCORDANCE WITH.A /C EQUIPMENT NAMEPLATES, IF DIFFERENT FROM THOSE
97 x 37 x 57.6
12- CUTTING AND PATCHING: MAJOR CUTTING, PATCHING & PAINTING REQUIRED BY THIS
SPECIFIED ON DRAWINGS, AS WELL AS ANY FEEDER CHANGES BEING AFFECTED BY
3. 'GENERAL: THE GENERAL AND SPECIAL CONDITIONS AND REQUIREMENTS OF THE
CONTRACT WILL BE PERFORMED IN A NEAT AND WORKMANLIKE MANNER. ALL
THIS CHANGE. CONTRACTOR SHALL MAKE ABOVE MENTIONED CHANGES AT NO EXTRA
CONTRACT AND SPECIFICATIONS AS WELL AS PLANS AND SPECIFICATIONS OF OTHER
SURFACES SHALL BE RETURNED TO ORIGINAL CONDITIONS AFTER THE INSTALLATION
COST.
DISCIPLINES AND TRADES SHALL BE A PART OF THE WORK HEREBY SPECIFIED. THESE
OF THE EQUIPMENT.
EXIST
SPECIFICATIONS AND ACCOMPANYING PLANS ARE INTENDED TO PROVIDE FOR THE
16,000
26.- ELECTRICAL CONTRACTOR SHALL COORDINATE WITH MECHANICAL; CONTRACTOR TO
COMPLETE FURNISHING AND INSTALLATION OF THE ELECTRICAL SYSTEMS. TO PROVIDE
13. -THE ELECTRICAL INSTALLATION SHALL MEET ALL STANDARD REQUIREMENTS OF
PROVIDE ALL REQUIRED J =BOXES AND CONDUITS FOR INSTALLATION OF CONTROL
MEANS TO FURNISH AND INSTALL.
THE LOCAL ELECTRIC UTILITY AND THE TELEPHONE COMPANY.
WIRING. LOW VOLTAGE CONTROL WIRING AND THEIR TERMINATION IS THE
EXIST
EXIST
RESPONSIBILITY OF THE, MECHANICAL CONTRACTOR.
4.- COMPLIANCE: WORKMANSHIP, MATERIALS AND INSTALLATION SHALL BE IN STRICT
14. -LOAD DATA IS BASED ON INFORMATION PROVIDED TO THE ENGINEER AT THE TIME
ACCORDANCE WITH THE APPLICABLE EDITION OF THE NEC, NFPA, NEMA, ASTM, OSHA,
OF DESIGN. ALL EQUIPMENT AND PANEL SIZES SHALL BE VERIFIED BEFORE ORDERING.
27.- ELECTRICAL METER AND .PANEL LOCATIONS SHOWN MAY :VARY. DEPENDING ON
HRS HEALTH AGENCIES, AND OTHER APPLICABLE NATIONAL, STATE, AND LOCAL
SERVICE ENTRANCE LOCATION.
CODES AND PERTAINING REGULATIONS ESTABLISHED BY THE RULING AUTHORITY
15.- CIRCUITS SHOWN ON PLANS ARE USED TO DETERMINE LOAD DATA AND PANEL
4
HAVING JURISDICTION, CONTRACTORS SHALL ALSO MEET THE REQUIREMENTS OF
SIZES. THE CONTRACTOR SHALL PROVIDE CIRCUIT ROUTING TO SUIT THE JOB
28. -ALL LIGHTING FIXTURES TO BE SELECTED, BY THE OWNER /ARCHITECT, U.O.N. AND
OTHER STANDARDS WHERE SUCH REQUIREMENTS ARE MORE STRICT THAN THOSE
CONDITIONS.
SHALL BE INSTALLED BY THIS CONTRACTOR.
STANDARDS CITED ABOVE.
5
ROOF RECEPTACLES
16.- FURNISH AND INSTALL ALL FIXTURES AS CALLED FOR ON THE PLANS OR AS
29.- BALANCE ALL PHASES AT EACH PANEL AND MDP /SERVICE MAINS.
5.- WORKMANSHIP: ALL WORK SHALL BE PERFORMED BY CONTRACTORS LICENSED IN
SELECTED BY OWNER /ARCHITECT.
EXIST
THEIR RESPECTIVE DISCIPLINE. WORK SHALL BE DONE IN A FIRST CLASS MANNER,
30. -CHECK AVAILABLE ELECTRICAL SERVICE CHARACTERISTICS WITH THE LOCAL
FULLY OPERATIVE, AND TO THE ACCEPTANCE OF THE ARCHITECT AND THE ENGINEERS.
17.- MINIMUM WIRE SIZE SHALL BE #14 AWG. UNLESS OTHERWISE NOTED, ALL
POWER COMPANY PRIOR TO ORDERING ANY EQUIPMENT. INFORM THE ARCH /ENGINEER IF
CONTRACTOR SHALL PROVIDE FOR ALL NECESSARY LABOR AND MATERIAL REQUIRED
CONDUCTORS SHALL BE COPPER WITH THHN /THWN INSULATION. CONDUCTORS #10 AND
IT IS DIFFERENT FROM WHAT IS SHOWN ON PLANS.
FOR THE COMPLETION OF THE WORK INCLUDING BUT NOT LIMITED TO RELATED WORK
SMALLER MAY BE SOLID; #8 AND LARGER SHALL BE STRANDED ALUMINUM
7
SUCH AS CONNECTION OF EXISTING SYSTEMS, EXCAVATIONS AND BACK FILLING.
CONDUCTORS MAY BE ALLOWED FOR SERVICE ENTRANCE IF SPECIFICALLY APPROVED
31.- CONTRACTOR SHALL PROVIDE TEMPORARY SERVICE AND LIGHTING FOR USE OF
120
BY THE ENGINEER.
ALL TRADES AS REQUIRED FOR CONSTRUCTION AND AUTHORITIES HAVING
6.- MATERIALS: CONTRACTOR SHALL PROVIDE ALL NEW MATERIALS OF AMERICAN
1,000
JURISDICTION.
MANUFACTURE, BEARING THE UNDERWRITER'S LABORATORY (UL) LABEL AS
18. -ALL CONDUCTORS SHALL BE RUN IN CONDUIT, U.O.N.
FREEZER
APPLICABLE. MATERIALS SHALL BE NEW, SUITABLE FOR THE APPLICATION AND
120
32.- ELECTRICAL CONTRACTOR SHALL ASSURE THAT ALL FEATURES OF SERVICE
ABOVE STANDARD QUALITY NORMALLY USED FOR THE PURPOSE AS CALLED FOR ON
19.- INSTALL 3/4" EMPTY CONDUIT TO ALL TELEPHONE /DATA OUTLETS. PROVIDE PULL
COMPLY WITH THE POWER COMPANY'S REQUIREMENTS AND SHALL MAKE ALL
PLANS, SUPPLEMENTAL MATERIALS, PRODUCTS AND COMPONENTS NECESSARY TO
WIRE.
NECESSARY ARRANGEMENTS WITH POWER COMPANY FOR SERVICE. ALL EQUIPMENT
COMPLY WITH THE INTENT OF THE CONTRACT DRAWINGS AND /OR SPECIFICATIONS,
120
NOT FURNISHED AND /OR INSTALLED BY THE POWER CO. IS TO BE FURNISHED AND
BUT NOT NOTED OR SPECIFIED ON THESE SECTIONS, SHALL BE PROVIDED BY THE
20. -ALL CONDUITS SHALL BE GALVANIZED RIGID (GRC), EXCEPT AS FOLLOWS:
INSTALLED BY THE ELECTRICAL CONTRACTOR.
CONTRACTOR AS REQUIRED FOR THE COMPLETION OF THE WORK AT NO ADDITIONAL
10
COST TO THE OWNER. CONTRACTOR SHALL BE RESPONSIBLE FOR PROVISIONS AND
(A) UL LISTED PVC CONDUITS MAY BE USED UNDERGROUND OUTDOORS OR
33.- U.O.N., COORDINATE REQUIRED A.I.C. RATINGS WITH POWER COMPANY.
COORDINATION OF DELIVERY OF MATERIALS. EQUIPMENT MARRED DURING SHIPMENT OR
UNDER SLAB INSIDE THE BUILDING AS ALLOWED BY CODE. CONDUIT FITTINGS AND
EXIST
INSTALLATION SHALL BE TOUCHED UP AND REFINISHED TO FACTORY FINISH,
CEMENT SHALL BE PRODUCED BY THE SAME MANUFACTURER.
34. -WHERE MORE THAN ONE DEVICE IS INDICATED AT ANY LOCATION, THESE SHALL
REPLACED WHERE NOT ACCEPTABLE.
BE GANGED UNDER ONE COMMON COVER.
20
(B) ELECTRICAL METALIC TUBING (EMT), MAY BE USED IN OR ON WALLS OR
EXIST
7.- PERMITS AND INSURANCE: CONTRACTOR SHALL SECURE AND PAY FOR ALL
CEILINGS WHERE NOT SUBJECT TO MECHANICAL DAMAGE, CORROSIVE OR DAMP
35.- QUANTITY AND LOCATION OF ELECTRICAL, TELEPHONE /DATA & TV OUTLETS,
PERMITS, FEES, TAXES, INSPECTIONS, TESTS, FINES AND OTHER ITEMS AS REQUIRED
CONDITIONS.
LIGHTS AND LIGHT CONTROLS, SHALL BE ADJUSTED TO SUIT THE OWNER'S
FOR THE INSTALLATION OF THE COMPLETE ELECTRICAL SYSTEMS AS OUTLINED HEREIN
20
REQUIREMENTS AS PER OWNER /ARCHITECT INSTRUCTIONS. SAID ARRANGEMENTS
AND SHOWN ON PLANS, CONTRACTOR SHALL PROVIDE ALL REQUIRED INSURANCE FOR
(C) ELECTRICAL NON METALIC TUBING (ENT), MAY BE USED WHEN INSTALLED IN
SHALL NOT BE IN CONFLICT WITH APPLICABLE CODES.
PROTECTION AGAINST PUBLIC LIABILITY AND PROPERTY DAMAGE FOR THE DURATION
ACCORDANCE WITH THE REQUIREMENTS OF THE NEC ARTICLE 362 AND ONDUIT
OF THE WORK.
MANUFACTURER'S INSTRUCTIONS.
36.- ELECTRICAL CONTRACTOR SHALL VERIFY REQUIREMENTS, EXACT LOCATIONS, ,TYPE
AND ARRANGEMENT OF OUTLETS FOR ALL ELECTRICAL FIXTURES;. APPLIANCES AND
8.- EXISTING CONDITIONS: BEFORE BIDDING, THE CONTRACTOR SHALL VISIT THE JOB
(D) METAL CLAD CABLE (MC), SHALL BE LIMITED TO BRANCH CIRCUITING AND BE
EQUIPMENT, PRIOR TO INSTALLATION.
SITE AND ASCERTAIN ALL EXISTING CONDITIONS WHICH WILL AFFECT HIS WORK.
INSTALLED IN ACCORDANCE WITH THE REQUIREMENTS OF NEC ARTICLE 330 AND CABLE
20
FAILURE TO DO SO WILL NOT BE ACCEPTED AS A REASON FOR REQUESTING EXTRA
MANUFACTURER'S INSTRUCTIONS.
3i. -ALL BRANCH CIRCUITS THAT SUPPLY 125 - VOLTS, SINGLE PHASE, 15 AND 20
PAY WHERE THE EXISTING CONDITIONS RESULT IN EXTRA MATERIALS OR ANY
AMPERE OUTLETS INSTALLED IN DWELLING UNIT BEDROOMS SHALL BE PROTECTED BY
EXISTING CONDITIONS FOUND BY THE CONTRACTOR WHICH WILL ADVERSELY AFFECT
(E) NONMETALLIC CABLE (NM), (NMC) & (NMS) MAY BE USED FOR INTERIOR
AN ARC -FAULT CIRCUIT INTERRUPTER (AFCI) LISTED TO PROVIDE PROTECTION OF THE
THE WORK SHALL BE IMMEDIATELY BE BROUGHT TO THE ATTENTION OF THE
WIRING, EXPOSED OR CONCEALED IN DRY LOCATIONS, MUST NOT BE USED EMBEDDED
ENTIRE BRANCH CIRCUIT.
ARCHITECT /ENGINEER. CORRECTION OF ANY DEFECTS SHALL BE COMPLETELY WITHOUT
IN CONCRETE, MASONRY, FILL OR PLASTER, ITS USE AND INSTALLATION SHALL
16
ADDITIONAL CHARGE AND SHALL INCLUDE REPLACEMENTS OR REPAIR OF ANY OTHER
COMPLY WITH NEC ARTICLE 334.
38.- INSTALLATION OF LIGHTING FIXTURES INSIDE CLOTHES CLOSETS SHALL COMPLY
PHASE OF THE INSTALLATION WHICH MAY HAVE BEEN DAMAGED THEREBY.
EXIST
WITH THE NEC ARTICLE 410 -8.
1,000
(F) FLEXIBLE CONDUIT SHALL BE USED FOR CONNECTIONS TO VIBRATING
9.- SUBSTITUTIONS: PRODUCTS AND MATERIALS CALLED OUT BY TRADE NAME
EQUIPMENT AND RECESSED LIGHT FIXTURES, WHERE PERMITTED BY CODE. EMBEDDED
39.- PROVIDE A TYPEWRITTEN DIRECTORY FOR EACH ELECTRICAL PANEL.
AND /OR CATALOG NUMBERS ESTABLISH A STANDARD OF QUALITY, APPEARANCE,
IN CONCRETE, MASONRY, FILL OR PLASTER. IF USED OUTDOORS, IT SHALL BE
40.'-CONTRACTOR SHALL FURNISH -AS =BUILT DRAWINGS TO THE OWNER UPON
PERFORMANCE AND DIMENSION. CONTRACTORS SHALL BASE HIS PROPOSAL ON THOSE
LIQUIDTIGHT.
ITEMS AS THEY SHALL BE CONSIDERED AS A STANDARD BASIS OF BIDDING.
GENERAL RECEPTACLES
COMPLETION OF WORK AND PRIOR TO FINAL PAYMENT.
REQUESTS FOR SUBSTITUTION SHALL BE SUBMITTED IN WRITING TO THE
21.- PROVIDE FIRE RETARDANT U.L. APPROVED SEALANT ON ALL PENETRATIONS,
'ALLOY
ARCHITECT /ENGINEER, DEMONSTRATING THAT PRODUCT IS OF COMPARABLE AND BASIC
WALLS AND STRUCTURAL SLABS. IT SHALL BE THE RESPONSIBILITY OF THE
41.- OUTLET BOXES SHALL BE PRESSED STEEL IN DRY LOCATIONS, CAST WITH
DESIGN, CONSTRUCTION, STANDARDS AND WARRANTIES, DIMENSIONS TO FIT WITHOUT
ELECTRICAL CONTRACTOR TO VERIFY, PRIOR TO SUBMITTING BID, THE LOCATIONS OF
THREADED' HUBS-IN WET /DAMP LOCATIONS AND SPECIAL ENCLOSURES AS REQUIRED
CHANGE, AND DOES NOT CAUSE EXTRA WORK TO OTHER TRADES. CONTRACTOR
ALL SUCH FIRE RATED PARTITIONS, WALLS, AND STRUCTURAL SLABS.
FOR OTHER CLASSIFIED AREASiAND'SHALL CONFORM TO NEMA STANDARDS. PLASTIC
SHALL BE RESPONSIBLE FOR PROVIDING EQUALITY OF SUBSTITUTION:
1,200
BOXES MAY BE USED WHERE PERMITTED UNDER APPLICABLE CODES AND ORDINANCES.
ARCHITECT /ENGINEER WILL, UNDER NO CIRCUMSTANCES, BE REQUIRED TO PROVE SUCH
22,- INTERFERENCE: THE CONTRACTOR SHALL COORDINATE HIS WORK WITH OTHER
GENERAL RECEPTACLES
ITEM IS OR IS NOT OF EQUAL QUALITY TO THE SPECIFIED ITEM. ARCHITECT /ENGINEER
TRADES SO THAT INTERFERENCE WITH EXISTING CONDITIONS, CONDUITS, PIPING,
42 -ALL DISCONNECT SWITCHES SHALL BE SIZED BY NEC REQUIREMENTS TO
EXPENSES INCURRED DUE TO CONTRACTOR'S REQUESTED REVISIONS OR
EQUIPMENT, ARCHITECTURAL AND STRUCTURAL MEMBERS BE AVOIDED.
ACCOMODATE THE EQUIPMENT SERVED, INCLUDING REJECTION CLIPS AND FUSES, WHEN
SUBSTITUTIONS SHALL BE PAID BY THE CONTRACTOR.
GENERAL RECEPTACLES
APPLICABLE. SWITCHES SHALL BE HP RATED, QUICK -MAKE, QUICK - BREAK, IN NEMA 1
23.- PLANS: DRAWINGS ARE BASICALLY DIAGRAMS INTENDED TO DEPICT
ENCLOSURES FOR INDOOR AND NEMA 3R FOR OUTDOOR.
10.- MOTORS STARTERS SHALL BE MANUAL OR MAGNETIC AS INDICATED OR REQUIRED,
APPROXIMATELY EQUIPMENT LOCATIONS AND ARRANGEMENTS, NOT TO SHOW EVERY
1,400
WITH OVERLOAD RELAYS OR FUSES IN EACH HOT LEG.
MINOR DETAIL. PLANS SHALL NOT BE SCALED TO DETERMINE EXACT LOCATION AND
43.= VERIFY SLAB STRUCTURAL DESIGN WITH STRUCTURAL ENGINEER.
GENERAL RECEPTACLES
DIMENSIONS.
120
1- CLOSE OVERHANG SOFFIT VENTS WITHIN 10' OF GENERATOR
EXAUST TERMINATION POINT AND RE -OPEN THE SAME NUMBER OF
CLOSED /SEALED VENTS AT OTHER OVERHANG LOCATION
2- GENERATOR EXHAUST TERMINATION POINT SHALL NOT BE
LOCATED WITHIN 10' OF ANY BUILDING OPENING (WINDOW, DOOR
WALL /ROOF VENTS, WALL A/C UNITS, ETC.)
GENERATOR SCHEDULE
MANUFACTURE
ARMSTRONG
MODEL #
AGM60Si
RATED POWER
60 kW
VOLTAGNSINGLE PHASE)
120/240
Amps (la 120/240
225 NG
ENGINE /ALTERNATOR(RPM)
1,800
MAIN LINE CIRCUIT BREAKER
400 Am
SOUND OUTPUT AT FULL LOAO(23 ft)
72 dB(A)
DIMENSIONS (L "xW "xH ")
97 x 37 x 57.6
WEIGHT 1,207 Kg
GENERATOR NOTES
1.- GENERATOR MUST BE SET AT, OR ABOVE THE MINIMUM FEMA FLOOD ELEVATION.
2. -A PERMANENT SIGN SHALL BE PLACED AT THE ELECTRICAL SERVICE EQUIPMENT THAT INDICATES THE
LOCATION OF ON -SITE OPTIONAL STANDBY POWER SOURCES.
3.- PROVIDE RELAY TO PREVENT A/C HEATER FUNCTION DURING GENERATOR USE.
PHASE: 10
VOLTAGE: 120/240 v
PANEL AMPS: 400 Amps
EXISTING PANEL •'A" TYPE: SQD -QO /FLUSH
MAIN BREAKER: 400
(BRANCH BREAKERS TYPE GP, 10KAIC)
GFI= Ground Fault Interrupter NCL= Non - concurrent load REC= Receptacle Ckt Lts= Lighting Ckt ST= Breaker with shunt trip T= Via timer
IS= Isolated ground Ckt C= Via contactor SWO= On -Off Switching Duty /or HID= Rated Breaker,as per NEC 240 -83(0) LV= Via low voltage transformer
HACK= Breaker suitable for the protection of heating,A /C and refrigeration equipment AFCI= Breaker suitable for arc -fault Ckt. protection Interrupter bkr.
Ckt
No
USE
PANEL
SPEC
VOLT
BKR
AMP
WIRE
AWG
COND
SIZE
VA
PHASE
Ckt
No.
USE
SPEC
VOLT
BKR
AMP
WIRE
AWG
COND
SIZE
VA
A
C
1
ROOF TOP UNIT
240
80
EXIST
EXIST
16,000
•
2
X -RAY
240
80
EXIST
EXIST
16,000
3
11
u
4
11
u
5
ROOF RECEPTACLES
GFI
120
20
EXIST
EXIST
200
6
REFRIGERATOR
120
20
EXIST
EXIST
1,000
7
OUTDOOR LIGHTS
120
20
EXIST
EXIST
1,000
•
8
FREEZER
120
20
EXIST
EXIST
1,000.
9
ULTRASOUND #5
120
20
EXIST
EXIST
1,200
•
10
AUTOCLAVE #1
120
20
EXIST
EXIST
1,400
11
ULTRASOUND #20
120
20
EXIST
EXIST
2,000
12
AUTOCLAVE #2
120
20
EXIST
EXIST
1,400
13
•
1
14
GENERAL RECEPTACLES
120
20
EXIST
EXIST
900
15
•
16
GENERAL RECEPTACLES
120
20
EXIST
EXIST
1,000
17
•
18
GENERAL RECEPTACLES
120
20
EXIST
EXIST
1,600
19
GENERAL RECEPTACLES
120
20
EXIST
EXIST
1,200
•
20
GENERAL RECEPTACLES
120
20
EXIST
EXIST
1,600
21
GENERAL RECEPTACLES
120
20
EXIST
EXIST
1,400
•
22
GENERAL RECEPTACLES
120
20
EXIST
EXIST
1,600
23
GENERAL RECEPTACLES
120
20
EXIST
EXIST
500
• 1
24
GENERAL RECEPTACLES
120
20
EXIST
EXIST
1,400
25
GENERAL RECEPTACLES
120
20
EXIST
EXIST
2,000
•
1
26
GENERAL RECEPTACLES
120
20
EXIST
EXIST
1,200
27
GENERAL LIGHTS
120
20
EXIST
EXIST
800
•
28
GENERAL RECEPTACLES
120
20
EXIST
EXIST
800
29
GENERAL LIGHTS
120
20
EXIST
EXIST
1,000
30
GENERAL RECEPTACLES
120
20
EXIST
EXIST
1,200
31
GENERAL LIGHTS
120
20
EXIST
EXIST
1,000
•
32
GENERAL RECEPTACLES
120
20
EXIST
EXIST
1,000
33
GENERAL LIGHTS
120
20
EXIST
EXIST
800
•
34
351
•
36
37
1 J
a
38
39
1
1
•
40
41
* SEE LOAD CALCULATION
** VERIFY NAME PLATE
•
Load Calculation for Panel A:
Equipment Load = 62,100 va
25% Continuos Lights = 625 va
25% Largest Motor = 900 va
-50% Rectp demand over 10kW= -3,700
Total VA = 59,925 va
Panel Load = 59,925/240= 250 Amps
42
GENERATOR CALCULATION:
(A /C with out heater, see generator notes.)
Equipment Load = 52,100 va
25% Continuos Lights = 625 va
25% Largest Motor = 900 va
-50% Rectp demand over 10kW= -31700
Total VA = 49,925 va
Panel Load = 49,925/240= 208 Amps
#8 GND IN
1/2" PVC
CONDUIT
v/
\`
WEATHERPROOF
HOUSING �y
NEW (3) #500 CU & (03 GND
CU IN 2 -1/2" THWN (CU)
ANCHORING
"RED H
(S
` WIRE MESH, ATTACH 8" C IN EA. DIRECTION ON 12"
TO #5 RIGID BAR 6 MIL.
\ WELL COMPACTED FILL.
\ al
'�I I IIIr
12" X 18" CONC. FOOTING W/
(1) #5 CONTINUOUS
� \
� \app
y °qF
DETAIL "A"
IQ lz11- 1 PAD ANCHORING
�_j _j _j ( MIN. 3/8 "x2" TAP CONS. OR EQUAL)
EXISTING I I
EXISTING J _ A.T.S. I J NAT GAS \
METER /MAIN _j -j-I -I ETER `
JJJJJJ
P_jJJJJJ .:..
JJJJJJ `�
JJJJJJ
JJJJ
_j _j \
GENERATOR
CONC.POLE \
�L SITE PLAN '
. N 40
soly
PROPERTY LINE 168.91' P,???, 0,4f X.
EXISTING 60A PLUG EXISTING (3) #500 CU IN 2 -1/2"
L J FOR PORTABLE THWN (CU) TO "FP &L" 10066:_
GENERATOR. (CONTRACTOR TO VERIFY)
I- - - EXISTING SERVICE TO
J "FP &L" POLE
co F -T" r M _
IC1TY OF SOUTH MIAMI
I EXISTING � --� � � � _ ( � -i I I �' -�' I
PANEL "A" ' I EXISTING I ( EXISTING EXISTING EXISTING _ BUILDING DEPT.
400A MCB, ATS MCB I METER I I METER I ELECTRICAL SECTION
10,120/240V ( I 400A, 10, I 1400A, 10 I 400A,10 I I 150A, 10
42 SPACE 120/240V 120/240V 120/240V
120/240V
L J L - L WP 7 J W W
P I P APPROVED
BY.
EXISTING (3) #500 CU & b- EXISTING (1) #1/0 CU IN
(1) #3 GND CU IN 2 -1/2" I 3/4 THWN (CU) I DAM c
THWN (CU) (CONTRACTOR TO
(CONTRACTOR TO VERIFY) I VERIFY) -TO C.W.P
- - - - CITY OF SOUTH MIA
BUILDING DEPT.
STRUCTURAL SECTION
EXISTING ��� �;PPROVED BY:
GROUNDING RODS
CL4TE 1111 f
ELECTRICAL RISER DIAGRAM
N.T.S
C.A. # 9360
THE ENGINEERING
CONSULTING GROUP, P.A.
MECHANICAL, ELECTRICAL, PLUMBING, 8
PRE PROTECTION ENGINEERING DESIGN
4937 S.W. 74th CL
Miami, Florida 33155
Tel: (305) 663 -9191
Fax: (305)663 -6768
tecgroup@tecgroup- pa.com
Seal /.
o �
�s ....
ERNESTi0:RODRIGUEZ
MECHANICAL ENGINEER
PE #:58155
L �
�O 0
L >- LL
0
ICU < Q
N z W 2
I-
Vr W Z n
c�WU
-L > J Q
W
WQ� _
�W W W
X
C: o
a) :D _
0) O
E O 0
m E W
Z
m W 0)
o M
EL (U
WRITTEN DIMENSIONS ON THIS DRAWING
SHALL HAVE PRECEDENCE OVER SCALED
DIMENSIONS. CONTRACTOR SHALL VERIFY
AND BE RESPONSIBLE FOR ALL
DIMENSIONS AND CONDITIONS ON THE
JOB. THE DESIGN PROFESSIONAL MUST BE
NOTIFIED IN WRITING OF ANY VARIATION
FROM THE DIMENSIONS.
PLANS ARE PROTECTED UNDER THE
COPYRIGHT LAWS OF FLORIDA:
ALL RIGHTS RESERVED
ALL IDEAS DESIGN ARRANGEMENTS AND
PLANS INDICATED OR REPRESENTED BY
THIS DRAWINGS ARE OWNED BY AND THE
PROPERTY OF THE DESIGN PROFESSIONAL
AND WERE CREATED EVOLVED AND
DEVELOPED FOR USE ON AND IN
CONNECTION WITH THE SPECIFIED
PROJECT. ANY CHANGES TO THESE PLANS
WITHOUT THE WRITTEN APPROVAL OF THE
DESIGN PROFESSIONAL OR ANY
CONSTRUCTION EXECUTED FROM THESE
PLANS WITHOUT EXPRESSED APPROVAL
OF THE DESIGN PROFESSIONAL SHALL
AUTOMATICALLY RENDER THE DESIGN
PROFESSIONAL HARMLESS TO ANY
LIABILITY CLAIMS, SUIT OR LITIGATION BY
ANY INTERESTED PARTIES OF THE
PROJECT. NO PART THEREOF OF THESE
PLANS SHALL BE COPIED OR REPRODUCED
BY ANY MEANS, OR USED IN CONNECTION
WITH ANY WORK OTHER THAN FOR THE
SPECIFIC PROJECT FOR WHICH THEY HAVE
BEEN PREPARED WITHOUT WRITTEN
CONSENT OF THE DESIGN PROFESSIONAL
Revisions:
1 11/17/08 BLD OPT COMMS
ISSUE DATE Sept. 19, 2008
DWN E.R. APPRV E.R.
Phase:
CONSTRUCTION
DOCUMENTS
Scale:
AS NOTED
S
f Dwg Title:
ELECTRICAL GENERATOR
SITE PLAN, CALLS. & SCHED
S
Sheet No.:
r
E_1
N.
GENERATOR - ENGINE CONTROL
PANEL
ANCHORING
"RED H
(S
` WIRE MESH, ATTACH 8" C IN EA. DIRECTION ON 12"
TO #5 RIGID BAR 6 MIL.
\ WELL COMPACTED FILL.
\ al
'�I I IIIr
12" X 18" CONC. FOOTING W/
(1) #5 CONTINUOUS
� \
� \app
y °qF
DETAIL "A"
IQ lz11- 1 PAD ANCHORING
�_j _j _j ( MIN. 3/8 "x2" TAP CONS. OR EQUAL)
EXISTING I I
EXISTING J _ A.T.S. I J NAT GAS \
METER /MAIN _j -j-I -I ETER `
JJJJJJ
P_jJJJJJ .:..
JJJJJJ `�
JJJJJJ
JJJJ
_j _j \
GENERATOR
CONC.POLE \
�L SITE PLAN '
. N 40
soly
PROPERTY LINE 168.91' P,???, 0,4f X.
EXISTING 60A PLUG EXISTING (3) #500 CU IN 2 -1/2"
L J FOR PORTABLE THWN (CU) TO "FP &L" 10066:_
GENERATOR. (CONTRACTOR TO VERIFY)
I- - - EXISTING SERVICE TO
J "FP &L" POLE
co F -T" r M _
IC1TY OF SOUTH MIAMI
I EXISTING � --� � � � _ ( � -i I I �' -�' I
PANEL "A" ' I EXISTING I ( EXISTING EXISTING EXISTING _ BUILDING DEPT.
400A MCB, ATS MCB I METER I I METER I ELECTRICAL SECTION
10,120/240V ( I 400A, 10, I 1400A, 10 I 400A,10 I I 150A, 10
42 SPACE 120/240V 120/240V 120/240V
120/240V
L J L - L WP 7 J W W
P I P APPROVED
BY.
EXISTING (3) #500 CU & b- EXISTING (1) #1/0 CU IN
(1) #3 GND CU IN 2 -1/2" I 3/4 THWN (CU) I DAM c
THWN (CU) (CONTRACTOR TO
(CONTRACTOR TO VERIFY) I VERIFY) -TO C.W.P
- - - - CITY OF SOUTH MIA
BUILDING DEPT.
STRUCTURAL SECTION
EXISTING ��� �;PPROVED BY:
GROUNDING RODS
CL4TE 1111 f
ELECTRICAL RISER DIAGRAM
N.T.S
C.A. # 9360
THE ENGINEERING
CONSULTING GROUP, P.A.
MECHANICAL, ELECTRICAL, PLUMBING, 8
PRE PROTECTION ENGINEERING DESIGN
4937 S.W. 74th CL
Miami, Florida 33155
Tel: (305) 663 -9191
Fax: (305)663 -6768
tecgroup@tecgroup- pa.com
Seal /.
o �
�s ....
ERNESTi0:RODRIGUEZ
MECHANICAL ENGINEER
PE #:58155
L �
�O 0
L >- LL
0
ICU < Q
N z W 2
I-
Vr W Z n
c�WU
-L > J Q
W
WQ� _
�W W W
X
C: o
a) :D _
0) O
E O 0
m E W
Z
m W 0)
o M
EL (U
WRITTEN DIMENSIONS ON THIS DRAWING
SHALL HAVE PRECEDENCE OVER SCALED
DIMENSIONS. CONTRACTOR SHALL VERIFY
AND BE RESPONSIBLE FOR ALL
DIMENSIONS AND CONDITIONS ON THE
JOB. THE DESIGN PROFESSIONAL MUST BE
NOTIFIED IN WRITING OF ANY VARIATION
FROM THE DIMENSIONS.
PLANS ARE PROTECTED UNDER THE
COPYRIGHT LAWS OF FLORIDA:
ALL RIGHTS RESERVED
ALL IDEAS DESIGN ARRANGEMENTS AND
PLANS INDICATED OR REPRESENTED BY
THIS DRAWINGS ARE OWNED BY AND THE
PROPERTY OF THE DESIGN PROFESSIONAL
AND WERE CREATED EVOLVED AND
DEVELOPED FOR USE ON AND IN
CONNECTION WITH THE SPECIFIED
PROJECT. ANY CHANGES TO THESE PLANS
WITHOUT THE WRITTEN APPROVAL OF THE
DESIGN PROFESSIONAL OR ANY
CONSTRUCTION EXECUTED FROM THESE
PLANS WITHOUT EXPRESSED APPROVAL
OF THE DESIGN PROFESSIONAL SHALL
AUTOMATICALLY RENDER THE DESIGN
PROFESSIONAL HARMLESS TO ANY
LIABILITY CLAIMS, SUIT OR LITIGATION BY
ANY INTERESTED PARTIES OF THE
PROJECT. NO PART THEREOF OF THESE
PLANS SHALL BE COPIED OR REPRODUCED
BY ANY MEANS, OR USED IN CONNECTION
WITH ANY WORK OTHER THAN FOR THE
SPECIFIC PROJECT FOR WHICH THEY HAVE
BEEN PREPARED WITHOUT WRITTEN
CONSENT OF THE DESIGN PROFESSIONAL
Revisions:
1 11/17/08 BLD OPT COMMS
ISSUE DATE Sept. 19, 2008
DWN E.R. APPRV E.R.
Phase:
CONSTRUCTION
DOCUMENTS
Scale:
AS NOTED
S
f Dwg Title:
ELECTRICAL GENERATOR
SITE PLAN, CALLS. & SCHED
S
Sheet No.:
r
E_1