11-1169R (2)-002A/C DUCT SMOKE DETECTOR NOTES 1. A/C UNITS SHALL HAVE U.L. LISTED FACTORY INSTALLED SMOKE DETECTOR IN THE SUPPLY AIR SECTION. SMOKE DETECTORS SHALL BE INNOVAIR MODEL# DHIOOACDCI OR EQUAL. 2. A/C DUCT SMOKE DETECTOR SHALL NAVE AN AUDIBLE ALARM WITH VISIBLE SIGNAL TROUBLE LIGHT AND SHUT -OFF UNIT AUTOMATICALLY UPON SENSING SMOKE. 3. SMOKE DETECTORS SHALL BE INSTALLED PER SMC AND NFPA. FAN SCHEDULE A/H UNIT SCHEDULE UNIT NUMBER EF -I EF -2 _ -EF -3 _ EQUIP. OR AREA SERVED RESTROOMS EMPLOYEE LOUNGE JANITOR'S PLAAISBA - - -- --------------- - - - -- - -- -- - - - -- - - - - -- - TOTAL COOLING CAPACITY BTUH _ _ROOM - MANUFACTURER GREENHECK _ _ G_REENNECK _ _GREENHECK _ MODEL NUMBER G -075 -E G- 080 -D- _ G-060-D.____ CFM 200 - - -- 375 100 - -- STATIC_ PRESSURE - - - 0.125" - 0.25'_ -_ 0.25 ------ __ FAN H.P. - -- -- - - -- DRIVE RPM -- --------- - - - - -- -- - I /80 _ DIRECT_ _ _ -_1/60 -- - -- DIRECT - - -15_50 DIRECT - - -- 105_0 - - - - -- -- 15_50 _ _ 12.0/1/60_ - - -- __12_0/1/60 ELECTRICAL SERVICE 120/1/60 _ ROOF OPENING REQUIRED 12 "xl2" -- _ 14 "x14" - --- - - - - -- _ - 12 "A2' - - - -- BONES---------- -- --- - - - - -- --- - - -2.8 7.2 - 3.7 -- - - - -- WEIGHT - LBS (W /CURB) - - -- 26 - - - -- 26 26 NOTES: I. ELECTRICAL CONTRACTOR SHALL WIRE EF -I TO BE ON CONTINUOUS DURING THE BANK'S HOURS OF OPERATION. SEE COND. UNIT_ 2. ELECTRICAL CONTRACTOR SHALL SUPPLY ON /OFF SWITCH FOR EF -2 (EMPLOYEE LOUNGE). SEE COND. UNIT 3. ELECTRICAL CONTRACTOR SHALL SUPPLY ON /OFF SWITCH FOR EF -3 (JANITOR'S ROOM). MINI - SPLIT. AIR COOLED MINI SPLIT A/H UNIT SCHEDULE UNIT NUMBER MINI SPLIT -I - - -- MINI SPLIT -2 ------- - - - - -- - - - - - -- - MITSUBISHI ----- --- - - - - -- - - - - -- - - - - - -- -- - - - - -- - - MANUFACTURER - MITSUBISHI --------------- --- MODEL NUMBER PLAAISBA - - - - -- - - -- - - -- PLAAISBA - - -- --------------- - - - -- - -- -- - - - -- - - - - -- - TOTAL COOLING CAPACITY BTUH - - -- -- 181000 181000 NOMINAL TONNAGE- - -- - 1.5 - - -- - - -- ---- - - - - -- - 1.5 - - - -- - - - -- - - - - -- - -- -- - - - - -- ---- - - - -- - -- - - - -- -- - -- -- CFM SUPPLY AIR 420 - 500 420 - 500 CFM OUTSIDE AIR - -- REFRIGERATION LINE SIZE (VAPOR) (O.D.) EXTERNAL STATIC PRESSURE "N.G." --- - -- S.E.E.R. 14.20 14.20 FAN MOTOR FLA 0.51 0.51 EVAP FAN MOTOR HP - -- - KW (AUXILIARY ELECTRIC - - NEAT) - - -- -- - -- - - - -- - - - -- NONE ----- - - - - -- -- - - - - -- NONE -- - -- --- - - - - -- - -- -- - - UNIT WEIGHT (LB5.) - - - -- - 49 _ - - - - - -- -._ 4q - - - -- - - REFRIGERANT LINE 51ZE (VAPOR) - _ 1/2" _ 5/8" -LINE - - - - - -- - - - -- - REFRIGERANT LINE SIZE (LIQUID) -- - - 114" - - -- -- - -- _ _114" - - -- - - -- - - -- - - -- - - - - - - - -- - CONDENSATE DRAIN (FPT) -- R -410A - - -- -- - - - - -- - - -- - R -410A -- - ----- - - - - -- -- - - -- - -- -- -- - - - - -- - - -- ------------ - - - - ELECTRICAL SERVICE---- -- - -- - LOCATION - - - - - - -- -- - - - -- - - - - -- -- - -- ---- - - - - -- - - MINIMUM CIRCUIT AMPS SEE COND. UNIT SEE COND. UNIT_ SEE COND. UNIT --_ -- - MAXIMUM FUSE AMPS SEE COND. UNIT NOTE5: I. MECHANICAL CONTRACTOR SHALL PROVIDE CONDENSATE PUMP FOR EACH MINI - SPLIT. 2. INSULATED CONDENSATE LINES BY PLUMBING CONTRACTOR. SEE PLUMBING DRAWINGS. AIR COOLED MINI SPLIT CONDENSING UNITS SCHEDULE UNIT NUMBER - - -- MINI SPLIT -I ----- - - - -- ---- ---MINI 5PLIT -2 -- ---- ^UFACTURER -------- - - - - -- - - - -- - - - -- -- - - - MAN - MITSUBISHI - -- - - - - - -- -- MITSUBISHI --- - -- ------- -- - - - - -- -- -- - -- - - - -- - - - - -- MODEL NUMBER PUYAISNHA PUYAIS A --------------------------- - TOTAL COOLING CAPACITY - - - -- - -- -- - - - - -- 375 - -- - - -- - - - - -- - - -- - - - -- - - - -- --- - - - - -- - -- - ------- - NOMINAL TONNAGE - -- 1.5 ------------- - - - - -- --------- - - - - -- ---------- - - - - -- ---------------------- - - - 5.E.E.R. - -- - -- - 14.20 -- ------------ - - - - -- --- - - - - -- 14.20 -------------- - - - - -- - - - - - -- - - -- - -- - - -- - - -- - - -- -- -- - - - - - -- UNIT WEIGHT (LB5.) 97 q REFRIGERATION LINE SIZE (VAPOR) (O.D.) 1/2 REFRIGERATION LINE SIZE (LIQUID) (O.D.) - _ 114' - _ _ -114 "- _ ------------ - - - - -- --------------- - -- ELECTRICAL SERVICE E 208/1/60 208/1/60 MINIMUM CIRCUIT AMPS - 13.0 13.0 - - - -- - AMPS, - - - 18.0. - -- -- - 18 -0 -- - _MAXIMU_M_FUSE _- _ AMBIENT TEMP. (DEGREES FAHRENHEIT ) ql . - -- ql -- - REFRIGERANT (R) - - -- -- - R -410A -- -- -- - - - - - - - -- - - R -410A - - - - - -- ----- - -- - -- - - - - --------- - - - - -- -------- - - CONPRE550R MOTOR LRA (AMPS) - -- 14 - - -- - - - - - - -- -- -- -- 14 - -- ---------------- - - -- -- - - - - -- -- -- CO_MPRES50R RLA 12 12 FAN MOTOR _MFLA _OTOR (AMPS) - -_ - - _ 0.35 - -_ _ _ _ 0.35 - -- LOCATION - - - - - - -- -- - - - -- - - - - -- -- ROOF ROOF NOTE: A.S.H.R.A.E. 62.1 -2007 TABLE 6 -1 REQUIRES OUTSIDE AIR FOR INDOOR AIR QUALITY: OFFICE SPACE / RECEPTION AREA / LOBBIES / TELEPHONE 4 DATA ENTRY - 5.0 CFM PER PERSON CALCULATIONS: RTU -I (ZONE -1) - 12 PEOPLE x 5.0 CFM = 60 CFM RTU -2 (ZONE -2) - 14 PEOPLE x 5.0 CFM = 70 CFN TOTAL OUTSIDE AIR REQUIRED (26 TOTAL PEOPLE) = 130 CFM OUTSIDE AIR PROVIDED THROUGH A/C EQUIPMENT: RTU -I (ZONE -1) = 300 CFN RTU -2 (ZONE -2) = 400 CFN TOTAL OUTSIDE AIR PROVIDED (EQUALS = 2q.g2 CFN PER PERSON) = 700 CFN TOTAL DESIGN OUTDOOR AIR CONPLIES WITH REQUIREMENTS OF A.S.H.R.A.E. 62.1 -2007 TABLE 6 -1 -:�- :�r>r•' - -- �- -�}► -- "'•raerr-- ,cw�•�e- ,-r•.e - *.• u. �, rrt -1r- ":srr..- w*_- ?�sce1'- "- -'-s'!Dr"�'!r"'"'" ALL RECTANGULAR DUCT SIZES SHOWN ON DRAWINGS ARE ACTUAL SIZE, 1 -1/2" THICK R -6 INTERNAL INSULATION HAS BEEN ACCOUNTED FOR. EQUIVALENT SIZES MAY BE USED TO INSURE PROPER INSTALLATION Is- u =� FE. w • I I I r I I I "I :111 I -I •: / r •I • I • • : •: I I• I I I' r• r 11111111111111111111111111111111111111111111111�■ '�' '�' �- '� : :: v pm _ ��JIIIIIIIIIIIIIIIC�'� �. ,� • >i �_ ■I� II■ _ ���i�uiuuunNnuiu�iiiuuuu�niiiNiNUi�rl�, :�a ,,,e.� �i °� w� taw ® - WdV ,.;.n, = w 13"W UP ffi ❖: �w R EWA ii�i� ®■ 1 - oil �•�•�•�•i i �•�••�••••••�••�•�• '•_ -__ " .mss -�•��� _� Yom■ . III ■ ■ • • D ENTRY ► � jai. a I u • -_ ■ Ste,_ mil► �� _ ,�ouuuuuuulIl11k IPA 1=3 �LP I _� ■�� �` - o� ° =i I I iii =, = ,��� � � - �'-- -- - • -cam 1 E14 1-1111-11 FE_ IN PEN We Vii% ■_ - -==�j -��` ,'� __ O . , ��� �G j I . s-+ L1 I , 0 111111 1111111111- - �IIII ►-�i� 11 1 1 I 11 r1 1 11 I 11 =• p �• _:I • 11 � ®� ■ dlle�l■■ I1% ��l �nui�nili�lli�ili�� liiililnnni�i��lt� � �1 ,•�1 � 111 ,® �` �!'� ��!� M!' - s�l��'�■i■i --�r �. .�__ � � ��� -•�� _ ��i���l�ii� s ®�■�■v�t' ii ■■911 II {�l�l{ . ,I ® ®il ■■ i� ..1 �iioo�i��iil�Niia�iii��in�iiiii�iil�iiiiiiN�iii�� . •- 11111111 ' 111111111111111` /11111111111111111111111111 �IIIIIIIIIIIIII�IIIililillllllllllll 111111111111111���I 11111111111111111111111 1111111 �1■!• -�:'I REFRIGERANT LINES F OR I• - INNOVAIR MODEL r DUCT 5NCKE .-I VE CEILING-UP NECPWCAL CONTRACTOR DETECTOR REMOTE -I r THRU G005ENECK ON ROOF. FIELD VERIFY VAULT r THIS LOCATION. DUCT SMOKE DETECTORS OP ALL A/C UNIT FANS TRANSITION CONNECTION -I ONE UNIT SENSING SMOKE AND CAUSE A V151BLE AND AUDIBLE • NORMALLY OCCUPIED AREA AND INDICATE TROUBLE - RUN DUCT IN OPEN SPACE AT END OF BAR JOIST V151BLY OR AUDIBLY PER NFPA qOA:6.4.4.3. ALSO SEE SMOKE DETECTOR 1 1' IIIAI I NOT ON cam DRIVE � �RU HVAC FLOOR PLAN BUILDING AIR BALANCE SYMBOL ------------ A UNIT NUMBER -- - -- - - - - -- RTU - 1 RETURN AIR --------- - - - - -- 2700 OUTSIDE AIR -------------- - - - - -- +300 - - - - - -- EXHAUST AIR ------------------- - - - - -- ---------- - - - - -- MAKE -UP AIR ----- - - - - -- - - - - - -- - -- ----- - - - - -- - -- - -- RESULTING - - PRESSURE - -- ----- -- - - -- -- +300 - - - - - -- -- -- +400 -- - - -- - - - - -- - - - - -- RTU -2 - - - - - -- - -- 2600 - - +400 ------- - - - - -- - - - -- - -- -- - - - - -- 375 - -- - - -- _ EF -I - - - -- - -- -------- - - - - -- _ _ - -- -- EF-2 ---- - EF -3 - - - - -- - - - �� -- - - -- - - -- TOTALS: 700 CFN -675 CFM +700 CFN BUILDING POSITIVE PRESSURE: +25 CFM ALL EXHAUST FAN OPERATING ( +425 CFM, EF -2 EMPLOYEE LOUNGE FAN OFF) NOTES: I. THE AIR BALANCE FOR THIS BUILDING COMPLIES WITH THE REQUIREMENTS OF THE 2007 FLORIDA ENERGY CODES. 2. RESTROOM EXHAUST IS BASED ON MINIMUM 50 CFM PER WATER CLOSET OR URINAL PER 2007 FBCM TABLE 403.3. ----------- D -- E - - - -- F ------------ G DIFFUSER SCHEDULE SYMBOL ------------ A TYPE MODEL # AND I_._D.______ _ LAY -IN OR FRAME - -- SIZE - - - - - -- LAY -IN _DUCT ATTACHMENT NECK SIZE ------ - - - - -- CONN. DUCT - - - - -- -- - - - 1200 12'0 1010 --- - - - - -- --- - - - - -- -- _ 1010 - - - 10 "� _ - - - -- S ----------------- - - - - -- 8 -- - - - - -- --- - - - - -- - FINISH - - - - - -- WHITE WHITE WHITE -- - - - - - -- WHITE - - WHITE QTY. - -- -- - - I 7 - - - - - -- -- - - --- 2 - -- - - - - - -- I ----- - - - - -- MANUFACTURE # - - - - -- - - TDC -AA -3 S I - ZE - - - -- 15 "xl5' DIRECTION - - - - -- -- - SUPPLY I- WAY 15 "x15" 15 "x15" 15NI5" -- -- - - - - -- B C SUPPLY SUPPLY TDC -AA -3 15 "xl5' 4- WAY LAY -IN TDC -AA -3 IVA5' 4 -WAY - - - - -- LAY -IN ----- - - - - -- ----------- D -- E - - - -- F ------------ G - - SUPPLY - -- - - - -- TDC -AA -3 - - - -- 12 "AV -------- - - 4 -WAY _ _ - LAY -IN- - - - 12 "xl2" _ 12'xI2" _ -- SUPPLY - - -- TDC -AA -3 - -- 12 "A2' C LAY -IN - SUPPLY - - TDC -AA -3 - - -- 12 "xl2' - - -3-WAY- 4 -WAY -- - - - - - -- - -- _ LAY -IN - - - -- -- 12 "x12" - - - -- ----- - - - - -- 12 "x12" - - - -- - - - -- WHITE ------- - - - - -- WHITE - -- - - - - -- - -- - - - - - -- - - - - - -- TDC -AA -3 - 12 "x I2' 3- WAY - -- LAY -IN -- - - - - -- - - -- _SUPPLY SUPPLY - - - - -- - -- TDC -AA -3 -- -- q"xq' -- - - - -- 4- WAY _ -- -- LAY -IN _ q "xq" _ __ _ - -- 6 " "� -- -- - -- -- 6 "�- 16 10 144 --WHITE -- WHITE -- WHITE WHITE WHITE--- W_ ITE_ WHITE - 1 - -- ----- 2____ - - -I I 6 _ - _2 - - - -- -- - -- - -- - - -- J K SUPPLY - - - - -- SUPPLY R.T.E. -- -- TDC- AA- 3 - - - -- --- glxq" 3 -WAY - -- LAY -IN - - - -- - q "xq, - - -q "xq" - 22 "x22" - - ---- - -- AA- 3_______ -- n -- q x9 - -- _ CORNER - LAY -IN ------ _____ _TDC- 50 -FF -3 24 'x24' REMOVABLE CORE LAY -IN ------- L ------------- M - -- N - - - - - - -- R.T.E. -- - - - - -- R.T.E. - - - - -- 50 -FF -3 24 "x24" REMOVABLE CORE REMOVABLE CORE LAY -IN 22 "x22" 22_ "x22" - -- 22 "x22" - - -- - --- - - - - --- 50 -FF -3 -- 24 "x24" _ - LAY -IN - 12"0 -- - - - 1010 - - - - - -- -- R.T.E.- - -- 50 -FF -3 24 "x24" REMOVABLE CORE _ ___ LAY -IN - - 0 -- R.T.E._ - - - -- 50 -FF -3 - - -- 24 "x24" -- REMOVABLE CORE LAY -IN - -- _ 22 "x2_2 "_ 22 "x22" - -- 10"x10" 8 "m___ _ - - - -- 600 - - 6110 __WHITE WHITE WHITE I - - -- 3 -m I -__- P - -- _- R.T.E. R.T.E. -- 50 -FF -3 - -- - 24 "x24" REMOVABLE CORE LAY -IN Q 50 -FF -I 10 "x10 SIDE EXHAUST 10 -1/4 "x10 -1/4" NOTES: 1. DIFFUSERS SHALL BE TITUS OR APPROVED EQUAL. 2. ALL FRAMING REQUIRED FOR DIFFUSER INSTALLATION SHALL BE BY GENERAL CONTRACTOR. 3. OPPOSED BLADE DAMPER SHALL BE INSTALLED AT EACH DIFFUSER. 4. TYPE R.T.E. = RETURN /TRANSFER/EXHAU5T 5. DIFFUSER 'A' SHALL HAVE ADJUSTABLE BLADES FOR AIR FLOW TO ENTRANCE. e•_ .,..��,.. , . SCALE: 1/4" = V -0" PACKAGE A/C UNIT SCHEDULE (R-410A REFRIGERANT) UNIT NUMBER RTU -I RTU -2 --------------- - - - - -- ------------------ - - - - -- ------ - - - - -- - - - -- -- - -- - - - - -- - - -- - - - - -- ------- - - - - -- - - - -- - -- LOCATION ROOF ROOF QUANTITY REQUIRED - - - -- -- -- - - - - - - -- AREA SERVED ZONE -I ZONE -2 --------------- - - - - -- ------ - - - - -- --------------- - - - - -- - -- - - - - -- - - - - - -- -- -- - - - -- - -------- - - - - -- - -- ------------ - - - - -- -- - MANUFAGTURER - - - - _ _ _ -- _ -- - -- - - -- - -- -- -- - -- -- LENNOX -- LENNOX MODEL NUMBER - _ _ -- - _ -- -- - - -- __ -- _ - -_ -- -_ - - -- _ - _ -- LCN0g2H4I3 LCHOg2H4B TOTAL COOLING CAPACITY BTUH 80,000 901 000 65 635 _SENSIBLE _HEAT CAPACITY STUN___ TONS- - - - - - -- - - - -- -- - - - - -- - - -- - -- - -- -- - -- - - 7 -5 -- -- -- - - - - -7.5 - -- CFM SUPPLY AIR - - -- -- - - - - - - - 31000 CFM OUTDOOR AIR 300 400 - -- - -- - - -- - - - - -- - - - - -- - -- - - - -- - -- - - - -- - - - - - - - - -- - - - - - -- -- - - - - - - - - -- - EXTERNAL STATIC PRESSURE EVAP._FAN H.P, - -- -- - - -- - - -- -- - -- - - - - 3.0 - - - - -- -3.0 E.E.R. -- - - - - 12.7 12.7 -------------- - - - - -- - - - -- - - - -- - - - - - -- - -- -- - - - - - - -- - - - - -- - -- - --- - - - - -- NUMBER OF COMPRESSORS - - - -- -- - - - - - - -- - - - - 2- 2 - - - - -- - - - - -- - -- - -- - - - - -- -- - -- - -- INTEGRATED PART LOAD VALUE 12.8 12.q ------------- - - - - -- - - -- ------- - - - - -- - - - -- ---------- - - - - -- ------------------------ KW (ELECTRIC) FACTORY STRIP NEAT 15.0--@ 230V___ -15.0 @-230V- UNIT WEIGHT (LBS) - - - - -- -- - - - - - -- - _ ELECTRICAL SERVICE _• 208/230/3/60 _ 208/230/3/60 -- _- MINIMUM CIRCUIT AMPS 53.0/58.0 53.0/5q.0 - - -- ------------------------------ - - - - -- - - - - - -- - - - - -- - - -- -- - - - - - - -- --------- - - - - -- - - -- - - -- MAXIMUM FUSE AMPS 60.0 /60.0 60.0/60.0 NOTES: I. UNITS WEIGHTS INCLUDES ROOF CURB AND OUTSIDE AIR HOOD. 2. FURNISH WITH MANUAL OUTSIDE AIR DAMPERS WITH FILTER SCREENS. 3. ELECTRICAL DISCONNECT SWITCH PROVIDED BY ELECTRICAL CONTRACTOR. 4. EACH PACKAGE A/C UNIT SHALL HAVE A U.L. LISTED FACTORY INSTALLED SMOKE DETECTOR IN THE SUPPLY AIR SECTION OF EACH UNIT. SMOKE DETECTORS SHALL BE INNOVAIR MODEL# DHIOOACDCI OR EQUAL. EACH A/C DUCT SMOKE DETECTOR TO HAVE AN AUDIBLE ALARM WITH VISIBLE SIGNAL TROUBLE LIGHT AND SHUT -OFF UNIT AUTOMATICALLY. 5. RTUS #1 AND #2 SHALL HAVE LENNOX "UMIDITROL FACTORY OPTION 6. RTUS #1 AND #2 SHALL HAVE FACTORY INSTALLED CONDENSER AND EVAPORATOR COIL COATING O PROTECTION OPTION. 7. PROVIDE RTU WITH MOTORIZED VOLUME DAMPERS WIT" SHUT -OFF DAMPER TO CONTROL OUTSIDE AIR INTAKES IN ACCORDANCE WITH FBC -B 13- 40q.AB3.3. 8. ROOFTOP A/C UNITS AND ROOF CURBS TO RESIST 146 MPH WINDS. SEE MOUNTING DETAIL ON DRAWING SHEET M2.0. q. RTU SHALL BE PROVIDED WIT" AUXILIARY DRAIN FLOAT SWITCH TO SHUT -OFF EQUIPMENT IN ACCORDANCE WITH FBC -M 307.2.3.1. HVAC DESIGN REQUIRES: YES NO DUCT SMOKE DETECTOR _ • FIRE DA r - FIRE-DAMPER(5) -- - -- - SMOKE DANPER(S_)__ • FIRE RATED ENCLOSURE _ • FIRE RATED ROOF /FLOOR • CEILING ASSEMBLY - - - -- ----------- - - - - -- - -- - - -- - - - -- FIRE _STOPPING _ • SMOKE CONTROL - -- - - EXCEPT IN FIRE RATED WALL FOR JANITOR'S CLOSET LEGEND LEGEND MAY CONTAIN ITEMS NOT USED IN THIS BUILDING - CONTRACTOR TO VERIFY I- VOLUME DAMPER O THERMOSTAT (WALL MOUNTED) HS HUMIDITY SENSOR (RETURN DUCT MOUNTED) ORS REMOTE TEMP SENSOR (RETURN DUCT MOUNTED) SUPPLY DIFFUSER - f ®~ ARROWS INDICATE FLOW RETURN /EXHAUST AIR DIFFUSER F.D. RADIATION /FIRE DAMPER /A-i\ DIFFUSER 45o SYMBOL- NUMBER/CFM RTU -2 A/C UNIT OR FAN NUMBER ROUND OR RECTANGULAR METAL DUCT FLEX DUCT FACTORY INSTALLED SD DUCT SMOKE DETECTOR ACCESS DOOR SD SMOKE DETECTOR REMOTE ALARM/TROUBLE STATION wz z i � � I n v Q O v O IL H - O V V U) n v � P z v � v Z � OC O{-- Q O ru z O tL d > m Q CIS o m O ILV � W.� c• ac oc � 0 °• �. Ix4) 0 V *� Z 0 _ aw L C L ' 0 0 c C .y N. ro �o 0 C9 - 1 r 0 cl M a 0 0 a- 00x1ft niiiiiiism 0 1: MINI Cc CC of . � 1 ) _o -_ _i ti•• �! ce_ � cc'�'•' 0 Qo �+ W - • _ 0 uY W 4_ N N I. 0 - U-1 u- e D aWC °L 0 s Ao •- > �C O <e> 1V Z w (�1 %3 no 0 Z -_ O O .■ C N >1 .D W d r Z •-• - ®3 0 0 0 a �:.■a� 4)