11-626R-021GENERAL ELECTRICAL NOTES
1. ALL WORK SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE,
FLORIDA BUILDING CODE AND OTHER APPLICABLE CODES AND STANDARDS.
2. a) THE DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS AND
BOXES REQUIRED TO MAKE A COMPLETE NEAT INSTALLATION IN ACCORDANCE WITH
N.E.C.
b) WHEN CONFLICTS ARISE IN LOCATIONS WIRING DEVICES, ELECTRICAL EQUIPMENT,
DISCONNECTS, PANELBOARDS, ETC. DUE TO FIELD CONDITION OR IMPROPER FIELD
COORDINATION CONTRACTOR SHALL BRING IT TO THE A/E'S ATTENTION AND AT NO
EXTRA COST RELOCATE, AND OR EXTEND WITHIN A REASONABLE DISTANCE SUCH ITEM
WHICH IS IN CONFLICT. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING
LOCATION OF ALL COMPONENTS PRIOR TO ROUGH IN WITH ALL TRADES NO EXTRAS WILL
BE ALLOWED FOR FAILURE TO DO SO.
3. THE CONTRACTOR IS RESPONSIBLE FOR EVALUATING FIELD CONDITIONS BY VISITING THE
SITE PRIOR TO COMMENCING / BIDDING WORK.
4. THE CONTRACTOR SHALL SATISFACTORILY REPAIR / REPLACE EQUIPMENT OR PART OF
STRUCTURE DAMAGED AS A RESULT OF HIS WORK. SURFACES AND FINISHED AREAS
SHALL BE RESTORED TO MATCH ADJACENT AREAS.
5. ALL DEVICE BOXES SHALL BE INSTALLED FLUSH AND CONDUITS RUN CONCEALED IN
FINISHED AREAS EXCEPT AS SPECIFICALLY SHOWN /NOTED OTHERWISE.
6. ALL ELECTRICAL EQUIPMENT SHALL BE REMOVED FROM STRUCTURE TO BE REMOVED.
ACCESSIBLE RACEWAYS, WIRES, BOXES, SWITCHES AND OTHER ELECTRICAL ITEMS
ASSOCIATED WITH THIS WORK SHALL BE REMOVED IF NOT REQUIRED FOR NEW
EQUIPMENT TO CONTINUE IN SERVICE.
7. WIRE SHALL BE REMOVED BACK TO SOURCE FROM INACCESSIBLE RACEWAYS NOT
REUSED. INSTALL BLANK PLATES ON FLUSH OUTLETS NOT REUSED. OLATE COLOR SHALL
MATCH ADJACENT SURFACE AS NEAR AS POSSIBLE IN FINISHED AREAS.
8. a) MODIFY AND REROUTE EXISTING WIRING AS REQUIRED TO ACCOMPLISH INDICATED
WORK AND CONTINUE SERVICE TO LOADS BEYOND AREA IN WHICH WORK IS DONE.
b) CONTRACTOR SHALL RE -USE EXISTING SPARE BRANCH CIRCUIT BREAKER AND/OR
EXISTING BRANCH CIRCUITS PRESENTLY SERVING ELECTRICAL DEVICES BEING REMOVED
IN AREAS BEING REMODELED. ACTUAL CIRCUIT NUMBERS MAY VARY FROM ACTUAL
FIELD CONDITIONS BUT ARE SHOWN TO FACILITATE CIRCUITING LAYOUT.
9. INSTALL POWER AND CONTROL WIRING AND REQUIRED CONTROL COMPONENTS FOR AIR
CONDITIONING SYSTEM AS SHOWN NOTED ON THESE DRAWINGS AND PER OTHER
APPLICBLE DRAWINGS / INSTRUCTIONS. SEE AIR CONDITIONING DRAWING.
10. ALL MATERIAL REMOVED SHALL BE SISPOSED OF AS DIRECTED BY OWNER.
11. ALL WIRING INDICATED AS EXISTING IS BASED ON ORIGINAL CONTRACT DRAWINGS AND
IS TO BE VERIFIED BY CONTRACTOR AT JOB SITE.
12. WIRE SIZE SHALL BE # 12 THHN / THWN UNLESS OTHERWISE NOTED ON PLANS.
13• ALL CONDUCTORS SHALL BE COPPER RUN IN METALLIC CONDUIT.
14. ALL CONDUCTORS SHALL BE RUN IN CONDUIT METALLIC TYPE). IF PVC SCHEDULE 40 IS
USED FOR UNDERGROUND FEEDERS ONLY, AN QUIPMENT GROUND CONDUCTOR SIZED IN
ACCORDANCE WITH N.E.C. 250 -122 MUST BE INSTALLED AND CONDUIT SIZE INCREASED AS
REQUIRED.
15. ALL MATERIALS SHALL BE U.L APPROVED.
16. NEW TYPEWRITTEN PANEL TALLY SHALL BE FURNISHED AFTER JOB IS COMPLETED.
17. ALL BRANCH CIRCUITS SHALL BE PROPERLY PHASE BALANCED.
18. ALL NON POWER RELATED WIRING I N CEILING AIR CONDITIONING PLENUM RUNNING
WITHOUT CONDUIT SHALL BE TEFLON COATED CLASSIFIED FOR USE IN PLENUMS.
19. ALL EXISTING LUMINARIES TO BE REUSED SHALL BE THOUGHLYCLEANED AND
RELAMPED.
20. ALL BRANCH CIRCUITS TO HAVE A GREEN EQUIPMENT GROUNDING CONDUCTOR SIZED AS
PER N.E.C. 250.122.
21. ALL DEVICES IN EXISTING WALLS NOT AFFECTED BY NEW CONSTRUCTION SHALL REMAIN ACTIVE.
22 ALL EMPTY CONDUITS TO BE PROVIDED WITH NYLON PULL STRINGS.
23. FUSES SHALL BE DUAL ELEMENT, TIME DELAY TYPE UNLESS OTHERWISE NOTED.
24. A/C EQUIPMENT WIRING, BREAKER AND FUSE SIZES ARE BASED ON A/C EQUIPMENT
SPECIFIED ON CONTRACT DRAWING. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL
WIRING, BREAKER AND FUSES SIZES IN ACCORDANCE WITH A/C EQUIPMENT NAMEPLATE
REQUIREMENTS IF DIFFERENT FROM THAT SPECIFIED ON DRAWINGS, AS WELL AS ANY
FEEDER CHANGES BEING AFFECTED BY THIS CHANGE CONTRACTOR SHALL MAKE ABOVE
MENTIONED CHANGES AT NO EXTRA COST.
25. CONTACTOR SHALL COORDINATE ALL HIS WORK WITH OTHER TRADES IN ORDER TO
FURNISH AND INSTALL ALL CONTROL WIRING AND RACEWAYS, ALL POWER CONTROL
CIRCUIT WIRING AND RACEWAY AS SHOWN ON THE AIR CONDITIONING DRAWING OR
SPECIFICATIONS. IF AIR CONDITIONG DRAWING REFER TO MANUFACTURER ALL
REQUIREMENT AND INCLUDE ALL RELATED WORK IN HAS CONTACT.
26. ALL LUMINARIES SHALL BE PROPERLY SUPPORTED IN ACCORDANCE WITH THE CEILING
SYSTEM MANUFACTURER RECOMMENDATIONS AND LOCAL CODE REQUIREMENTS.
27. RISERS ARE DIAGRAMMATIC ONLY. THEY DO NOT SHOW EVERY BEND REQUIRED FOR THE
INSTALLATION.
28. THIS DRAWING IS A GUIDE FOR THE ELECTRICAL INSTALLTION. THE ELECTRICAL
CONTRACTOR IS RESPONSIBLE TO PROVIDE A FUNCTIONING SYSTEM.
29. ALL CABLES SHALL BE RUN WITH OUT SPLICES EXCEPT IF OTHERWISE INDICATED.
30. ALL PULL AND JUNCTION BOXES SHAL BE ACCESSIBLE AT ALL TIMES.
31. EXACT POINT AND METHODS OF CONNECTION SHALL BE DETERMINED IN FIELD.
32. ALL WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER.
33. ALL LOADS IN EXISTING PANELBOARDS ARE ESTIMATED.
34. ALL RACEWAY ROUTED, INSULATED CONDUCTORS SYSTEM SHALL BE COLOR CODED AS
FOLLOWS:
120/240 V SYSTEM
PHASE 'A' BLACK
PHASE 'B' RED
NEUTRAL WHITE
GROUND GREEN
TYPE: SQ'D MTG: FLUSH MOUNTED NEW PANEL 'A' I22K A I CI BUS VOLTS: 1225 240V, 10, 3W
MAIN: M.L.O CU BUS /GND. BUS LOAD: 42.5KVA/240 = 177.3A
LOAD
COND.
WIRE
TRIP
POLE
DESCRIPTION
CKT No.
CKT No.
DESCRIPTION
POLE
TRIP
WIRE
COND.
LOAD
900
1/2"
12
20
1
2ND FL LIGHTS
1
2
GND FL. LIGHTS
1
20
12
1/2"
900
700
1/2"
12
20
1
2ND FL. LIGHTS
3
4
900
720
1/2"
12
20
1
GROUND FLOOR RECEPTS
5
6
800
900
7
8
1000
720
9
10
GND FL RECEPTS
900
720
11
12
900
720
13
14
720
720
15
16
720
1000
2ND FLOOR LIGHTS
17
18
EXTERIOR RECEPTS
720
--
--
--
SPARE
19
20
EXISTING 2ND FL RECS
720
--
--
--
21
22
EXISTING 2ND FL RECS
720
--
--
--
23
24
EXISTING SPRINKLER PUMP
1
30
10
3/4"
2100
--
--
--
25
26
SMOKE DUCT DETECTOR
1
20
12
1/2"
200
27
28
SPARE
1
20
--
--
--
--
--
--
29
30
SPARE
1
20
--
--
--
11256
1 1/4"
4
7
2
NEW AHU #1 ( * *)
31
32
NEW CU #1 ( * *)
2
60
6
1"
6600
--
--
--
33
34
--
--
--
7500
3/4"
6
5
2
EXISTING AHU ( * *)
35
36
EXISTING CU ( * *)
2
40
4
3/4"
4800
--
--
--
37
38
--
--
--
7500
3/4"
6
5
2
EXISTING AHU ( * *)
39
40
EXISTING CU ( * *)
2
40
4
3/4"
4800
--
--
--
41
1 42
--
--
--
COOLING & HEATING LOADS ARE NON- CONCURRENT - PROVIDE HACR TYPE BREAKER.
NEW 2P -200A SERVICE
RATED (42K AIC) MAIN
ENCLOSED BREAKER
NEW 1 #4(G) -3/4 "C
TO (2) 5/8" DIAX101
LONG COPPER CLAD
STEEL GROUND DRIVE
RODS SPACED 6Ff
APART & C.W.P.
� I
' I
I
I
3 #3/0 -2 "C
EXISTING 3 #3/0 -2 "C FPL
OVERHEAD SERVICE TO REMAIN.
i
1 NEW 3 #3/0 & 1 #6(G) -2 "C
1
I
I
1
I
I
1
r - -1 - -� r- -iE - -�
I 1 I I
EXISTING EXTERIOR PANEL
'F 4", ;.� TO BE REMOVED WITH ALL
ASSOCIATED WIRING
I I
I I I I
aC
I
_ EXISTING GROUND
EXISTING FPL TO BE REMOVED
METER TO MAIN
NEW
PANEL
"A"
ELECTRICAL RISER DIAGRAM
N.T.S.
o.
R;fr 91R11DA
JMM Consulting Engineers LLC
Certificate OF Authorization #9692
Jose M. Martinez, P.E. #56018
8353 SW 124 St. Suite 108 TEL (305) 255 -1621
Miami, Florida 33156 FAX (786) 467 -0815
TO THE BEST OF MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED
HEREWITH COMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE
APPLICABLE BUILDING CODES. THIS DRAWING IS THE SOLE PROPERTY OF
'JMM CONSULTING ENGINEERS LLC' AND IS AN INSTRUMENT OF SERVICE NOT TO BE
REPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSION
OF JMM CONSULTING ENGINEERS, LLC.
PROJECT No. 11009
Office Remodeling
6361 Sunset Drive
South Miami, F1 33143
OWNER
OGV Sunset Holdings LLC
8400 NW 66 St.
Doral A 33166
STRIBUTIONT__.� DA'TET
®OWNER'S REVISION 06/29/12
Pablo Corazzini I AR - 91716
Luigi Vitalini I AR - 13513
N, � I **..o vitalinicorazzini
A R C H I T E C T S
300 Aragon Avenue, Suite 330 1 Coral Gables, FL 33134
tel: 305.567.0602 1 fax: 305.446.3197 1
www.vcmiami.com FL Registration AA26001654
SHEET NO.
E -3