11-626R-007L— Air System -Qi-,in- Summary for EXIST. AHU-3 I Project Name: DORAL IMAGING INSTITUTE 07/11/12 Prepared by: JMM CONSULTING 10:46 AM Air System Information System Name —EXIST. AHU-3 Equipment Class —SPIT AHU Number of Zones System Type —SZCAV Floor Area 532.0 ft2 Sizing Calculation Information Zone and Space Sizing Method: Zone CFM Peak zone sensible load Space CFM —Coincident space loads Central Cooling Coil Sizing Data _9113 BTU/hr Total coil load —2.4 Tons Sensible coil load 1.9 Tons Coil CFM at Oct 140Q_1071 CFM Max possible CFM 1071 CFM Design supply temp. 555.0 'F ft2fTon 117.2 BTU/hr/ft2 55.3 Water flow @ 10.0 *F rise gpm Central Heating Coil Sizing Data Max coil load _9113 BTU/hr Coil CFM at Des Htg--1 071 CFM Max possible CFM 1071 CFM Water flow @ 20.0 *F drop gpm Supply Fan Sizing Data Actual max CFM at Oct 1400_1 071 CFM Standard CFM 1070 CFM Actual max CFWft2 9.01 CFM/ft2 Outdoor Ventilation Air Data Design airflow CFM 55 CFM CFMtft2 0.10 CFM1ft2 Calculation Months Jan to Dec Sizing Data _Calculated Load occurs at _Oct 1400 OADB/WB 86.7/74.9 °F Entering D13 / WI3 77.8 166.0 'F Leaving DB / WI3 58.1157.1 *F Coil ADP 56.0 'F Bypass factor 0.100 Resulting RH CA % Zone T-stat Check I of I OK Load occurs at Des Htg BTU/hr/ft2 17.1 Ent. DB / Lvg DB 68.3176.2 *F Fan motor BHP 0.00 BHP Fan motor kW 0.00 kW Fan static 0.00 in. wg. CFM/person 10.34 CFM/person Carrier Hourly Analysis Program v4.04 Page 7