11-626R-006Air System Design Load Summary for EXIST. AHU-2 Project Name: DORAL IMAGING INSTITUTE 07/11/12 Prepared by: JMM CONSULTING 10:46 AM Carrier Hourly Analysis Program v4.04 Page 6 DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 1600 HEATING DATA AT DES HTG COOLING OA DB I WB 90.7 *F 176.9 *F HEATING OA DB /-WB-- 46.0 *F 138.6 *F Sensible Latent Sensible Latent ZONE LOADS Details (BTU/hr) (BTU/hr) Details (BTU/hr) (BTU/hr) Solar Loads 90 ft2 3048 - go ft2 Wall Transmission 870 ft2 2766 - 870 ft2 2678 Roof Transmission 667 W 1925 - 667 W 787 Glass Transmission go ft2 1244 - go ft2, 2153 Skvliqht Transmission 0 ft2 0 - 0 ft2 0 - Door Transmission 0 W 0 - 0 ft. 0 - Floor Transmission 0 ft2 0 - 0 ft2 0 - Partitions 0 ft2 0 - o ft. o - Ceiling 0 ft2 0 - 0 ft2 0 - Overhead Li Ig 2881 W 9831 - 0 0 - Task Lia��.. 334 W 1138 - 0 0 - Electric Equipment 0 w 0 - 0 0 - FP—eople 5 1135 950 0 0 0 Infiltration - 0 0 0 0 0 Miscellaneous 0 3000 0 0 Safety Factor 5%/5% 1054 197 5% 281 0 — Total Zone Loads 22141 4147 - 5899 0 Zone Conditioning - 21160 4147 - 5640 0 Plenum Wall Load 0 %® 0 - 0- 0 - Plenum Roof Load 0 %® 0 0- 0 - Plenum Lighting Load 0% 0 - 0 0 - Return Fan Load 1026 CF IV 0 1026 CF IV 0 - Ventilation Load 50 CF IV 707 1464 50 CF M 1269 0 Supp!y Fan Load 1026 CF IV 6— - 1026 CF M 0 - Space Fan Coil Fans --o - - 0 Duct Heat Gain / Loss 0% 0 - 0% 0 - >> Total System Loads - 21868 5612 6909 0 Central Cooling Coil 218681 5613 0 0 Central Heating Coil 01 - 6909 - >> Total Conditioning 2186:81 6613 6909 0 Key: Positive values are cig loads Positive values are ht9 loads Negative values are ht-q loads Ne ative values are cl loads Carrier Hourly Analysis Program v4.04 Page 6