11-626R-004Sizing Calculation Information Zone and Space Sizing Method: Zone CFM Peak zone sensible load Space CFM Coincident space loads Central Cooling Coil Sizing Data 6909 BTU/hr Total coil load 13 Tons Sensible coil load 1.8 Tons Coil CFM at Jul 1600-1026 CFM Max possible CFM 1026 CFM Design supply temp. 555.0 *F ftI/Ton 791.3 BTUIhr/ft2 41.2 Water flow @ 10.0 'F rise gpm Central Heating Coil Sizing Data Max coil load 6909 BTU/hr Coil CFM at Des Htg.-1026 CFM Max possible CFM 1026 CFM Water flow @ 20.0 *F drop -- gPm Supply Fan Sizing Data Actual max CFM at Jul 1600 1026 CFM Standard CFM 1025 CFM Actual max CFMIft2 1.54 CFMIft2 Outdoor Ventilation Air Data Design airflow CFM 50 CFM CFM/ft' 0.07 CFM/ft2 Calculation Months 'an to Dec Sizing Data Calculated Load occurs at — OADB/WB- Entering DB I WB- Leaving DB / WB — Coil ADP Bypass factor — Resulting RH- Zone T-stat Check Jul 1600 90.7176.9 *F 78.2166.1 -F 58.4157.3 *F .56.2 -F ,0.100 53 % .1 of 1 OK Load occurs at Des Htg BTU/hrfft2 10.4 Ent. DB / Lvg DB 68.4174.6 *F Fan motor BHP 0.00 BHP Fan motor kW 0.00 kW Fan static 0.00 in. wg. CFM/person 10.79 CFM/person Carrier Hourly Analysis Program v4.04 Page 4