Loading...
11-626R-003Air System Design Load Summa 1y for NEW AHU-1 Project Name: DORAL IMAGING INSTITUTE 07111112 Prepared by: JMM CONSULTING 10:46 AM Ga�e r Hourly Ana ty s i s Program v4-054 Page 3 DESIGN COOLING DESIGN HEATING COOLING DATA AT Jul 1500 HEATING DATA AT DES HTG COOLING OADBIWB 91.0*F/77.0*F HEATING OADBIWB 46.0*FI38.6*F Sensible Latent Sensible Latent ZONE LOADS Details (BTU /hr l (BTU/hr ) Details (BTU/hr) (BTU/hr) Solar Loads 239 ft2 6901 - 239 ft2 Wall Transmission 1317 ft2 4399 - 1317 ft2 4052 - Roof Transmission 1121 ft2 3692 - 1121 ft2 1322 - Glass Transmission 239 ft2 3341 - 239 ft2, 5745 - Skylight Transmission 0 ft2 0 - 0 ft2 0 - Door Transmission 0 ft2 a - 0 ft2 0 - Floor Transmission 0 ft2 0 - 0 ft2 0 - Partitions 0 W 0 - 0 ft2 0 Ceiling 0 ft2 0 - 0 ft2 0 - Overhead Li htin 3916 W 13361 - 0 0 - Task Lighting 493 W 1680 - 01 0-- - Electric Eguipment ow 0 - 0 0 - People 14 3430 2870 0 0 0 Infiltration - 0 0 0 0 0 Miscellaneous 0 4000 - 0 0 Safe �L Factor 15 5 016 0,16 1 11340 – 344 5% - 556 0 >> Total Zone Loads - 38645 7214 - 11675 0 Zone Condifioniag_ - 37643 7214. - 12183 0 Plenum Wall Load 0% 0 - 0 0 - Plenum Roof Load 0% 0 0 0 Plenum Lighting Load 0% 0 1 0 o------- - Return Fan Load 1798 CF IV 0 - 1798 CF IV 0 - Ventilation Load 130 CF IV 1933 3947 130 CF IV 3335 0 Supp!y Fan Load 1798 & 0 1798 CF M 0 - Space Fan Coil Fans - 0 0 Duct Heat Gain / Loss 0% 0 - O.R. 0 - >> Total System Loads - 39576 11160 - 15518 0 Central Cooling Coil 39576 11162 - 0 0 Central Heating Coil 0 - - 15518 - >> Total Condigqq!gq — ----------- L 39576 11162 - 15518 0 Key: Positive values are cIg loads Positive values are htg loads Negative values are htq loads Negative values are cIq loads Ga�e r Hourly Ana ty s i s Program v4-054 Page 3