11-626R-001Air System Sizing Summary far NEW AHU -1 _ Project Name: DORAL IMAGING INSTITUTE 07111/12 Prepared by: JMM CONSULTING 10:46 AM Air System Information System Name NEW AHIJ-1 Equipment Class SPLTAHIJ System Type 0ZCAV Sizing Calculation Information Zone and Space Sizing Method: Zone CFM Peak zone sensible load Space CFM Coincident space loads Central Cooling Coil Sizing Data Jul 1500 Total coil load 1.2 Tons Sensible coil load 1.3 Tons Coil CFM at Jul 150Q-1798 CFM Max possible CFM 1798 CFM Design supply temp. 55.0 *F ft'/ Ton 396.6 BTU/hrtft2 30.3 Water flow@ 10.0 *F rise _- gpm Central Heating Coil Sizing Data Max coil load 15518 BTU/hr Coil CFM at Des Htg-1798 CFM Max possible CFM 1798 CFM Water flow @ 20.0 *F drop gpm Supply Fan Sizing Data Actual max CFM at Oct 1400-1798 CFM Standard CFM 1798 CFM Actual max CFWft2 1.07 CFWft2 Outdoor Ventilation Air Data Design airflow CFM CFM/ft2 130 CFM 0.08 CFM/ft2 Number of Zones I Floor Area 1677.0 ft2 Calculation Months Jan to Dec Sizing Data Calculated Load occurs at Jul 1500 0ADB/WI3 91.0177.0 *F Entering DB / WI3 78.2166.0 *F Leaving DB I WB 57.8 156.7 *F Coil ADP 55.6 *F Bypass factor 0.100 Resulting RH 52 % Zone T-stat Check -- I of I OK Load occurs at - Des Htg BTU/hr /ft' _9.3 Ent. D13 / Lvg DB 98.0176.0 'F Fan motor BHP 0.00 BHP Fan motor kW 0.00 kW Fan static 0.00 in. wg. CFM/person 9.29 CFWperson Carrier Hauriy Analysis Program v4.04 Page 1