11-626-035Y GENERAL ELECTRICAL NOTES 1. ALL WORK SHALL BE IN ACCORDANCE WITH NATIONAL ELECTRICAL CODE, COND, FLORIDA BUILDING CODE AND OTHER APPLICABLE CODES AND STANDARDS. 2. a) THE DRAWINGS ARE DIAGRAMMATIC AND DO NOT SHOW ALL OFFSETS, BENDS AND y BOXES REQUIRED TO MAKE A COMPLETE NEAT INSTALLATION IN ACCORDANCE WITH CKT No. N.E.C. b) WHEN CONFLICTS ARISE IN LOCATIONS WIRING DEVICES, ELECTRICAL EQUIPMENT, WIRE DISCONNECTS, PANELBOARDS, ETC. DUE TO FIELD CONDITION OR IMPROPER FIELD LOAD COORDINATION CONTRACTOR SHALL BRING IT TO THE A /E'S ATTENTION AND AT NO 3/4" EXTRA COST RELOCATE, AND OR EXTEND WITHIN A REASONABLE DISTANCE SUCH ITEM 25 WHICH IS IN CONFLICT. THE CONTRACTOR IS RESPONSIBLE FOR COORDINATING NEW AHU #4 /CU #4 ( *) LOCATION OF ALL COMPONENTS PRIOR TO ROUGH IN WITH ALL TRADES NO EXTRAS WILL 2 BE ALLOWED FOR FAILURE TO DO SO. 3. THE CONTRACTOR IS RESPONSIBLE FOR EVALUATING FIELD CONDITIONS BY VISITING THE 10 SITE PRIOR TO COMMENCING / BIDDING WORK. 4. THE CONTRACTOR SHALL SATISFACTORILY REPAIR / REPLACE EQUIPMENT OR PART OF -- STRUCTURE DAMAGED AS A RESULT OF HIS WORK. SURFACES AND FINISHED AREAS SHALL BE RESTORED TO MATCH ADJACENT AREAS. 5. APPROVAL SHALL BE OBTAINED FROM A STRUCTURAL ENGINEER PRIOR TO CUTTING OR 4 DRILLING ANY STRUCTUALSUPPORT MEMBER. 6. ALL DEVICE BOXES SHALL BE INSTALLED FLUSH AND CONDUITS RUN CONCEALED IN 3 FINISHED AREAS EXCEPT AS SPECIFICALLY SHOWN /NOTED OTHERWISE. 7. ALL ELECTRICAL EQUIPMENT SHALL BE REMOVED FROM STRUCTURE TO BE REMOVED. 3/4" ACCESSIBLE RACEWAYS, WIRES, BOXES, SWITCHES AND OTHER ELECTRICAL ITEMS 30 ASSOCIATED WITH THIS WORK SHALL BE REMOVED IF NOT REQUIRED FOR NEW NEW AHU #6 /CU #6 ( *) EQUIPMENT TO CONTINUE IN SERVICE. 8. WIRE SHALL BE REMOVED BACK TO SOURCE FROM INACCESSIBLE RACEWAYS NOT 1 REUSED. INSTALL BLANK PLATES ON FLUSH OUTLETS NOT REUSED. OLATE COLOR SHALL 12 MATCH ADJACENT SURFACE AS NEAR AS POSSIBLE IN FINISHED AREAS. 9. a) MODIFY AND REROUTE EXISTING WIRING AS REQUIRED TO ACCOMPLISH INDICATED -- WORK AND CONTINUE SERVICE TO LOADS BEYOND AREA IN WHICH WORK IS DONE. b) CONTRACTOR SHALL RE -USE EXISTING SPARE BRANCH CIRCUIT BREAKER AND /OR TVSS EXISTING BRANCH CIRCUITS PRESENTLY SERVING ELECTRICAL DEVICES BEING REMOVED 8 IN AREAS BEING REMODELED. ACTUAL CIRCUIT NUMBERS MAY VARY FROM ACTUAL 1 FIELD CONDITIONS BUT ARE SHOWN TO FACILITATE CIRCUITING LAYOUT. 10. INSTALL POWER AND CONTROL WIRING AND REQUIRED CONTROL COMPONENTS FOR AIR -- CONDITIONING SYSTEM AS SHOWN /NOTED ON THESE DRAWINGS AND PER OTHER 100 APPLICBLE DRAWINGS / INSTRUCTIONS. SEE AIR CONDITIONING DRAWING. 11. ALL MATERIAL REMOVED SHALL BE SISPOSED OF AS DIRECTED BY OWNER. 12. ALL WIRING INDICATED AS EXISTING IS BASED ON ORIGINAL CONTRACT DRAWINGS AND 9 IS TO BE VERIFIED BY CONTRACTOR AT JOB SITE. 13. MINIMUM WIRE SIZE SHALL BE # 12 THHN / THWN UNLESS OTHERWISE NOTED ON PLANS. 14. ALL SHALL BE THWN. 15. ALL CONDUCTORS SHALL BE COPPER RUN IN METALLIC CONDUIT. 16. ALL CONDUCTORS SHALL BE RUN IN CONDUIT METALLIC TYPE). IF PVC SCHEDULE 40 IS 7 USED FOR UNDERGROUND FEEDERS ONLY, AN EQUIPMENT GROUND CONDUCTOR SIZED IN -- ACCORDANCE WITH N.E.C. 250 -122 MUST BE INSTALLED AND CONDUIT SIZE INCREASED AS 20 REQUIRED. 17. ALL MATERIALS SHALL BE U.L. APPROVED. 12 -- 18. NEW TYPEWRITTEN PANEL TALLY SHALL BE FURNISHED AFTER JOB IS COMPLETED. 19. ALL BRANCH CIRCUITS SHALL BE PROPERLY PHASE BALANCED. 20, CONTRACTOR TO REMOVE AND /OR REPLACE CIRCUIT BREAKERS IN EXISTING PANEL TO SPACE OBTAIN AMOUNT REQUIRED AS A MINIMUM PER PANEL SCHEDULE. ALL EXISTING EXCESS -- BREAKERS, IF ANY, TO REMAIN AS SPARE. 21. ALL NON POWER RELATED WIRING I N CEILING AIR CONDITIONING PLENUM RUNNING -- WITHOUT CONDUIT SHALL BE TEFLON COATED CLASSIFIED FOR USE IN PLENUMS. ' 22. PROVIDE TRAPEZE HANGER AS ASSEMBLE FOR PLENUM COMMUNICATION CABLE WITH SPACE 3/8" DIAMETER. THREADED ROD AND CHANNEL ASSEMBLY TO SUPPORT CABLE BUNDLES 1 EVERY 4 FT. O.C. (MAXIMUM CABLES SHALL NOT LIE ON TOP OF CEILING TILE OR LUMINARIES). 23. SEE ARCHITECTURAL DRAWING FOR INFORMATION CONCERNING EXISTING CONDITIONS AND COUNTER DETAILS. 24. ALL BRANCH CIRCUITS TO HAVE A GREEN EQUIPMENT GROUNDING CONDUCTOR SIZED AS r PER N.E.C. 250.122. 25. ALL DEVICES IN EXISTING WALLS NOT AFFECTED BY NEW CONSTRUCTION SHALL REMAIN -- ACTIVE. 26 ALL EMPTY CONDUITS TO BE PROVIDED WITH NYLON PULL STRINGS. 27. FUSES SHALL BE DUAL ELEMENT, TIME DELAY TYPE UNLESS OTHERWISE NOTED. ` -- 28. A/C EQUIPMENT WIRING, BREAKER AND FUSE SIZES ARE BASED ON A/C EQUIPMENT - SPECIFIED ON CONTRACT DRAWING. CONTRACTOR IS RESPONSIBLE FOR PROVIDING ALL 18 WIRING, BREAKER AND FUSES SIZES IN ACCORDANCE WITH A/C EQUIPMENT NAMEPLATE " REQUIREMENTS IF DIFFERENT FROM THAT SPECIFIED ON DRAWINGS, AS WELL AS ANY FEEDER CHANGES BEING AFFECTED BY THIS CHANGE CONTRACTOR SHALL MAKE ABOVE MENTIONED CHANGES AT NO EXTRA COST. r 29. CONTACTOR SHALL COORDINATE ALL HIS WORK WITH OTHER TRADES IN ORDER TO FURNISH AND INSTALL ALL CONTROL WIRING AND RACEWAYS, ALL POWER CONTROL CIRCUIT WIRING AND RACEWAY AS SHOWN ON THE AIR CONDITIONING DRAWING OR SPECIFICATIONS. IF AIR CONDITIONG DRAWING REFER TO MANUFACTURER ALL 13 REQUIREMENT AND INCLUDE ALL RELATED WORK IN HAS CONTACT. 30. ALL LUMINARIES SHALL BE PROPERLY SUPPORTED IN ACCORDANCE WITH THE CEILING 1 SYSTEM MANUFACTURER RECOMMENDATIONS AND LOCAL CODE REQUIREMENTS. 31. RISERS ARE DIAGRAMMATIC ONLY. THEY DO NOT SHOW EVERY BEND REQUIRED FOR THE INSTALLATION. 32. THIS DRAWING IS A GUIDE FOR THE ELECTRICAL INSTALLTION. THE ELECTRICAL CONTRACTOR IS RESPONSIBLE TO PROVIDE A FUNCTIONING SYSTEM. 33. ALL CABLES SHALL BE RUN WITH OUT SPLICES EXCEPT IF OTHERWISE INDICATED. 34. ALL PULL AND JUNCTION BOXES SHAL BE ACCESSIBLE AT ALL TIMES. 35. EXACT POINT AND METHODS OF CONNECTION SHALL BE DETERMINED IN FIELD. 36. ALL WORK SHALL BE DONE IN A NEAT AND WORKMANLIKE MANNER. 37. ALL LOADS IN EXISTING PANELBOARDS ARE ESTIMATED. 38. ALL RACEWAY ROUTED, INSULATED CONDUCTORS SYSTEM SHALL BE COLOR CODED AS FOLLOWS: 1 120/208 V SYSTEM PHASE K PHASE B' RED PHASE 'C' BLUE NEUTRAL WHITE GROUND GREEN 277/480 V SYSTEM PHASE 'A' BROWN PHASE 'B' PURPLE PHASE 'C' YELLOW 17 NEUTRAL GRAY GROUND GREEN TYPE: SIEMENS PI NEW PANEL •AC" 42 KAICI BUS: UT: 10200A/2QaV, 30, 4W MTG: FLUSH MOUNTED MAIN: M.L.O CU BUS /GND. BUS LOAD: 14.2 KVA /360V =39.4A LOAD COND, WIRE TRIP POLE DESCRIPTION CKT No. CKT No. DESCRIPTION POLE TRIP WIRE COND. LOAD 3,652 3/4" 10 25 2 NEW AHU #4 /CU #4 ( *) 1 2 NEW AHU #5 /CU #5 ( *) 2 25 10 3/4" 3,652 ! • • -- -- (112.5 KVA) 3 4 1 3 4 -- 3,092 3/4" 10 30 2 NEW AHU #6 /CU #6 ( *) 5 6 EXTERIOR RECEPTACLES 1 20 12 1/2" 200 -- -- -- 40/] 1 TVSS 7 8 SPARE 1 20 1 1 -1/2' -- 720 100 1/2" 12 15 1 WARNING LIGHT 9 10 1 20 -- 1 -- -- 7 700 -- -- 20 1 SPARE 11 12 -- -- 1 20 -- -- -- SPACE 13 -- -- -- -- -- SPARE 13 14 SPACE --- 1 -- 15 16 15 16 -- -- -- -- __ -- -- _� __ -- -- -- 17 18 NOTE: ALL BRANCH BREAKERS TO BE RATED FOR 42K AIC. 1. ( *) PROVIDE HACR TYP. BREAKER ELECTRICAL SYMBOL LEGEND FO ® WALL OR CEILING MOUNTED EXIT LIGHT FIXTURE WITH BATTERY BACK -UP. ARROWS, NUMBER OF FACES AND MOUNTING AS REQUIRED TO INDICATE A CLEAN PATH TO EXIT. N$N 120/277 V., 20 AMP., SINGLE POLE LIGHT SWITCH. $ 3 120/277V„ 20 AMP., THREE WAY SWITCH. $ M MANUAL MOTOR STARTER. ELECTRICAL PANEL ❑J FUSED DISCONNECT SWITCH SIZED PER EQUIPMENT NAMEPLATE. ® MAGNETIC MOTOR STARTER, PROVIDED BY MECHANICAL CONTRACTOR, INSTALLED BY ELECTRICAL CONTRACTOR. 4 ELECTRIC MOTOR. %_ V B EQUIPMENT CONNECTION WITH FLEXIBLE CONDUIT. 20A., 120 V., QUADRUPLEX RECEPTACLE, TWO DUPLEX IN TWO BOX. 18" A.F.F. 20 A., 120., V., DUPLEX RECEPTACLE, GROUNDING TYPE, U.O.N. MOUNTED 18" A.F.F. =8H 20 A., 125 V., HOSPITAL GRADE RECEPTACLE. Q FQ CEILING OR WALL MOUNTED JUNCTION BOX. Q TELEPHONE /DATA OUTLET ACCESSIBLE JUNCTION BOX 3/8" FLEXIBLE CONDUIT.- MAX 6FT. AS PER NEC 348.3 - BRANCH CIRCUIT FINISH SLAB GRID SUPPORT NEXT TO FIXTURE LIGHTING FIXTURE -1 '-- FINISHED CEILING RECESSED FLOURESCENT LT. FIXTURE CONNECTION DETAIL N.T.S. NOTES: 1.- ALL RECESSED LIGHT FIXTURES ARE TO BE CONNECTED AS DETAILED. 2.- ALL JUNCTION BOXES ARE TO BE READILY ACCESIBLE. NEW FPL APPROVED o 600A METER 313 2 RUNS OF (4 #350KCMIL)- 3 -1/2 "C TO FPL SERVICE POLE. BUILDING EXTERIOR 2 RUNS OF 4 #350KCMIL- 3 -1/2 "C (EMT) EACH �2 RUNS OF 4 #350KCMIL do 1 #1/0(G)- 3 -1/2 "C EACH NEW 3P -600A SERVICE RATED i I ENCLOSED MAIN BREAKER 65K AIC. 3R SURGE SUPPRESSOR 1#3/0-1"C TO (2) APT TE /2HP 5/8" DIA. X LOFT. LONG ADJACENTOTOTPANEL COPPER CLAD STEEL GROUND DRIVERS RODS. NEW NEW PANEL PANEL "DP" "AC" •f•• ••Y i • ••••• ••Y POLE DESCRIPTION CKT No. CKT No. DESCRIPTION POLE TRIP WIRE COND. LOAD f • • • • • t r • • v EXISTING CIRCUIT 1 2 EXISTING CIRCUIT 1 r•• •Y• • • • 0090 ! • • TYPE: SIEMENS PI NEW PANEL •A• 110 KAICI BUS: 250A 208V, 30, 4W • ' MTG: FLUSH MOUNTED ' MAIN: M.L 0 CU BUS /GND. BUS LOAD: 45.6KVA/360V= 126.64 ` • LOAD COND. WIRE TRIP POLE DESCRIPTION CKT No. CKT No. DESCRIPTION POLE TRIP WIRE COND. LOAD 700 1/2" 12 20 1 EXISTING CIRCUIT 1 2 EXISTING CIRCUIT 1 20 12 1/2".' •4bO -- -- -- (112.5 KVA) 3 4 1 3 4 -- - 1 -- 5 fi .r -_ -- -- -- 3/4" 8 40/] 1 TVSS 7 5 6 3 100 1 1 -1/2' 10,600 __ -- -- 9 10 -- -- -- 1 - - -- 7 8 11 1 -- -- -- -- -- -- -- -- SPACE 13 14 SPACE -- 1 -- -- 9 10 - - --- 1 -- 15 16 _- -- -- -- -- 1 11 12 1 NOTE: ALL BRANCH BREAKERS TO BE RATED FOR 42K AIC. 1 13 14 1 1 15 16 1 1 17 18 1 1 19 20 1 7,500 1" 6 50 2 EXISTING AHU ( *) 21 22 1 -- -- I -- 23 24 1 7,500 1" 6 50 2 EXISTING AMU ( *) 25 26 1 -- -- -- 27 28 1 7,500 1" 6 60 2 EXISTING AHU /CU ( *) 29 30 EXISTING CU ( *) 2 40 8 3/4" 4,160 -- 31 32 -- -- -- 2,000 3/4" 10 30 1 EXISTING SPRINKLER PUMP 33 34 EXISTING CU ( *) 2 5V 6 1" 5,200 700 1/2" 12 20 1 EXISTING CKT 35 36 -- -- -- 750 1/2" 12 20 1 NEW CT LTS. 37 38 NEW CONTROL ROOM RECS. 1 20 12 1/2" 720 200 1/2" 12 20 1 NEW BATHROOM LTS. 39 40 NEW RECEPTION RECS. 1 20 12 1/2" 720 -- -- -- -- __ SPACE 41 42 SPACE -- -- -- -- -- 1. ( *) COOLING AND HEATING LOADS ARE NON - CONCURRENT. PROVIDE HACR TYP. BREAKER 2. ALL EXISTING CIRCUITS SHALL BE TRACED BY THE CONTRACTOR AND PROPERLY IDENTIFIED IN THE PANEL DIRECTORY. • 1 • • r • r �r•Y• ••• ru•• Y r u r ,000041 ••• • off* • 600A 208V, 30, 4W TYPE: SIEMENS L600FF NEW PANEL •DP' [ 42 KAICI BUS: 600A MTG: FLUSH MOUNTED UNTED MAIN: M.L.O CU BUS /GND. BUS LOAD: 168.7 KVA/360V= 468.6A LOAD COND. WIRE TRIP POLE DESCRIPTION CKT No. CKT No. DESCRIPTION POLE TRIP WIRE COND. LOAD 112,500 2" (2)3/0 400 3 CT SCAN XMER 1 2 NEW PANEL "A" 3 200 310 2" 45,600 -- -- -- (112.5 KVA) 3 4 -- -- -- - -- 5 fi -_ -- -- -- 3/4" 8 40/] 3 TVSS 7 8 NEW PANEL "AC" 3 100 2 1 -1/2' 10,600 __ -- -- 9 10 -- -- -- -- - - -- 11 12 -- -- -- -- -- -- -- -- SPACE 13 14 SPACE -- -- -- -- -- -- - - --- -- -- 15 16 _- -- -- -- -- -- 17 18 NOTE: ALL BRANCH BREAKERS TO BE RATED FOR 42K AIC. 2 RUNS OF 3 #3/0 & 1 #6(G) -2 "C 4 #3/0 do 1 #6(G) -2 "C 4 #2 do 1 #8(G)- 1 -1/2 "C ELECTRICAL RISER DIAGRAM N.T.S. -4 #1 k 1 #1 /0(G) -2 "C TO "Al" MAIN DISCONNECT IN CT SCAN ROOM. (SEE SHEETS BY GE HEALTHCARE SYSTEM.) BUILDING EXTERIOR V NEW PANEL ' ' 3P -90A (25K AIC) "A" ENCLOSED BREAKER. (3R) (3R) 3P -400A ENCLOSED XMER NEMA 3R BREAKER (22K AIC) , .. 4 #1 k 1 #1 /0(G) -2 "C GRADE 2 RUNS OF (3 #3/0 k 1#6(G))-2"C NOTES: 1. ENGINEER ASSUMED A FAULT CURRENT OF 65K AIC. CONTRACTOR SHALL COORDINATE WITH FPL FOR ACTUAL FAULT CURRENT. EQUIPMENT INSTALLED SHALL WITHSTAND FPL'S AVAILABLE FAULT CURRENT. PRIOR TO ORDERING AND BID THE ELECTRICAL SWITCHGEAR THE CONTRACTOR SHALL OBTAIN FROM FPL A LETTER STATING THE AVAILABLE FAULT CURRENT. NO EXTRAS WILL BE ALLOWED FOR FAILURE TO DO SO. 2. ALL EQUIPMENT AND DEVICES SHALL BE MOUNTED ABOVE FLOOR CRITERIA. 3. COORDINATE NEW SERVICE REQUIREMENTS WITH FPL REPRESENTATIVE MR. BRUNO BRAVO (305) 387 -6668 �4" CONCRETE SLAB 1 #2/0 -1 "C STEP -UP XMER IN WEATHER TO A 5/8" DIA. X 1OFT. ENCLOSED 112.5 KVA, 208V, 30- PRIMARY LONG COPPER CLAD STEEL 277/48OV, 30- SECONDARY GROUND DRIVER ROD. .•`Go1S 61 JMM Consulting Engineers LLC Certificate OF Authorization #9692 Jose V. Martinez, P.E. #56018 8353 ST 124 St. Saute 108 TEL (305) 255 -1621 Miami, Florida 33156 FAX (305) 255 -1732 TO THE NEST OE MY KNOWLEDGE, THE PLANS AND SPECIFICATIONS SUBMITTED HEREWITH COMPLY WITH EXISTING INTERPRETATIONS AND PROVISIONS OF THE APPLICABLE BUILDING CODES, THIS DRAWING ' S THE SOLE PROPERTY OF 'JMM CONSULTING ENGINEERS LLC' AND IS AN INSTRUMENT OF SERVICE NOT TO IF REPRODUCED IN WHOLE OR IN PART WITHOUT THE EXPRESS WRITTEN PERMISSION OF JMM CONSULTING ENGINEERS, LLC. 3 PROJECT I No. 11009 Interior Remodeling 6361 Sunset Drive South Miami, FI 33143 OWNER Doral Imaging Institute 7775 NW 48th St Doral Fl 33166 pISTRI�UTION ­­ DATE Pablo Corazzini I AR - 91716 Luigi Vitalini I AR - 13513 s Nl�� vitalinicora zini A R C H I T E C T S 300 Aragon Avenue, Suite 330 1 Coral Gables, FL 33134 tel: 305.567.0602 1 fax: 305.446.3197 1 www.vcmiami.com FL Registration AA26001654 SHEET NO. E-3