Loading...
11-626-017Air Sy tem Sizing Summary for AHU -3 Project Name: DORAL IMAGING INSTITUTE Prepared by: JMM CONSULTING Air System lnformation System Name AHU -3 Equipment Class __.- __... -_..._ -_. -SALT AHU Number of Zones System Type .. -... SZCAV Floor Area _ Sizing Calculation Information Zone and Space Sizing Method: 06/15/11 07:27 AM 1 532.0 ft2 Zone CFM _- _.__._.. __. -_ Peak zone sensible load Calculation Months Jan to Dec Space CFM F Coincident space loads Sizing Data _._. Ca ICU lated Central Cooling Coil Sizing Data 113 BTU /hr Total coil load 2.4 Tons Sensible coil load 1.5 Tons Coil CFM at Oct 1400 1071 CFM Max possible CFM 1071 CFM Design supply temp. 55.0 'F ft2/Ton _.__._..1070 CFM BTU /hr /ft2 __2.01 CFM /ft2 Water flow @ 10.0 `F rise - gpm Central Heating Coil Sizing Data Max coil load 113 BTU /hr Coil CFM at Des Htg __- -_1071 CFM Max possible CFM 1071 CFM Water flow @ 20.0 7 drop - gpm Supply Fan Sizing Data 10.34 CFM /person Actual max CFM at Oct 1400 1071 CFM Standard CFM----,.-.-.- _.__._..1070 CFM Actual max CFM/ft' - __2.01 CFM /ft2 Outdoor Ventilation Air Data Design airflow CFM _. 55 CFM CFM/ft' _ -_ -- --- ........ 0.10 CFM /fe Load occurs at OA De /WB_ - — Entering DB / WB_ Leaving DB / WB Coil ADP Bypass factor ...___ Resulting RH T Zone T -stat Check Load occurs at BTU /h r /ft2 Ent. DB / Lvg DB.. Oct 1400 / 74.9 'F 77.8 /66.0'F 58.1 / 57.1 'F 56.0 'F 0.100 54 1 of 1 OK Des Htg 17.1 6&3176.2 'F Fan motor BHP_ -_ 0.00 BHP Fan motor kW _ - 0.00 kW -�� Fan static 0.00 in. wg. CFM /person 10.34 CFM /person . _._. - -_ Carrier Hourly _ A_ nalysis Program v4.04 �- Page 7